Hitachi L200 SERIES Engineering Note

Type
Engineering Note

This manual is also suitable for

Hitachi L200 SERIES

The Hitachi L200 SERIES is a versatile and powerful variable frequency drive (VFD) that can be used to control the speed and torque of AC motors. It is ideal for a wide range of applications, including:

  • Industrial automation
  • HVAC systems
  • Material handling
  • Robotics

The L200 SERIES is available in a variety of models to meet the specific needs of your application.

Hitachi L200 SERIES

The Hitachi L200 SERIES is a versatile and powerful variable frequency drive (VFD) that can be used to control the speed and torque of AC motors. It is ideal for a wide range of applications, including:

  • Industrial automation
  • HVAC systems
  • Material handling
  • Robotics

The L200 SERIES is available in a variety of models to meet the specific needs of your application.

Hitachi America, Ltd.
EN-050202-1
ENGINEERING NOTE
SUBJECT: ANALOG VOLTAGE INPUT CALIBRATION ERROR
AFFECTED
MODELS:
L200 and SJ200 – MFG DATE 0501 & BEFORE
Certain models of L200 and SJ200 were inadvertently shipped with the 0 – 10
Volt Analog Input (terminal O – L) span parameter improperly calibrated.
The symptom is easily determined. The inverter will operate properly with a
frequency reference from keypad potentiometer, analog 4 – 20 mA input or F001
setting. However when the frequency reference is set to the O voltage input, the
inverter will act erratically at 0 V input, and may trip on overcurrent. The output
frequency will ramp up linearly from 0 V to approximately 0.2 V input with a
corresponding output frequency of 0 to the maximum (factory default is 60 Hz)
frequency. From input voltages from 0.2 V to 10.0 V, the inverter output will
remain pegged at the maximum frequency.
To correct this problem, first stop the inverter. Then follow these steps:
1. Press FUNC to enter the PROGRAM mode.
2. Using the UP / DN arrow keys, navigate to parameter
C091.
3. Press FUNC to view the contents, and press UP arrow key to change the
value to
01
4. Press STR to save the change. This will make the so-called “debug”
parameters accessible.
5. Using UP arrow key, navigate to parameter
C121
6. Press FUNC to view contents. It most likely is
6553
PGC - 2/2/05 Page 1 of 2
7. Using the DN arrow key, change the value to 1100. (Note the decimal
point after the number - this is critical!!) As you decrement the parameter
value, you will scroll past
1100 (WITHOUT a decimal point!!) Continue
going down toward zero, and the sequence will start again at 9999.
(WITH decimal point after!) and continue decrementing from there.
8. Continue down until the display reaches
1100. Press STR to save the
value. The display should show
C121 again.
9. Navigate with the DN arrow key to C091 and press FUNC again.
10. Change setting from 01 back to 00 with DN arrow key. Press STR
again to save. Display again should read
C091
11. Press FUNC TWICE until display reads
C---
12. Press UP arrow key until you reach
o 001
13. Press FUNC, then STR This step re-establishes the output frequency
display as the power-on default display.
The analog voltage input should now operate linearly with a 0 – 10 V input
corresponding to a 0 – 60 Hz output.
PGC - 2/2/05 Page 2 of 2
  • Page 1 1
  • Page 2 2

Hitachi L200 SERIES Engineering Note

Type
Engineering Note
This manual is also suitable for

Hitachi L200 SERIES

The Hitachi L200 SERIES is a versatile and powerful variable frequency drive (VFD) that can be used to control the speed and torque of AC motors. It is ideal for a wide range of applications, including:

  • Industrial automation
  • HVAC systems
  • Material handling
  • Robotics

The L200 SERIES is available in a variety of models to meet the specific needs of your application.