MULTISPAN PIC-38 Owner's manual

Type
Owner's manual

MULTISPAN PIC-38 is a process indicator with a 4-digit, 7-segment, 0.8” red LED display. It has a size of 48 X 96 X 65 mm and a panel cutout of 44 X 92 mm. The input range is 0-10V DC, 0-20mA DC, or 4-20mA DC, and the output is 1 relay, 1 C/O & 24V DC Transmitter. The selectable range is -999 to 9999. It has protection level (As per request) IP-65 (Front side) AS per IS/IEC 60529:2001. The operating temperature is 0°C to 55°C, and the relative humidity is up to 95% RH non-condensing.

The features of the MULT

MULTISPAN PIC-38 is a process indicator with a 4-digit, 7-segment, 0.8” red LED display. It has a size of 48 X 96 X 65 mm and a panel cutout of 44 X 92 mm. The input range is 0-10V DC, 0-20mA DC, or 4-20mA DC, and the output is 1 relay, 1 C/O & 24V DC Transmitter. The selectable range is -999 to 9999. It has protection level (As per request) IP-65 (Front side) AS per IS/IEC 60529:2001. The operating temperature is 0°C to 55°C, and the relative humidity is up to 95% RH non-condensing.

The features of the MULT

PowerSupply
ProtectionLevel
Operating
Relative
(Asperrequest)
Temperature
Humidity
100to250VAC,50/60Hz,Approx4VA
IP-65(Frontside)ASperIS/IEC60529:2001
0°CTo55°C
Upto95%RHNonCondensing
Model
Display
Size(HXWXD)
PanelCutout
Input
Output
Range
PIC-38
48X96X65mm
44X92mm
4Digit7seg0.8”,redLEDDisplay
0-10VDC,0-20mADC,4-20mADC
1Relay1C/O&24VDCTransmitter
-999To9999Selectable
Working
Display
4DigitsDisplayinRedcolorindicatescurrentreadingofPV
1.Whenthepowerissuppliedtotheinstrumentthedisplaywillshowthepresent
PROCESSvalue.
2.TheRangecorrespondingto4to20mADCisselectablefromkeypad.
3.Thesensorwillprovide4to20mADCinputtothecontroller.Thedisplaywill
indicatetheProcessvalueaspertheselectableRangevalue.
4.IftheRangeissetto9999thenat4mADCinputthedisplaywillshow0and20mADC
thedisplaywillindicateselectedrange9999.
5.Ifyouselectloweralarmasamodetheninitiallyrelaywillremaininoncondition.
Whencurrenttemperatureequals(settemperature+HYST)relaywillbeturnoff.
Sotemperaturegoesdownandwhenittouchessettemperaturerelaywillagain
turnON.andthisprocesswillcontinuetoflow.
6.Ifyouselecthigheralarmtheninitiallyrelaywillbeinonconditionsotemperature
goesdownandwhenittouches(settemperature-HYST)valuerelaywillturnoffand
sotemperaturewillgohighandwhenitreachessetvaluerelaywillturnONandcycle
Continues.
7.IftheSLLvalueisbelow3.5mAthandisplayshowLow.
8.AndifSLLvalueisbetween3.5to4.00mA,DisplayShows‘00’.
9.WhentheinputexceedsthefullscaleRange(Approxabove1ADC)Displaywill
showOVER.
OPERATINGMANUAL
ProcessIndicator
PIC-38
Page-1
PIC-38 www.multispanindia.com
R1 R2 ENT
SET
PIC 38
1 2 3 4
Presskey
Presskey
Presskey
Presskey
Presskey
s E T
P A S S
1 2 3
0 0 0 0
H A L L A L In - b O t- B A B - L A B - O
0 0 0 0
H Y S
M O D E
Hystersis
Mode
Password
// / / /
(Range:1to1000Count)
USER CONFIGURATION
PowerON
Press

Press

&keytosetvalue

&keytosetmode

Press

Press

&keytosetvalue

&keytosetpassword

Presskey
Presskey
Presskey
Presskey
d p
I n p
0 0 0 0
Presskey
Presskey
Input
Press

keytosetDecimalpoint

DecimalPoint
0-10VDC
0-20mADC
4-20mADC
0 - 1 0 0 - 2 0
4 - 2 0 Selectbykey
L R N G
H r n g
0 0 0 0
0 0 0 0
Presskey
Presskey
Presskey
Presskey
Press

&keytosetlowrange

Press

&keytosethighrange

LowRange
HighRange
Page-2
PIC-38 www.multispanindia.com
f L T R
O F S T
C R F C
0 0 0 0
0 0 0 0
0 0 0 0
s L L
A 3.5
Presskey
Presskey
Presskey
Presskey
Presskey
Presskey
Presskey
Press

Press

&keytosetfiltertime

&keytosetoffsetcount

Press

Press

(Ifselect4-20mA)
&keytocorrectionfactor

&keytosetsignallowlavel

Filtertime
Offset
CorrectionFactor
SignalLowLevel
(range:±100counts)
(range:0.1secto10.0sec)
(range:±999counts)
PresskeyforSave&Exit
ConnectionDiagram
Page-3
PIC-38 www.multispanindia.com
+
+ +
-
-
12 3 4 5 6 7 8 9 10
0/4-20
mA DC
24V DC
NO C
O/P
NC
0-10V
DC
Range:
-999 To 9999
I/P:
0-10V DC
4-20mA DC
0-20mA DC
LN
~
50/60 Hz
4VA
100
250V AC
!
MadeinIndia
www.multispanindia.com
Product improvement and upgrade is a constant procedure. So for more updated operating information and support,
Please contact our helpline : +91-9978991474/76/82 or Email at [email protected] Ver: 04-2017
Allsafetyrelatedcodifications,symbolsandinstructionsthatappearinthisoperatingmanual
orontheequipmentmustbestrictlyfollowedtoensurethesafetyoftheoperatingpersonnelas
wellastheinstrument.
Ifalltheequipmentisnothandledinamannerspecifiedbythemanufacturer,itmightimpairthe
protectionprovidedbytheequipment.
=> Readcompleteinstructionspriortoinstallationandoperationoftheunit.
WARNING : Riskofelectricshock.
3) Cable used for connection to power source, must have a cross section of 1mm or greater. These wires
should have insulations capacity made of at least 1.5kV.
2) To reduce electro magnetic interference, use wire with adequate rating and twists of the same of equal size shall
be made with shortest connection.
1) To prevent the risk of electric shock power supply to the equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is being supplied.
4) A better anti-noise effect can be expected by using standard power supply cable for the instrument.
1) This equipment, being built-in-type, normally becomes a part of main control panel and such in case the
terminals do not remain accessible to the end user after installation and internal wiring.
2) Do not allow pieces of metal, wire clippings, or fine metallic fillings from installation to enter the product
or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator.
3) Circuit breaker or mains switch must be installed between power source and supply terminal to
facilitate power ‘ON’ or ‘OFF’ function. However this mains switch or circuit breaker must be
installed at convenient place normally accessible to the operator.
4) Use and store the instrument within the specified ambient temperature and humidity ranges as
mentioned in this manual.
WarningGuidelines
SafetyPrecautions
Installation Guidelines
Maintenance
1) Prepare the panel cutout with proper dimensions as show above.
2) Fit the unit into the panel with the help of clamp given.
3) The equipment in its installed state must not come in close proximity to any heating source,
caustic vapors, oils steam, or other unwanted process by products.
4) Use the specified size of crimp terminal (M3.5 screws) to wire the terminal block. Tightening the
screws on the terminal block using the tightening torque of the range of 1.2 N.m.
5) Do not connect anything to unused terminals.
1) The equipment should be cleaned regularly to avoid blockage of ventilating parts.
2) Clean the equipment with a clean soft cloth. Do not use isopropyl alcohol or any other cleaning agent.
3) Fusible resistor must not be replaced by operator.
2
Mechanical Installation
136mm - 5.35 inches
60mm - 2.36 inches
B
A
F
E
MODEL A
48mm 96mm 44mm 92mm 4.5mm 66mm
BC
D E
F
DIMENSIONS
C
D
PIC 38
SET
R1 R2
ENT
1 2 3 4
Page-4
PIC-38 www.multispanindia.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

MULTISPAN PIC-38 Owner's manual

Type
Owner's manual

MULTISPAN PIC-38 is a process indicator with a 4-digit, 7-segment, 0.8” red LED display. It has a size of 48 X 96 X 65 mm and a panel cutout of 44 X 92 mm. The input range is 0-10V DC, 0-20mA DC, or 4-20mA DC, and the output is 1 relay, 1 C/O & 24V DC Transmitter. The selectable range is -999 to 9999. It has protection level (As per request) IP-65 (Front side) AS per IS/IEC 60529:2001. The operating temperature is 0°C to 55°C, and the relative humidity is up to 95% RH non-condensing.

The features of the MULT

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI