Installation, Operation & Maintenance Instructions for the
PRIER C-634 Heavy Commercial Wall Hydrant
*Please leave this sheet for the property owner*
Thank you for purchasing the PRIER C-634 Heavy Commercial Wall Hydrant, the nest quality commercial
hydrant available. Your C-634 will provide you years of dependable service with little or no maintenance.
Please note: Your C-634 hydrant has drain holes under the packing nut. After shutoff, the drain holes will allow water to
drain for a few moments to prevent freezing. This is normal and according to design.
Installation:
Installation procedures may vary slightly depending on the seat option purchased and the installation inlet options. The
C-634 wall hydrant is available with the following inlet options:
N 1” MIP x 3/4” FIP
P 1” Male SWT x 3/4” Female SWT
V 3/4” ProPress Ready
Operation:
Operation of the C-634 Commercial Wall Hydrant is a simple process. Water ows through the hydrant after turning the
loose key one full turn counter-clockwise to the “on” position. The hydrant will achieve maximum ow at 2 1/2 full turns.
Turn off the hydrant by turning the loose key clockwise to the “off” position.
The hydrant will drain for a few moments. If the dripping persists after a few moments, tighten the key slightly until the
dripping stops. Be careful not to overtighten the hydrant.
The C-634 incorporates an integral atmospheric anti-siphon vacuum breaker that, in the rare occurrence of a back siphon-
age, opens to the atmosphere preventing contamination of the water supply.
As well as an atmospheric vacuum breaker, the C-634 incorporates vacuum breaker check valve in the rare case that
water is forced backwards into the valve.
*ALWAYS REMOVE HOSE DURING FREEZING TEMPERATURES*
*INTENDED FOR IRRIGATION USE AND OUTDOOR WATERING*
1. Determine the location for the installation of the hydrant. Ensure there is adequate
work room in the interior of the structure for securing the hydrant to the plumbing
piping. Bore a 1 1/8” diameter hole through the wall in the desired position for the
installation and a 1/4” hole that is 1/2” deep.
2. The PRIER C-634 is designed for installation in either the horizontal or vertical
position. If using vertical installation, it is recommended that the hydrant be installed
with the hose threads in the “up” position. Refer to the drawings below.
3. If you are planning to solder the connection, be certain the hydrant is in the fully
open position to prevent seat damage from the heat.
4. Connect the water supply piping to the hydrant as desired. With a closed-end hose
on the valve creating back pressure, test the installation for leakage.
5. After the water supply connection is made, secure the hydrant to the structure.
4515 East 139th Street
Grandview, MO 64030
(800) 362-9055
Fax (800) 362-1463
INSTALLATION:
5. Flush all foreign particles from the water line before
connecting the Freezeless Hydrant. Foreign particles
may clog the vacuum breaker/backflow preventor caus-
ing it to fail.
6. Insert the Freezeless Hydrant through the previously
bored hole and secure the hydrant to the inside of the
wall with the provided wall clamping ring.
7. Secure the Freezeless Hydrant to the supply piping.
Test the installation for leakage.
1. De
termine the location for installation of the Freeze-
less Hydrant. Be sure there is adequate work area on
the interior of the structure for securing the Freezeless
Hydrant to the waterline.
3. Using the template provided on the box, bore a 1
3
/
8
diameter hole through the wall in the desired position,
and a
1
/
4
hole that is
1
/
2
deep.
2. The Prier C-634 is designed for installation in either
horizontal or vertical position. If using vertical installa-
tion, it is recommended that the hydrant be in
stalled with
the hose threads in the upposition. Refer to drawings
to the right for correct installations.
4. If planning to solder the Freezeless Hydrant to the
supply piping, remove the operating stem before apply-
ing heat to the valve. Heating the valve will damage the
sealing surfaces on the stem of the Freezeless Hydrant
OPERATION:
The operation of a Prier C-634 Freezeless Wall
Hydrant is simple. The Freezeless Hydrant will
begin to flow at about 1 full turn of the key and will
achieve maxi
mum flow at 2
1
/
2
full turns.
After shutoff, the hydrant will drain water from be-
hind the packing nut. If the water drains for more
than 1 minute, the stopper may need to be replaced.
Do not overturn when opening or closing the hydrant!
MAINTENANCE:
The Prier C-634 Freezeless Wall Hydrant requires no
scheduled maintenance for long wear life. If the op-
erating stem is removed, replacement of the O-Ring
on the worm sleeve and worm drive is recommended.
Recommended
Acceptable
Not Recommended
Acceptable
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR
PRIER C-634 HEAVY COMMERCIAL WALL HYDRANTS
PARTS:
7 13
12
11
3
4
10
8
1
5
6
9
2
ID Part No. Description
1
300-6003 Valve Stem Cap-Brass
2
300-6004 Hose Piece-Brass
3
336-0001 O-Ring for Worm Sleeve Buna
4
336-6001 O-Ring for Worm Drive Buna
5
337-6001 Stop Check-Acetal
6 346-6001 VB Check Washer-Silicone
7
399-6001 Stopper-Brass & EPDM
8
C-108KT-808 Operating Key on Lanyard
9
C-634KT-806 Vacuum Breaker Check Valve Assy
10
C-634KT-809 Worm Drive Assembly-Brass
11
C-634KT-808 Worm Sleeve Assembly-Brass
12
C-634WCR W
all Clamp Ring-Iron
13
231-06CC Stem for Close Coupled C-634
231-0604 Stem for 4" C-634
231-0606 Stem for 6" C-634
231-0608 Stem for 8" C-634
231-0610 Stem for 10" C-634
231-0612 Stem for 12" C-634
231-0614 Stem for 14" C-634
231-0618 Stem for 18" C-634
231-0624 Stem for 24" C-634
4515 East 139th Street
Grandview, MO 64030
(800) 362-9055
Fax (800) 362-1463
INSTALLATION:
5. Flush all foreign particles from the water line before
connecting the Freezeless Hydrant. Foreign particles
may clog the vacuum breaker/backflow preventor caus-
ing it to fail.
6. Insert the Freezeless Hydrant through the previously
bored hole and secure the hydrant to the inside of the
wall with the provided wall clamping ring.
7. Secure the Freezeless Hydrant to the supply piping.
Test the installation for leakage.
1. De
termine the location for installation of the Freeze-
less Hydrant. Be sure there is adequate work area on
the interior of the structure for securing the Freezeless
Hydrant to the waterline.
3. Using the template provided on the box, bore a 1
3
/
8
diameter hole through the wall in the desired position,
and a
1
/
4
hole that is
1
/
2
deep.
2. The Prier C-634 is designed for installation in either
horizontal or vertical position. If using vertical installa-
tion, it is recommended that the hydrant be in
stalled with
the hose threads in the upposition. Refer to drawings
to the right for correct installations.
4. If planning to solder the Freezeless Hydrant to the
supply piping, remove the operating stem before apply-
ing heat to the valve. Heating the valve will damage the
sealing surfaces on the stem of the Freezeless Hydrant
OPERATION:
The operation of a Prier C-634 Freezeless Wall
Hydrant is simple. The Freezeless Hydrant will
begin to flow at about 1 full turn of the key and will
achieve maxi
mum flow at 2
1
/
2
full turns.
After shutoff, the hydrant will drain water from be-
hind the packing nut. If the water drains for more
than 1 minute, the stopper may need to be replaced.
Do not overturn when opening or closing the hydrant!
MAINTENANCE:
The Prier C-634 Freezeless Wall Hydrant requires no
scheduled maintenance for long wear life. If the op-
erating stem is removed, replacement of the O-Ring
on the worm sleeve and worm drive is recommended.
Recommended
Acceptable
Not Recommended
Acceptable
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR
PRIER C-634 HEAVY COMMERCIAL WALL HYDRANTS
PARTS:
7 13
12
11
3
4
10
8
1
5
6
9
2
ID Part No. Description
1
300-6003 Valve Stem Cap-Brass
2
300-6004 Hose Piece-Brass
3
336-0001 O-Ring for Worm Sleeve Buna
4
336-6001 O-Ring for Worm Drive Buna
5
337-6001 Stop Check-Acetal
6 346-6001 VB Check Washer-Silicone
7
399-6001 Stopper-Brass & EPDM
8
C-108KT-808 Operating Key on Lanyard
9
C-634KT-806 Vacuum Breaker Check Valve Assy
10
C-634KT-809 Worm Drive Assembly-Brass
11
C-634KT-808 Worm Sleeve Assembly-Brass
12
C-634WCR W
all Clamp Ring-Iron
13
231-06CC Stem for Close Coupled C-634
231-0604 Stem for 4" C-634
231-0606 Stem for 6" C-634
231-0608 Stem for 8" C-634
231-0610 Stem for 10" C-634
231-0612 Stem for 12" C-634
231-0614 Stem for 14" C-634
231-0618 Stem for 18" C-634
231-0624 Stem for 24" C-634
4515 East 139th Street
Grandview, MO 64030
(800) 362-9055
Fax (800) 362-1463
INSTALLATION:
5. Flush all foreign particles from the water line before
connecting the Freezeless Hydrant. Foreign particles
may clog the vacuum breaker/backflow preventor caus-
ing it to fail.
6. Insert the Freezeless Hydrant through the previously
bored hole and secure the hydrant to the inside of the
wall with the provided wall clamping ring.
7. Secure the Freezeless Hydrant to the supply piping.
Test the installation for leakage.
1. De
termine the location for installation of the Freeze-
less Hydrant. Be sure there is adequate work area on
the interior of the structure for securing the Freezeless
Hydrant to the waterline.
3. Using the template provided on the box, bore a 1
3
/
8
diameter hole through the wall in the desired position,
and a
1
/
4
hole that is
1
/
2
deep.
2. The Prier C-634 is designed for installation in either
horizontal or vertical position. If using vertical installa-
tion, it is recommended that the hydrant be in
stalled with
the hose threads in the upposition. Refer to drawings
to the right for correct installations.
4. If planning to solder the Freezeless Hydrant to the
supply piping, remove the operating stem before apply-
ing heat to the valve. Heating the valve will damage the
sealing surfaces on the stem of the Freezeless Hydrant
OPERATION:
The operation of a Prier C-634 Freezeless Wall
Hydrant is simple. The Freezeless Hydrant will
begin to flow at about 1 full turn of the key and will
achieve maxi
mum flow at 2
1
/
2
full turns.
After shutoff, the hydrant will drain water from be-
hind the packing nut. If the water drains for more
than 1 minute, the stopper may need to be replaced.
Do not overturn when opening or closing the hydrant!
MAINTENANCE:
The Prier C-634 Freezeless Wall Hydrant requires no
scheduled maintenance for long wear life. If the op-
erating stem is removed, replacement of the O-Ring
on the worm sleeve and worm drive is recommended.
Recommended
Acceptable
Not Recommended
Acceptable
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR
PRIER C-634 HEAVY COMMERCIAL WALL HYDRANTS
PARTS:
7 13
12
11
3
4
10
8
1
5
6
9
2
ID Part No. Description
1
300-6003 Valve Stem Cap-Brass
2
300-6004 Hose Piece-Brass
3
336-0001 O-Ring for Worm Sleeve Buna
4
336-6001 O-Ring for Worm Drive Buna
5
337-6001 Stop Check-Acetal
6 346-6001 VB Check Washer-Silicone
7
399-6001 Stopper-Brass & EPDM
8
C-108KT-808 Operating Key on Lanyard
9
C-634KT-806 Vacuum Breaker Check Valve Assy
10
C-634KT-809 Worm Drive Assembly-Brass
11
C-634KT-808 Worm Sleeve Assembly-Brass
12
C-634WCR W
all Clamp Ring-Iron
13
231-06CC Stem for Close Coupled C-634
231-0604 Stem for 4" C-634
231-0606 Stem for 6" C-634
231-0608 Stem for 8" C-634
231-0610 Stem for 10" C-634
231-0612 Stem for 12" C-634
231-0614 Stem for 14" C-634
231-0618 Stem for 18" C-634
231-0624 Stem for 24" C-634
4515 East 139th Street
Grandview, MO 64030
(800) 362-9055
Fax (800) 362-1463
INSTALLATION:
5. Flush all foreign particles from the water line before
connecting the Freezeless Hydrant. Foreign particles
may clog the vacuum breaker/backflow preventor caus-
ing it to fail.
6. Insert the Freezeless Hydrant through the previously
bored hole and secure the hydrant to the inside of the
wall with the provided wall clamping ring.
7. Secure the Freezeless Hydrant to the supply piping.
Test the installation for leakage.
1. De
termine the location for installation of the Freeze-
less Hydrant. Be sure there is adequate work area on
the interior of the structure for securing the Freezeless
Hydrant to the waterline.
3. Using the template provided on the box, bore a 1
3
/
8
diameter hole through the wall in the desired position,
and a
1
/
4
hole that is
1
/
2
deep.
2. The Prier C-634 is designed for installation in either
horizontal or vertical position. If using vertical installa-
tion, it is recommended that the hydrant be in
stalled with
the hose threads in the upposition. Refer to drawings
to the right for correct installations.
4. If planning to solder the Freezeless Hydrant to the
supply piping, remove the operating stem before apply-
ing heat to the valve. Heating the valve will damage the
sealing surfaces on the stem of the Freezeless Hydrant
OPERATION:
The operation of a Prier C-634 Freezeless Wall
Hydrant is simple. The Freezeless Hydrant will
begin to flow at about 1 full turn of the key and will
achieve maxi
mum flow at 2
1
/
2
full turns.
After shutoff, the hydrant will drain water from be-
hind the packing nut. If the water drains for more
than 1 minute, the stopper may need to be replaced.
Do not overturn when opening or closing the hydrant!
MAINTENANCE:
The Prier C-634 Freezeless Wall Hydrant requires no
scheduled maintenance for long wear life. If the op-
erating stem is removed, replacement of the O-Ring
on the worm sleeve and worm drive is recommended.
Recommended
Acceptable
Not Recommended
Acceptable
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR
PRIER C-634 HEAVY COMMERCIAL WALL HYDRANTS
PARTS:
7 13
12
11
3
4
10
8
1
5
6
9
2
ID Part No. Description
1
300-6003 Valve Stem Cap-Brass
2
300-6004 Hose Piece-Brass
3
336-0001 O-Ring for Worm Sleeve Buna
4
336-6001 O-Ring for Worm Drive Buna
5
337-6001 Stop Check-Acetal
6 346-6001 VB Check Washer-Silicone
7
399-6001 Stopper-Brass & EPDM
8
C-108KT-808 Operating Key on Lanyard
9
C-634KT-806 Vacuum Breaker Check Valve Assy
10
C-634KT-809 Worm Drive Assembly-Brass
11
C-634KT-808 Worm Sleeve Assembly-Brass
12
C-634WCR W
all Clamp Ring-Iron
13
231-06CC Stem for Close Coupled C-634
231-0604 Stem for 4" C-634
231-0606 Stem for 6" C-634
231-0608 Stem for 8" C-634
231-0610 Stem for 10" C-634
231-0612 Stem for 12" C-634
231-0614 Stem for 14" C-634
231-0618 Stem for 18" C-634
231-0624 Stem for 24" C-634
Maintenance:
The C-634 Heavy Commercial Wall Hydrant leaves the factory fully air tested and operational. It is treated with an FDA
approved lubrication. The hydrant requires no scheduled maintenance to provide long life. If the stem is removed, the
bypass O-Ring needs to be replaced and lubricated with an FDA approved lubricant to avoid tearing.
*P and V inlets only available with CC length
ID Part No. Description ID Part No. Description
1 See Below Stem Assembly, Contains: 5, 14 310-6009 1” Hose Piece for C-636 (NP Brass)
P-231-0604 Stem for 4” C-634 Hydrant, 4
11
/
16
” OAL 5 336-0001 O-Ring Worm Sleeve
P-231-0606 Stem for 6 “ C-634 Hydrant, 6
11
/
16
” OAL 6 336-6001 O-Ring Worm Drive
P-231-0608 Stem for 8” C-634 Hydrant, 8
11
/
16
” OAL 7 337-6001 Check Spider-Vacuum Breaker
P-231-0610 Stem for 10” C-634 Hydrant, 10
11
/
16
” OAL 8 346-6001 Diaphragm-Vacuum Breaker
P-231-0612 Stem for 12” C-634 Hydrant, 12
11
/
16
” OAL 10 C-108KT-808 Loose Key on Lanyard
P-231-0614 Stem for 14” C-634 Hydrant, 14
11
/
16
” OAL 11 C-634KT-802 Stopper Kit, Includes Stopper and Pin
P-231-0616 Stem for 16” C-634 Hydrant, 16
11
/
16
” OAL 12 324-0004 Pin Only
P-231-0618 Stem for 18” C-634 Hydrant, 18
11
/
16
” OAL 13 C-634KT-806 Vacuum Breaker Assembly
P-231-0620 Stem for 20” C-634 Hydrant, 20
11
/
16
” OAL 14 C-634KT-808 Worm Sleeve with O-Ring, Pin and Tool
P-231-0622 Stem for 22” C-634 Hydrant, 22
11
/
16
” OAL 15 C-634KT-809 Worm Drive Assembly with O-Ring
P-231-0624 Stem for 24” C-634 Hydrant, 24
11
/
16
” OAL 16 C-634WCR Wall Clamping Ring
2 300-6003 Valve Stem Cap (NP Brass) 17 399-0001 Secondary Check for ASSE 1052
3 300-6004 3/4” Hose Piece (NP Brass) C-634KT-807 C-634 Overhaul Kit, Contains: 10, 11, 12, 13, 14
Replacement Parts & Stems
Rough-In Dimensions
4515 East 139th Street
Grandview, MO 64030
(800) 362-9055
Fax (800) 362-1463
www.PRIER.com
**For the old style C-634 Series wall hydrant stems, see C-634 Series retired style spec sheet at www.PRIER.com.
0.75”
(19 mm)
4” 102 mm
6” 152 mm
8” 203 mm
10” 254 mm
12” 305 mm
14” 356 mm
16” 406 mm
18” 457 mm
20” 508 mm
22” 559 mm
24” 607 mm
Hydrant Length*
2”
(51 mm)
4.5”
(114 mm)
2.25”
(55 mm)
2.50”
(63 mm)
1.125”
(28 mm)
0.25” (6 mm)
6.50”
(165 mm)
6.0”
(152 mm)
Hydrant Length*
0.187”
(5 mm)
2.25”
(57 mm)
0.75”
(19 mm)
*Standard Hydrant
Lengths
1
2
13
7 8
3 17
10
16
14
15
65
11
N Style
3/4” (19 mm) FPT
x 1” (25 mm) NPT
P Style
3/4” (19 mm) Female SWT
x 1” (25 mm) Male SWT
V Style
3/4” (19 mm) ProPress Ready
Inlet Styles
Furnish and install Model C-634 Heavy Commercial Wall Hydrant manufactured by PRIER Products, Inc. Hydrant shall be surface mount and
installed through 1 3/8” round opening. Hydrant shall have automatic draining capabilities with integral vacuum breaker/backow preventor.
Hydrant shall ow 19 gallons per minute minimum at 25 PSI Differential and be at full ow in 2 handle rotations. Hydrant shaft shall be brass
with threaded and sealed connections. Hydrant shall have 3/4” or 1” (choose one) hose connection with freezeless water ow and self-draining
functions, one piece valve plunger, satin nickel nish, brass operating rod with positive triple seal shutoff mechanism. Hydrant shall be approved
under ASSE 1052 standard. Operating key & wall clamping ring to be furnished with each hydrant. Hydrant insertion length to be * inches.
Optional: Furnish and install ush-mount hydrant box for each valve. Hydrant box shall be manufactured of solid cast brass with a brass or satin
nickel plated brass (choose one) nish. Box may be installed separately and hydrant be insertable and removable from front of the box. Access
to the hydrant box shall be provided by the same operating key as the valve. *4” to 24” in 2” increments.
Specs
12
*When assembling the vacuum breaker, ensure the
dome is facing out on the check spider and the step is
facing out on the silicone washer.