meitav-tec TED-24-SUPER Series Product information

  • I have reviewed the provided datasheet for the Meitav-tec Thermostat TED24-SUPER. It details the device's various features, such as its ability to use internal or external sensors, multiple heating and cooling modes, and the options for compressor delay, fan control and fault detection. I am ready to help answer your questions based on this information.
  • What are the sensor options for this device?
    Can this device control a heat pump system?
    What is the purpose of the 'FAULT' input?
    Can I set the device to use Fahrenheit?
    What fan modes does the device offer?
Date:
Title:
No.Revision Date
Drawn: P.Rechtman
Checked: S.Lukin
Approved: E.Roy
TED24-SUPER
18/03/2008 File: ted24-super.vsd
Software: T24SUM01
Chksum: 2619
“A” Position “B” Position
Internal sensor* External sensorJP1
Heat/Cool (HC)* Heat Pump (HP)JP3
Heat Electric*Heat Oil/GasJP4
Heat pump active in heat (“B”)* Heat pump active in cool (“O”)JP5
Celsius* FahrenheitJP6
Short Open
No compressor delay (for test) 3 minutes compressor delay*JP2
*Default
Print name: TED24SUPER
meitav-tec
Tel: +972 (3) 962 6462
Fax: +972 (3) 962 6620
e-mail: support@meitavtec.com
W2 Y2 Y1 C RH RC
T
T
External
sensor
(option)
Controller
AUTO ON
t
o
ON
W1
B/O
JP6
A
B
JP5
A
B
JP4
A
B
JP3
A
B
A
B
JP2
FAN
HEAT OFF COOL
G
FAULT
TEMP
F
AUTO FAN
Use the [FAN] switch to select between:
Auto – The fan will work on during demand for cool or heat.
Fan – The fan will work continuously only when the unit is ON.
FAULT INPUT
When the “F” (fault input)
terminal accepts 24VAC, the
red LED “FAULT” will turn ON.
RH RCF
Contact
C
LED
FAULT
24VAC
/