Eaton 1250-3000 VA User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

This manual is also suitable for

Powerware 5130 Rack/Tower UPS
1250–3000 VA
User’s Guide
®
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
S Harmonized Standards: EN 62040-1-1 and EN 62040-2; IEC 60950-1
S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
93/68/EEC, Amending Directive 73/23/EEC
2004/108/EEC, Council Directive relating to electromagnetic compatibility
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC
Declaration of Conformity, contact:
Eaton Power Quality Oy
Koskelontie 13
FIN-02920 Espoo
Finland
Phone: +358-9-452 661
Fax: +358-9-452 665 68
Eaton, Powerware, FERRUPS, and LanSafe re registered trademarks of Eaton Corporation or its subsidiaries and
affiliates. National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc.
Phillips is a registered trademark of Phillips Screw Company. All other trademarks are property of their respective
companies.
ECopyright 2008 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be
reproduced in any way without the express written approval of Eaton Corporation.
Class A EMC Statements
(Low-Voltage Models)
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide r easonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference i n which case the user will be required to correct the interference at his own expense.
EN 62040-2
Some configurations are classified under EN 62040-2 as “Category C2 UPS.” For these configurations, the
following applies:
WARNING This is a category C2 UPS product. In a residential environment, this product may cause radio
interference, in which case the user may be required to take additional measures.
Class B EMC Statements
(High-Voltage Models)
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide r easonable protection against harmful interference in
a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user
is encouraged to try to correct the interference by one or more of the following measures:
S Reorient or relocate the receiving antenna.
S Increase the separation between the equipment and the receiver.
S Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
S Consult the dealer or an experienced radio/TV technician for help.
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock
symbol.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional
information, such as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This
product contains sealed, lead-acid batteries and must be disposed of properly. For more information,
contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in
the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
i
Table of Contents
1 Introduction 1.........................................................
2 Safety Warnings 3.....................................................
3 Installation 19..........................................................
Inspecting the Equipment 19................................................................
Checking the Accessory Kit 20..............................................................
Connecting the UPS Internal Battery 22........................................................
UPS Setup 23..........................................................................
Rackmount Setup 23...................................................................
Required Tools 23.....................................................................
Installing the Rail Kit 24................................................................
Tower Setup 25......................................................................
Installing the UPS 28.....................................................................
RPO and ROO Installation 31................................................................
UPS Rear Panels 33......................................................................
4 Operation 35...........................................................
Turning the UPS On 35....................................................................
Starting the UPS on Battery 36..............................................................
Turning the UPS Off 36....................................................................
Operating Modes 37.....................................................................
Normal Mode 37.....................................................................
Battery Mode 38.....................................................................
Standby Mode 38.....................................................................
5 Additional UPS Features 39...............................................
USB Port 39............................................................................
Contact Communication Port (optional) 41......................................................
Load Segments (PowerShare) 42.............................................................
Customizing the UPS with the UPS Configuration Tool 43...........................................
6 UPS Maintenance 45....................................................
UPS and Battery Care 45..................................................................
Transporting the UPS 45...................................................................
Storing the UPS and Batteries 46............................................................
When to Replace Batteries 46...............................................................
TABLE OF CONTENTS
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
ii
Replacing Batteries 46....................................................................
How to Replace Internal Batteries 47.......................................................
How to Replace Extended Battery Modules 49................................................
Recycling the Used Battery or UPS 50.........................................................
7 Specifications 51.......................................................
8 Troubleshooting 57......................................................
Audible Alarms and UPS Conditions 57........................................................
Service and Support 59...................................................................
9 Warranty 61...........................................................
Two-Year Limited Warranty (US and Canada) 61..................................................
Ten-Year Pro-Rated Limited Warranty (US and Canada) 63..........................................
Load Protection Guarantee (US and Canada) 65..................................................
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
1
Chapter 1 Introduction
Eaton’s Powerware
®
5130 uninterruptible power system (UPS) protects
your sensitive electronic equipment from basic power problems such as
power failures, power sags, power surges, brownouts, and line noise.
Power outages can occur when you least expect it and power
quality can be erratic. These power problems have the potential to
corrupt critical data, destroy unsaved work sessions, and damage
hardware causing hours of lost productivity and expensive repairs.
With the Powerware 5130, you can safely eliminate the effects of power
disturbances and guard the integrity of your equipment. The Powerware
5130 was designed for critical applications such as PCs, servers,
workstations, and telecommunications equipment.
Figure 1 shows the Powerware 5130 UPS with an optional Extended
Battery Module (EBM).
1
2
Figure 1. Powerware 5130 UPS with Optional EBM
INTRODUCTION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
2
Providing outstanding performance and reliability, the Powerware 5130’s
unique benefits include:
S Hours of extended runtime with up to four EBMs.
S Start-on-battery capability for powering up the UPS even if utility
power is not available.
S Hot-swappable batteries that simplify maintenance by allowing you to
replace batteries safely without powering down the critical load.
S Shutdown control through the remote power-off (RPO) and remote
on/off (ROO) port.
S Two standard communication options with a USB port and an RS-232
serial port.
S Advanced power management for graceful shutdowns and power
monitoring.
S Sequential shutdown and load management through separate
receptacle groups, called load segments (PowerShare).
S Optional communication cards with enhanced communication
capabilities for increased power protection and control.
S Backed by worldwide agency approvals.
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
3
Chapter 2 Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the
equipment and save this manual for future reference.
DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS.
WARNING
S This UPS contains its o wn energy source (batteries). The output receptacles may carry
live voltage even when the UPS is not connected to an AC supply.
S For 230V models, the output receptacles may remain electrically live. If the input power
source in your application is wired line-to-neutral (as in most European applications), the
voltage to the output receptacles is 0 V. With line-to-line input wiring, the voltage to the
output receptacles is 115V (measured from line-to-ground or line-to-neutral, depending
on the UPS wiring).
S Do not remove or unplug the input cord when the UPS is turned on. This removes the
safety ground from the UPS and the equipment connected to the UPS.
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature
must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95%
maximum).
S To comply with international standards and wiring regulations, the total equipment
connected to the output of this UPS must not have an earth leakage current greater than
3.5 milliamperes.
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
19
Chapter 3 Installation
This section explains:
S Equipment inspection
S UPS internal battery connection
S UPS setup and installation, including Extended Battery Modules
(EBMs)
S Remote power-off (RPO) or remote on/off (ROO) installation
S UPS rear panels
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping
cartons and packing materials for the carrier or place of purchase and file
a claim for shipping damage. If you discover damage after acceptance,
file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with
the carrier within 15 days of receipt of the equipment; 2) Send a copy of
the damage claim within 15 days to your service representative.
NOTE Check the battery recharge date on the shipping carton label. If the date has passed
and the batteries were never recharged, do not use the UPS. Contact your service
representative.
INSTALLATION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
20
Checking the Accessory Kit
Verify that the following additional items are included with the UPS:
Table 1. UPS Accessory Kit
Item Description
UPS user’s guide or CD
Quick start instructions
UPS front cover
USB cable
RS-232 serial cable
Rackmounting kit for 19-inch (48 cm) bays
2U models only.
Two pedestals with screws for tower position
Optional.
Network Management Card
INSTALLATION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
21
The high-voltage models include the following additional items:
Table 2. Additional High-Voltage Model Accessory Items
Item Description
Two cord-retention brackets
Two equipment power cords
2500–3000 VA models only.
Power cord
If you ordered an optional EBM, verify that the following items are
included with the EBM:
Table 3. EBM Accessory Items
Item Description
EBM user’s guide
EBM cable
EBM communication cable
Rackmounting kit for 19-inch (48 cm) bays
Joining bracket and screws for tower position
INSTALLATION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
22
Connecting the UPS Internal Battery
To ensure proper battery operation:
1. Verify that the UPS is off and unplugged.
2. Connect the internal battery connectors by firmly pressing the
connectors together (see Figure 2).
1
2
Figure 2. Connecting t he Internal Battery Connectors
NOTE A small amount of arcing may occur when connecting the batteries. This is normal
and does not damage the unit or present any safety concern.
3. Install the UPS front cover and snap into place (see Figure 3).
1
2
Figure 3. Installing the UPS Front Cover
4. Continue to the following section, “UPS Setup.”
INSTALLATION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
23
UPS Setup
The Powerware 5130 UPS is designed for flexible configurations and can
be installed in a rack or as a standalone cabinet.
If you are installing the UPS in a rack, continue to the following section,
“Rackmount Setup;” otherwise, continue to “Tower Setup” on page 25.
Rackmount Setup
The rail kit can be mounted in 19-inch panel (48 cm) racks from 24 to
30 inches (61 to 76 cm) deep and includes:
S Left and right sliding rail assemblies
S (12) M5 washers
S (12) M5×12 mm Phillips
®
-head screws
S (8) M4×5 mm Phillips-head screws
S (2) mounting brackets with handles
Required Tools
To assemble the components, a #2 Phillips screwdriver may be needed.
INSTALLATION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
24
Installing the Rail Kit
CAUTION
The UPS and EBM are heavy (see page 52). A minimum of two people are required to lift the
cabinets into the rack.
NOTE Mounting rails are required for each UPS and EBM cabinet. If mounting rails are not
already installed in your rack, contact your local distributor to order rail kits.
To install the rail kit:
1. Adjust the rail size for the depth of your rack.
2. Select the proper holes in the rail for positioning the UPS in the
desired location in the rack.
3. Using two M5 washers and two M5 screws, attach the rail to the
rear of the rack (see Figure 4).
4. Secure the rail to the front of the rack with two M5 washers and
two M5 screws.
5. Repeat Steps 3 and 4 for the other rail.
1
2
Figure 4. Installing the Rail Kit
INSTALLATION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
25
6. Place the UPS on a flat, stable surface with the front of the UPS
facing you.
7. Attach the supplied mounting brackets to the cabinet and secure
with four M4 screws on each side (see Figure 4).
8. If installing optional EBMs, repeat Steps 1 and 7 for each cabinet.
NOTE The UPS and EBMs MUST be installed at the bottom of the rack. If placed in a rack
with existing equipment, the rack must be reconfigured to allow the UPS installation at the
bottom of the rack.
NOTE The EBMs must be installed below the UPS.
9. Slide the UPS and any optional EBMs into the rack.
10. Secure the front of the cabinet to the r ack using two M5 washers
and two M5 screws on each side (see Figure 4).
11. Continue to “Installing the UPS” on page 28.
Tower Setup
The setup varies depending on the size of the cabinet you are installing:
1. Carefully position the cabinet upright with the air vents at the top
(see Figure 5).
1
2
Air Vents
Figure 5. 3U Cabinet
INSTALLATION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
26
2. For one 2U cabinet, the pedestals must be installed. Continue to
Step 3.
For one 3U cabinet, continue to “Installing the UPS” on page 28.
For two or more cabinets, the joining brackets must be installed. Skip
to Step 5.
3. Align the pedestals with the screw holes on the sides of the UPS
cabinet. Secure the pedestals with the captive screws.
1
2
Figure 6. Installing UPS Pedestals (for One 2U Cabinet)
4. Continue to the following section, “Installing the UPS.”
INSTALLATION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
27
5. Align each joining bracket with the adjacent cabinet screw holes
and secure with the supplied screws (see Figure 7).
NOTE Joining brackets are required for installations with two or more cabinets.
Joining Bracket
Figure 7. Installing the Joining Brackets
6. If installing additional EBMs, repeat Step 5 for each cabinet.
7. Continue to the following section, “Installing the UPS.”
INSTALLATION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
28
Installing the UPS
NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage
may o ccur t o your equipment and void your warranty.
See “UPS Rear Panels” on page 33 for the rear panel of each model.
To install the UPS and optional EBMs:
1. If installing an optional EBM, continue to Step 2; otherwise,
continue to Step 3.
2. Plug the EBM cable into the battery connector. Plug the EBM
communication cable into the RJ-11 port. See Figure 8.
Up to four EBMs may be connected to the UPS.
EBM Communication
Cable
EBM Cable
EBM Battery Connectors
Figure 8. UPS Installation with Four EBMs
INSTALLATION
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
29
3. If you plan to install power management software, connect your
computer to the USB port or RS-232 communication port using the
supplied communication cable.
OR
Figure 9. Installing a Communication Cable
4. For rackmount installations only. If your rack has conductors for
grounding or bonding of ungrounded metal parts, connect the
ground cable (not included) to the ground bonding screw. See “UPS
Rear Panels” on page 33.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74

Eaton 1250-3000 VA User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI