A comparison of induction units and fan coils with EC Technology was undertaken as part of a
scientific study. Owing
to their lower noise emissions, both system are frequently selected
solutions for the decentralised air conditioning of hotel bedrooms, but both have definite pros
and cons. The aim of the study was to compare the economical and technical differences
between both systems for the cooling
of hotel bedrooms.
Functional comparison of induction units and fan coils
Both units are installed in hotel bedrooms below suspended ceilings to meet the heating and
cooling loads of the rooms.
Induction units
Dened parameters for the calculation basis
Fan coil units
Induction units are connected directly to the air duct
system and induce the air to the rooms through
nozzles. The temperature of this air is adjusted in the
heat exchanger and fed back into the room with
the primary air through an air outlet grille.
Induction unit: Dry cooling at CPW 16 / 18 °C
Heating at LPHW 45 / 35 °C
Fan coils: Dry cooling at CPW 16 / 18 °C (as a comparison)
Wet cooling at CPW 7 / 12 °C
Heating at LPHW 45 / 35 °C
Assumed room temperatures: In winter: 21 °C / In summer: 26 °C
Assumed heating load: 60 W / m²
Assumed cooling load: 40 W / m²
Load prole: The load prole and the times the rooms were used
were in compliance with DIN 18599-10
Primary air percentage: With both versions using bafe-controlled
primary air
Building pollutants: 1 m³ / (h x m²)
People: 20 m³ / (h x person)
Room size: 20 m²
Room use: Unoccupied room: 20 m³/ h required
Occupied room: 60 m³/ h required
Air handling unit: Kampmann Airblock KG
With fan coil units, the supply air outlet is located in
the suspended ceiling. The room air is drawn in by
the fan through a shadow gap in the suspended cei
ling,
its temperature is adjusted before it is fed back into
the room.
Induction units vs.
Fan Coil units
Economical and technical
comparison for cooling in hotel bedrooms
Object of the scientic study
Various parameters were dened and a calculation model produced taking into account Guidelines
VDI 2067 “Efciency of building services systems.” A ctitious building with varying number of
rooms and room sizes was used as the basis for the study. The loads of the rooms were determined
for different cases using hourly calculations, and the fan coils and induction units were selected
on the basis of this.
Scope of analysis
The following aspects were examined based on the dened parameters:
electrical energy consumption
heating and cooling energy requirement
investment, maintenance and repair costs