Injung Tech INJ-45001 User Quick Manual

Type
User Quick Manual

This manual is also suitable for

NJ-4500L I 1
User Quick Manual
This manual describes how to use the S-Drive has been developed by a small pump motor inverter. Since
applying the high reliability products PID algorithm, be sure and get familiar with the operation manual before using.
2 I NJ-4500L
1. Safety Instructions
2. Technical Characteristics
- Performance
- Weight and dimensions
3. INJ-4500 Installation
- Before installation
- Installation on the pump
4. Wiring Diagram
5. Sensor Connection/Operation Method
- INJ-4500 Constant pressure control
6. INJ-4500 Display/Set-up
- LCD display
- Display color indications
- Setting the pressure
7. Multi-connection
8. Sensor Error
8. Inverter Parameters
9. Booster Parameters
10. Alarm Log
3
4
5
6
7
8
9
10
11-12
13-14
15
Table of Contents
An Alternative Answer to
Perfect Water Pressure”
Safety Instructions I 03
Safety Instructions
INJ-4500 series is intended for professional incorporation into comp lete equipment or systems as part of a xed
installation. If installed incorrectly it may present a safety hazard. The INJ-4500 series uses high voltages and
currents, carries a high level of stored electrical energy, and is used to control mechanical plant that may cause
injury. Close attention is required to system design and electrical installation to avoid hazards in either normal
operation or in the event of equipment malfunction. Only qualied electricians are allowed to install and maintain
this product.
System design, installation, commissioning and maintenance must be carried out only by personnel who have
the necessary training and experience. They must carefully read this safety information and the instructions in
this Guide and follow all information regarding transport, storage, installation and use of the INJ-4500 series,
including the specied environmental limitations.
Do not perform any ash test or voltage withstand test on the INJ-4500 series. Any electrical measurements
required should be carried out with the INJ-4500 series disconnected.
Electric shock hazard! Disconnect and ISOLATE the INJ-4500 series before attempting any work on it. High
voltages are present at the terminals and within the drive for up to 10 minutes after disconnection of the electrical
supply. Always ensure by using a suitable multimeter that no voltage is present on any drive power terminals
prior to commencing any work.
Where supply to the drive is through a plug and socket connector, do not disconnect until 10 minutes have
elapsed after turning o the supply.
Ensure correct earthing connections and cable selection as per dened by local legislation or codes. The drive
may have a leakage current of greater than 3.5mA; furthermore the earth cable must be sucient to carry the
maximum supply fault current which normally will be limited by the fuses or MCB. Suitably rated fuses or MCB
should be tted in the mains supply to the drive, according to any local legislation or codes.
The level of integrity oered by the Optidrive control input functions – for example stop/start, forward and
maximum speed is not sucient for use in safety-critical applications without independent channels of
protection. All applications where malfunction could cause injury or loss of life must be subject to a risk
assessment and further protection provided where needed.
The driven motor can start at power up if the enable input signal is present.
The STOP function does not remove potentially lethal high voltages. ISOLATE the drive and wait 10 minutes
before starting any work on it. Never carry out any work on the Drive, Motor or Motor cable whilst the input
power is still applied.
The INJ-4500 series can be programmed to operate the driven motor at speeds above or below the speed
achieved when connecting the motor directly to the mains supply. Obtain conrmation from the manufacturers of
the motor and the driven machine about suitability for operation over the intended speed range prior to machine
start up.
Do not activate the automatic ault reset function on any systems whereby this may cause a potentially dangerous
situation.
When mounting the drive, ensure that sucient cooling is provided. Do not carry out drilling operations with the
drive in place, dust and swarf from drilling may lead to damage.
The entry of conductive or ammable foreign bodies should be prevented. Flammable material should not be
placed close to the drive. Relative humidity must be less than 95% (non-condensing).
Ensure that the supply voltage, frequency and single phase input correspond to the rating of the Optidrive as delivered.
Never connect the mains power supply to the Output terminals U, V, W.
Do not install any type of automatic switchgear between the drive and the motor
Danger : Indicates a risk of electric shock, which, if not
avoided, could result in damage to the equipment and
possible injury or death.
Danger : Indicates a risk of electric shock,
which, if not avoided, could result in damage
to the equipment and possible injury or death.
Please read the IMPORTANT SAFETY INFORMATION below, and all Warning and Caution information elsewhere.
04 I Technical Characteristics
Technical Characteristics
Performance
Weight and Dimensions
• Power frequency: 50 - 60 Hz (+/- 2%)
• Stocking temperature: -30 to 70 °C (-22 to 158 °F)
• Min. ambient temperature at rated current: -10 °C (-14 °F)
• Max. ambient temperature at rated current: 40°C (104 °F)
• Grade of protection: IP55
* Weight indicated is without the packaging.
Model
V in
[V]
Max V out
[V]
Max I out
[A]
Typical
motor P2
[kW]
Size
INJ-45001
1 x 230 +/- 15% 3 x 230 5 0.75 1
INJ-4500
1 x 230 +/- 15% 3 x 230 8 1.5 1
INJ-4500
1 x 230 +/- 15% 3 x 230 12 2.2 1
Model Weight [Kg] Size
INJ-4500
2.4 1
INJ-4500
2.4 1
INJ-4500
2.4 1
INJ-4500 Installation I 05
INJ-4500 Installation
Before Installation
Installation Guide of the INJ-4500
• Carefully Unpack the INJ-4500 and check for any signs of damage.
Notify the shipper immediately if any exist.
INJ-4500 is installed on the motor with a specialized heat-sink custom design by INJUNGTECH.
1. Remove the current motor terminal box.
Note: The gasket installed on the original terminal box
and the screws should be kept and not thrown away.
3. Undo the 4 screws on the inverter.
5. Bolt down the four inner holes located inside
the drive down with the screws provided.
2. Place the heat-sink provided unto the motor. Connect the
motor wires to the inverter output lines. Use the screws from the
motor and bolt down the heatsink unto the motor. Note: The
original gasket should be placed before placing the heatsink.
4. Lift up the inverter top by loosening the gland and by
pushing in the terminal wires.
6. Close the top of the drive and bolt down the 4 corners
with the screws provided.
Connection lines learn more
(Grounding)
INVERTERS
06 I Wiring Diagram
Wiring Diagram
This manual is intended as a guide for proper installation. Injungtech Co., Ltd., cannot assume responsibility
for the compliance or the non-compliance to any code, national, local or otherwise, for the proper installation
of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are
ignored during installation.
This INJ-4500 contains high voltage capacitors that take time to discharge after removal of the main supply.
Before working on the drive, ensure isolation of the main supply from line inputs. Wait ten (10) minutes for the
capacitors to discharge to safe voltage levels. Failure to observe this precaution could result in severe bodily
injury or loss of life.
Only qualied electrical personnel familiar with the construction and operation of this equipment and the
hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual
and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result
in severe bodily injury or loss of life.
U
V
W
FG
L1/R
L2/T
FG
M
~
FG
FG
R
T
V
W
U
2Ph2C,220V,
50Hz
SEN+
SEN-
PRESSURE
SENSOR
4~20mA
SEN+
SEN-
TO.POWER BOARD
FROM.
12PIN
POWER BORAD
LINE
CONTROL
BORAD LINE
Power Connections
FG
EARTH
T
L2/T(INPUT POWER)
R
L1/R(INPUT POWER)
FG
EARTH
U
Motor connection
V
Motor connection
W
Motor connection
Control Connections
SEN +
SENSOR+
SEN -
SENSOR-
12PIN
POWER BORAD Connection
Sensor Connection I 07
To change the auto mode and multi mode,
please follow the instructions below;
1. Auto Mode : To set the automatic operation
mode, press the STOP button for 3 seconds.
Then, the LCD indicates the AUTO mode.
2. Manual Mode : To set to MANUAL
OPERATION MODE, press down on the STOP
button for 3 seconds. The AUTO indication will
disappear. In MANUAL OPERATION MODE,
press the and once the indication is on
Hz, change the constant speed required by
pressing either the or and press the
run button once the Hz is selected.
Sensor connection and switching to automatic or manual operation.
* Note : The color of the sensor can dier
depending on the brand. The sensor indicated
in this manual is a Keller brand sensor. The left
line of the sensor (Brown color) is SEN+ and
the right line (White color) is SEN-.
Pressure tank
INJ-4500
Pump
Check valve
Valve
INJ-4500 controls the pump speed to maintain constant pressure at a set point independent of
the water demand in the system.
Sensor Connection/Operation Method
INJ-4500 Constant Pressure Control
Sensor connection
Verify sensor
side +,- line.
08 I Display/Set-up
LCD Display
LCD Color
Setting the Set Pressure
Display/Set-up
Press or
button for 2 seconds.
Press or
button to set the desired
pressure.
Press button to
complete the pressure
setting.
1 2 3
Blue
Indicates that the system is in OPERATION mode
Purple
Indicates that the system is in STOP mode
Red
Indicates that the system is in FAULT mode
VFD Operation
VFD Stop
Parameter 1
Parameter 2
Sensor Alarm
VFD Alarm
Pump Alarm
Can Communication I 09
Booster Indivisual Parameter (C)
Multi-connection
• The INJ-4500 series can be linked up to 4 pumps.
• The INJ-4500 installation and electrical wiring is done as described in this manual.
A 2-wire twisted and shielded cable 0.5mm2 section must make the communication between devices.
* The pressure sensor should be connected to the master pump.
1. Automatic operation. 2. Press for 2 seconds, conrm automatic operation.
3. Check order using botton.
(Current pressure -> Hz -> A -> Order)
1. Setting up the MASTER pump: Press the for a duration of 2 seconds and see if the
indication on the bottom of the LCD indicates “AUTO”. The Master pump should state “1”.
2. Setting up the SLAVE pump: Press the for a duration of 2 seconds and the slave pump
should state “2”. If the indication on the bottom of the LCD does not indicate “AUTO”, please
recheck the RS-485connection. Same sequence and procedure is identical for up to 4 pumps.
RS485+
Sensor
<Master Inverter> <Slave Inverter 1> <Slave Inverter 2>
RS485+
RS-485 Connection:
RS485- RS485-
11
Can Communication
The INJ-4500 series can be linked up to 4 pumps
RS-485connection:
1 32 1 32 1 32 1 32
AB AB AB AB
The INJ-4500 installation and electrical wiring is done as described in this manual.
A 2-wire twisted and shielded cable 0.5mm2 section must make the communication between
devices.
1. Setting up theMASTER pump: Press the for a duration of 2
seconds and see if the indication arrow on the right hand side indicates
AUTOMATIC OPERATION. The Master pump should state "1"
2. Setting up the SLAVE pump: Press the for a duration of 2 seconds
and see if the indication arrow on the right hand side indicates MULTI-
CONNECTION. If the indication arrow on the right hand side does not
indicate MULTI-CONNECTION, please re-check the RS-485
connection. Same sequence and procedure is identical for up to 4 pumps.
압력센서 이
미지 삽입 요
11
Can Communication
The INJ-4500 series can be linked up to 4 pumps
RS-485connection:
1 32 1 32 1 32 1 32
AB AB AB AB
The INJ-4500 installation and electrical wiring is done as described in this manual.
A 2-wire twisted and shielded cable 0.5mm2 section must make the communication between
devices.
1. Setting up theMASTER pump: Press the for a duration of 2
seconds and see if the indication arrow on the right hand side indicates
AUTOMATIC OPERATION. The Master pump should state "1"
2. Setting up the SLAVE pump: Press the for a duration of 2 seconds
and see if the indication arrow on the right hand side indicates MULTI-
CONNECTION. If the indication arrow on the right hand side does not
indicate MULTI-CONNECTION, please re-check the RS-485
connection. Same sequence and procedure is identical for up to 4 pumps.
압력센서 이
미지 삽입 요
10 I Sensor Error
Sensor Error
When the SEN(sensor) error occurs as shown in the above diagram, the following steps
should be taken;
1. Stop all operation of the VFD’s.
2. On the master pump, press down the ‘STOP’ button for 3 seconds, and change the setting
mode to Manual Mode.
3. The other slave pumps will indicate a COM error once step 2 is completed. Change of the
VFD’s interconnected to the MASTER from AUTO to Manual Mode.
4. Once the sensor connection is conrmed, the next lead pump (2nd VFD) should be changed
from Manual Mode to AUTO mode by pressing the STOP button for a duration of 3 seconds.
This will then change the Master to the second pump.
1. Automatic operation. 2. Press for 2 seconds, conrm automatic operation.
3. Check order using botton.
(Current pressure -> Hz -> A -> Order)
RS485+
Sensor
<Master Inverter> <Slave Inverter 1> <Slave Inverter 2>
RS485+
RS485- RS485-
Inverter Parameters I 11
Inverter Parameters
Display Name Unit Range Description
Factory setting
220V 240V
P 00
Max.
Frequency
Hz 5.0 - 70 Maximum Motor Frequency 60 50
P 01
Max. Voltage
Frequency
Hz 5.0 - 70
Maximum Voltage Frequency
Note: can vary depending on the
motor input power.
60 50
P 02
Max. Voltage V 50 - 240 Maximum Voltage of the motor 220 240
P 03
Mid-Point
Frequency
Hz 5.0 - 70
This parameter sets the Mid-point
Frequency of the V/F curve. With this
setting, the V/F ratio between Minimum
and Mid-point Frequency can be
determinded. It can make the VFD
operate with quadratic characteristic.
30 25
P 04
Mid-Point
Voltage
V 3 - 220
Middle Point Voltage
Mid-point Voltage can be directly set by
the user. This function makes the VFD
operate with the quadratic characteristic.
This setting value must be equal to or
greater than Mini. Output Freq. and
eaqul to or less than Max. voltage Freq.
110 120
P 05
Min.
Frequency
Hz 0.1 - 20 Minimum Motor Frequency 1.5 1.5
P 06
Min. Voltage V 3 - 100 Minimum Motor Voltage 15 15
P 07
ACC Time Sec 3.0 - 99.9
Acceleration ramp time from P-05 to
base frequency (P-03) in seconds.
4 3
P 08
DEC Time Sec 3.0 - 99.9
Deceleration ramp time from base
frequency (P-03) to standstill in seconds.
4 3
To set the parameter, please press the ‘ ’ and
’ button for 3 seconds.
F
V
Max.
Frequency
quad. paern = 100%
50Hz
50Hz
240V
120V
40Hz
Max.Output
Voltage
Min. Output
Frequency
Mid-
Point
Freq.
Mid-
Point
Freq.
by user
Max.
Voltage
Freq.
Mid-Point
Voltage
12 I Inverter Parameters
Inverter Parameters
P 09
Stop Mode 0 or 1
- 0 (Ramp to stop): When the enable
signal is removed, the drive will ramp to
stop, with the rate controlled by P-08.
- 1 (Coast to Stop): When the enable
signal is removed, or if the mains
supply is lost, the motor will coast
(freewheel) to stop.
1 1
P 10
PUMP
Capacity
HP 0 - 4
- 0: 1HP
- 1: 1.5HP
- 2: 2HP
- 3: 2.5HP
- 4: 3HP
2 2
P 11
Overload
Rate
% 50 - 200
Trip current level against rated current
of the motor.
(Protection related to Motor)
150 150
P 12
Overload
Time
Sec 2.0 - 99.9
It sets the maintaining time of
overload trip level.
(Protection related to Motor)
10 10
P 13
Over-Voltage
Rate
%
100 - 200
[%]
Voltage is too high.
(Protection related to Inverter)
120 120
P 14
Low-Voltage
Rate
%
50 - 90
[%]
Voltage is too low.
(Protection related to Inverter)
60 60
P 15
Carrier
Frequency
KHz 3.0 - 15.0
It is possible to choose in the range
of 2.5 ,4, 6, 8, 10 kHz. Higher values
give a more sinusoidal wave with
fewer losses for the motor but higher
losses for the inverter (increased
inverter heating).
8 8
P 16
TEST
- 444: reset (VFD can be re-set to the
factory setting)
P 17
VERSION
0
F
Time
Delay Time(5sec.)
Min. output
Frequency
Max.
Freq.(60Hz)
Accel.
Decel.
PID Control
Ramp to stop
Coast to Stop
Seng operaon
ACC/DEC
TIME
Booster Parameters I 13
Booster Parameters
Display Name Unit Range Description
Factory setting
220V 240V
B 00
Set pressure Bar 0.3 ~ 6.0
The pressure value to be kept
constant.
2 2
B 01
Dierential
Pressure
Bar -0.3 ~ -0.2
To correct variation between
suction and discharge of the
pressure value
-0.3 -0.5
B 02
Sensor
Range
Bar 1.0 ~ 20.0
Selection of the sensor range
denpend on the pressure required.
10 6
B 03
Sensor
Adjustment
Bar -9.9 ~ 9.9
If the value indicated at the
pressure gauge diers from the
pressure sensor, please adjust the
sensor value with this paremeter.
0 0
B 04
Low
Pressure
setting
Bar 0.2 ~ 2.0
To set the lowest pressure.
Note : Once the default set
pressure is adjusted, the
Low Pressure setting will be
automatically adjusted to 20% of
the set pressure
0.3 0.5
B 05
Low Pressure
Stop
Sec 0 or 1
- 0 : OFF
- 1 : 1~999
20 20
B 06
Low Current Amp 0.5 ~ 5.0
Note : This value automatically
changes depend on P10
(Pump capacity).
1HP : 1.8A
1.5HP : 2.5A
2HP : 3.3A
2.5HP : 4.0A
3HP : 4.6A
3.3 3.3
B 07
Low Current
Stop
Sec 0 or 1
- 0 : OFF
- 1 : 1~999
10 10
B 08
Motor
Direction
0 or 1
- 0 : CW
- 1 : CCW
0 0
To set the parameter, please press the ‘ ’ and
’ button for 3 seconds.
14 I Booster Parameters
Booster Parameters
B 09
P 1 ~ 200
It is relevant to ‘P’ out of PID
control parameters. PID I-Gain 1
second means the time required
for the output power to be
accumulated to 1.0[Hz] when 200
bar errors are maintained.
25 25
B 10
I 1 ~ 200
It is relevant to ‘I’ out of PID
control parameters. PID I-Gain 1
second means the time required
for the output power to be
accumulated to 1.0[Hz] when 200
bar errors are maintained.
40 40
B 11
D 1 ~ 200
It is relevant to ‘D’ out of PID
control parameters. PID I-Gain 1
second means the time required
for the output power to be
accumulated to 1.0[Hz] when 200
bar errors are maintained.
40 40
B 12
Auto Reset Time 0 ~ 20
It can applied only for OC, OL, OV,
LV faculties.
(when the Auto reset occures,
there is approx. 1min. delay time.
If the delay time is too short, the
trip will occur)
5 5
B 13
Initial
Operation
Status
0 ~ 2
- 0 : Stop
- 1 : Run
- 2 : latest default
2 2
B 14
B 15
B 16
B 17
VERSION
Alarm Log I 15
Alarm Log
Alarm Log (Max 20 logs)
Display Alarm Reason Countermeasures
Over current
Over-current on the inverter
/Abnormal operation of the
motor /Short of the motor’s
output line
If problem repeats /
Check the pump/motor
Low voltage Low-voltage on the inverter Check the input voltage
Over voltage
Over-voltage on the
inverter, when excessive
voltage is inputted to the
inverter
Check the input voltage
Over load
Overload on the inverter /
Abnormal operation of the
motor/pump
Check the pump/motor
Fail communication
Master and slave are
communication fail
Check communication
line
Err of sensor Sensor fail to connect
Check the connection
of the sensor /
Change the sensor
Stop for low current
When the water level
of the tank is low /
When air enters the pumps
Check the tank /
Remove air from the
pump
Low pressure
When the pressure drops
below the set “Low press’
Lower the “Low press” /
Adjust the setting
for pump operation
In Main display, Press and button longer and together.
16 I NJ-4500L
http://www.injungtech.com/
+82-(0)31-357-8655
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Injung Tech INJ-45001 User Quick Manual

Type
User Quick Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI