The “Listed” equipment manufacturer’s Installation and Operating Instructions should provide all necessary information
as required by ANSI Z83.8-CSA 2.6 including but not limited to the following; Installation Codes, Hazard Warnings,
operation in chemical environments, gas piping, electrical connection, Lighting Instructions, Sequence of Operation,
proper adjustment of minimum firing rate, Manual reset switches, Wiring Diagrams, Clearance to Combustibles, Airflow
and Rise ranges, Venting and troubleshooting, annual inspection and maintenance.
The final determination of the safety and suitability of this product for the specific application shall be the responsibility
of the manufacturer of the “Listed” equipment and the listing Agency.
Installation of Duct Furnace
1. Before installing duct furnace, verify that electrical supply matches the voltage rating and the furnace is set-up
for the correct gas supply. Refer to Rating Plate attached to front shroud of furnace assembly.
2. Carefully support and lift module into position and slide into cabinet. Provide proper rigging to support module
during installation into cabinet. Do not lift module by tubes or burner housing, as damage could result.
3. Fasten frame to cabinet. Expansion and contraction occurs during heating and cooling cycles and heat
exchanger mounting employs elongated slots for mounting bolts. Nuts and washers are used to secure heat
exchanger elements to the frame in a manner that will allow for expansion of the heat exchanger assembly
within the frame. NEVER tighten nuts to supports. Heat exchanger damage can occur.
4. Condensate drains must be hard piped from the heat exchanger to the outside of the heating unit. ½” NPT
condensate drain fittings are provided in each collector box. Drain lines should be stainless steel, as any
condensate that forms during operating cycles is corrosive, particularly to copper. Attach a drain line with
proper pitch (1/4” per 12”) to provide positive drainage of any condensate. Condensation may occur during first
few minutes, at the beginning of a heating cycle, or during air conditioning operation if furnace is downstream
of cooling section (this condensate is typically non-acidic and harmless if it does not accumulate). Free flow of
any condensate that may be present is critical to life of the heat exchanger. Accumulation of condensate can
lead to corrosion and pre-mature heat exchanger failure. A trap is not necessary, but heat tape or other freeze
protection should be provided for outdoor installations to prevent blockage of condensate line and insure free
flow.
5. Connect supply piping to gas valve using a pipe sealant resistant to LP gases on pipe threads. Properly
support gas valve during supply installation to prevent valve from turning or damage to burner assembly.
6. Uncoil tubing from circulating airflow switch provided, and position open end of tube in representative airflow
location.
7. Perform electrical, operation and leak checks on assembled unit according to Agency procedure.
8. Instructions are provided with the power gas burner installed on furnace covering proper set-up and
adjustment, including minimum rate adjustment. These instructions must be included with the fully
assembled product.
Combustion Air
Air required for combustion is drawn in through the inlet of the fan assembly. If burner is located in a vestibule in the
heating unit, openings to provide an ample supply of combustion air need to be provided. Openings should be sized at
1 square inch of open area per 4,000 Btuh of input.
Openings should be located to avoid recirculation of flue gases from the vent discharge into the combustion air supply.
Consideration should be given to location of air openings so that flow of air is not impeded by other features of unit
design and to prevent blockage from snow build-up for outdoor installations. Air openings should be designed and
configured to minimize entry of windblown rain or snow into the burner compartment
Venting
Installation of venting system must conform to local building codes and / or the National Fuel Gas Code (ANSI
Z223.1) or in Canada the Canadian Installation Code (CAN/CGA-B149). These standards or local codes take
precedence over the information provided in this manual. Consult your local building authority.