Installing the Module
2-5
SIMATIC 505-2571 Program Port Expander Manual
If
you require hardware handshaking for flow control, you should refer to
the device documentation for information on connecting the RTS, CTS,
DCD, DTR, and DSR lines. The PPX:505-2571 RS–232 port is configured as
DTE. In addition, you should set the port DIP switch position 3 to ON
(see T
able 2-1 and Figure 2-1).
NOTE:
Most common operator interface devices do not use the hardware
handshaking lines; therefore, you do not need to connect them. If you DO
NOT use hardware handshaking you MUST set DIP switch 3 to OFF
(see T
able 2-1 and Figure 2-1).
First turn on the base power supply
. If the diagnostics on the PPX:505-2571
detect no problems, the ACTIVE indicator will illuminate. If the indicator
does not illuminate or exhibits a blinking pattern, the module has detected
a component failure. For information on viewing failed module status, refer
to your
SIMA
TIC TISOFT Programming Reference Manual
. See Chapter 4
of this manual for troubleshooting information.
Next, check that the module is configured in the memory of the PLC. T
o
view the PLC I/O configuration chart refer to your
SIMA
TIC TISOFT
Programming Reference Manual
. See
Figure 2-3.
01 0001 00 00 02 06 YES.
. . . .
. . . . . . . . . . . . . . . . . . . . . . . .
02 0000 00 00 00 00 NO
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
.
.
15 0000 00 00 00 00 NO.
. . . .
. . . . . . . . . . . . . . . . . . . . . . . .
16 0000 00 00 00 00 NO
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
505
I/O MODULE DEFINITION FOR CHANNEL
1 BASE 00.
. . .
SLOT
I/O
ADDRESS
NUMBER
OF BIT AND WORD I/O
X Y WX WY
SPECIAL
FUNCTION
Figure 2-3 Sample
I/O Configuration Chart
Powering Up the
Module
Checking PLC
Login