Eaton Powerware 5125 Two-in-One EBM User manual

Category
Toys
Type
User manual

Eaton Powerware 5125 Two-in-One EBM is a device that can be added to the 2400/3000 VA Powerware 5125 uninterruptible power system (UPS) to extend the available battery time. The EBM can provide up to 110 minutes of battery runtime at full load and 229 minutes at half load when used with the 2400 VA UPS, and up to 90 minutes of battery runtime at full load and 190 minutes at half load when used with the 3000 VA UPS. The EBM is also hot-swappable, meaning that it can be replaced without powering down the UPS. This makes it ideal for use in critical applications where downtime is unacceptable.

Eaton Powerware 5125 Two-in-One EBM is a device that can be added to the 2400/3000 VA Powerware 5125 uninterruptible power system (UPS) to extend the available battery time. The EBM can provide up to 110 minutes of battery runtime at full load and 229 minutes at half load when used with the 2400 VA UPS, and up to 90 minutes of battery runtime at full load and 190 minutes at half load when used with the 3000 VA UPS. The EBM is also hot-swappable, meaning that it can be replaced without powering down the UPS. This makes it ideal for use in critical applications where downtime is unacceptable.

Powerware 5125 Two-in-One
Extended Battery Module (EBM)
User’s Guide
®
For use with the Powerware 5125 Two-in-One
2400/3000 VA UPS Models
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the
associated warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for
additional information, such as important operating and maintenance
instructions.
RJ-45 RECEPTACLE - For 230V models only: this receptacle provides network
interface connections. Do not plug telephone or telecommunications equipment
into this receptacle.
This symbol indicates that you should not discard the UPS or the UPS batteries
in the trash. This product contains sealed, lead-acid batteries and must be
disposed of properly. For more information, contact your local recycling/reuse or
hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local
recycling/reuse or hazardous waste center.
Powerware is a registered trademark of Eaton Electrical Inc.
ECopyright 2003–2006 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be
reproduced in any way without the express written approval of Eaton Corporation.
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
i
Table of Contents
1 Introduction 1.........................................................
Safety Warnings 1......................................................................
2 Installation 13..........................................................
Inspecting the Equipment 13................................................................
EBM Installation 13......................................................................
Rack-Mount Installation 14..............................................................
Tower Installation 17..................................................................
3 EBM Maintenance 21....................................................
UPS and Battery Care 21..................................................................
Storing the UPS and Batteries 21............................................................
When to Replace Batteries 21...............................................................
How to Replace Extended Battery Modules 22...................................................
Recycling the Used Battery or UPS 24.........................................................
4 Service and Support 25..................................................
TABLE OF CONTENTS
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
ii
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
1
Chapter 1 Introduction
The Extended Battery Module (EBM) can be added to the 2400/3000 VA
Powerware
®
5125 uninterruptible power system (UPS) to extend the
available b attery time (see Table 1). Up to four EBMs can be installed
with the Powerware 5125 UPS.
Table 1. Battery Runtimes (in Minutes at Full/Half Load)
Model UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
2400 VA 7/19 35/73 60/124 85/177 110/229
3000 VA 5/15 25/61 49/103 69/146 90/190
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the EBM. Please read all instructions before operating the equipment and
save this manual for future reference.
WARNING
This UPS contains its own energy source (batteries). The UPS output receptacles may carry
live voltage even when the UPS is not connected to an AC supply.
CAUTION
S Batteries can present a risk of electrical shock or burn from high short-circuit current.
Observe proper precautions. Servicing should be performed by qualified service
personnel knowledgeable of batteries and required precautions. Keep unauthorized
personnel away from batteries.
S Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
13
Chapter 2 Installation
NOTE If you a re installing the UPS and the Extended Battery Module (EBM) together,
follow the installation instructions in the UPS user’s guide.
This section explains:
S Equipment inspection
S UPS and EBM setup
S EBM installation
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping
cartons and packing materials for the carrier or place of purchase and file
a claim for shipping damage. If you discover damage after acceptance,
file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with
the carrier within 15 days of receipt of the equipment; 2) Send a copy of
the damage claim within 15 days to your service representative.
NOTE Check the battery recharge date on the shipping carton label. If the date has expired
and the batteries were never recharged, do not use the UPS. Contact your service
representative.
EBM Installation
The Powerware 5125 EBM is designed for flexible configurations and
can be installed in a rack or as a standalone cabinet.
If you are installing the EBM in a rack, continue to the following section
“Rack-Mount Installation;” otherwise, continue to “Tower Installation”
on page 17.
INSTALLATION
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
14
Rack-Mount Installation
The EBM can be installed in 19-inch racks and needs only 2U of valuable
rack space.
CAUTION
The EBM is heavy (54.9 kg/121 lb). A minimum of two people are required to lift the cabinet
into the rack.
NOTE Fixed mounting rails are required for each UPS and EBM cabinet. If fixed rails are
not already installed in your rack, contact your local distributor to order rail kits.
To install the EBM in a rack:
1. Place the E BM on a flat, stable surface with the front of the EBM
facing toward you.
2. Attach the supplied mounting handles to the mounting brackets and
secure with the supplied screws (see Figure 1).
3. If installing additional EBMs, repeat S teps 1 and 2 for each cabinet.
Mounting Handle
Mounting
Bracket
Figure 1. Installing the Mounting Handles
INSTALLATION
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
15
NOTE The UPS and EBMs MUST be installed at the bottom of the rack. If placed in a rack
with existing equipment, the rack must be reconfigured to allow the UPS installation at the
bottom of the rack.
NOTE The EBMs must be installed below the UPS as shown in Figure 2.
4. Slide t he EBMs into the rack.
5. Secure the cabinets to the rack according to the rail kit instructions.
UPS
EBMs
Figure 2. Rack-Mount UPS with EBMs
6. Verify that all battery circuit breakers are in the OFF (O) position
(see Figure 3).
7. Plug the E BM cable(s) into the battery connector(s) as shown in
Figure 3. Up to four EBMs may be connected to the UPS.
8. Follow the installation instructions in the Powerware 5125
Two-in-One UPS (2500/3000 VA) User’s Guide for installing the
UPS.
NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is
recommended that the batteries charge for 24 hours after installation or long-term storage.
NOTE Ensure maximum battery runtime by using the ERM configuration tool on the
Software Suite CD.
NOTE If more than two EBMs are installed, an external battery charger is recommended
for faster recharge times.
INSTALLATION
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
16
UPS Battery
Connector
EBM Cable
ON OFF
Battery Circuit Breaker
UPS
EBM
EBM
EBM Battery
Connectors
Figure 3. Rack-Mount EBM Connections (120V Model Shown)
INSTALLATION
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
17
Tower Installation
The mounting brackets must be removed before positioning the
cabinets f or a tower installation. Unscrew and remove t he mounting
brackets on each side of all cabinets as shown in Figure 4.
Mounting
Bracket
Figure 4. Removing the Mounting Brackets
The setup varies depending on the number of cabinets you are installing:
1. For two cabinets, the pedestals and the joining brackets must be
installed. Skip to Step 2.
For three or more cabinets, the joining brackets must be installed. Skip
to Step 6.
2. Place the UPS cabinet horizontally so that the left end of the cabinet
is accessible (see Figure 5).
Figure 5. Installing UPS Pedestals (for Two Cabinets)
3. Align t he pedestals with the screw holes on the end of the UPS
cabinet. S ecure the pedestals with the screws provided in the
accessory kit.
INSTALLATION
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
18
4. Place the E BM cabinet upside down so that the right end of the
cabinet is accessible (see Figure 6).
Figure 6. Installing EBM Pedestals
5. Align t he pedestals with the screw holes on the end of the EBM
cabinet. S ecure the pedestals with the screws provided in the
accessory kit.
6. Carefully position the cabinets upright with the air vents at the top
(see Figure 7 or Figure 8).
Air Vents
Figure 7. Pedestals with Two Cabinets
NOTE Pedestals are required for installations with one or two cabinets. Joining brackets
are required for installations with two or more cabinets.
INSTALLATION
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
19
Air Vents
Figure 8. Tower Setup with Three Cabinets
7. Align each joining bracket w ith t he adjacent corner screw holes and
secure with the supplied screws (see Figure 9).
Joining Bracket
EBM
UPS
Joining Bracket
Figure 9. Installing the Joining Brackets (Top View with Pedestals)
8. If installing additional EBMs, repeat Step 7 for each cabinet.
INSTALLATION
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
20
9. Verify that all battery circuit breakers are in the OFF (O) position
(see Figure 10).
10. Plug the EBM cable(s) into the battery connector(s) as shown in
Figure 10. Up to four EBMs may be connected to the UPS.
11. Follow the installation instructions in the Powerware 5125
Two-in-One UPS (2500/3000 VA) User’s Guide for installing the
UPS.
NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is
recommended that the batteries charge for 24 hours after installation or long-term storage.
NOTE Ensure maximum battery runtime by using the ERM configuration tool on the
Software Suite CD.
NOTE If more than two EBMs are installed, an external battery charger is recommended
for faster recharge times.
UPS Battery
Connector
EBM Battery
Connectors
Joining Brackets
EBM Cables
ON
OFF
Battery Circuit Breaker
UPSEBMEBM
Figure 10. Tower EBM Connections (120V Model Shown)
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
21
Chapter 3 EBM Maintenance
This section explains how to:
S Care for the UPS and batteries
S Replace the Extended Battery Modules (EBMs)
S Recycle used batteries or UPS
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS
clean and dust-free. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 5 years to keep units running at peak efficiency.
Storing t he UPS and Batteries
If you store the UPS for a long period, recharge the batteries every
6 months by plugging the UPS into a power outlet. The batteries charge
to 90% capacity in approximately 3 hours. However, it is recommended
that the batteries charge for 24 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date
has expired and the batteries were never recharged, do not use the
UPS. Contact your service representative.
When to Replace Batteries
When the indicator flashes and the audible alarm beeps once every
five seconds, the batteries may need replacing. Contact your service
representative t o order new batteries.
EBM MAINTENANCE
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
22
How to Replace Extended Battery Modules
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
With the hot-swappable battery feature, UPS batteries can be replaced
easily without turning the UPS off or disconnecting the load.
If you prefer t o remove input power to change the batteries, see
“Turning the UPS Off” in the UPS user’s guide.
Consider all warnings, cautions, and notes before replacing batteries.
WARNING
S Batteries can present a r isk of electrical shock or burn from high short-circuit current. The
following precautions should be observed: 1) Remove watches, rings, o r other metal
objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of
batteries.
S ELECTRIC ENERGY HAZARD. Do not attempt to a lter any battery wiring or connectors.
Attempting to alter wiring can cause injury.
CAUTION
The EBM is heavy (54.9 kg/121 lb). A minimum of two people are required to lift the cabinet
into the rack.
To replace the E BMs:
1. Switch all battery circuit breakers to the OFF (O) position (see
Figure 11).
2. Unplug the E BM cable from the UPS.
If additional E BMs are installed, unplug the EBM cable from the
battery connector on each EBM.
3. If the EBM is in a tower configuration, remove the joining brackets.
4. If the EBM has pedestals installed, remove the pedestals and
retain.
5. If the EBM is in a rack, attach the supplied mounting handles to the
mounting brackets on the new EBM.
6. Replace the E BM. S ee “Recycling the Used Battery or UPS” on
page 24 for proper disposal.
EBM MAINTENANCE
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
23
7. Reinstall the pedestals if removed in Step 4.
8. Reinstall the joining brackets if removed in Step 3.
9. Plug the EBM cable(s) into the battery connectors as shown in
Figure 11.
10. Remove the breaker tie from the circuit breaker on all EBMs.
11. Switch all battery circuit breakers to the ON (
| ) position.
UPS Battery
Connector
EBM Battery
Connectors
Joining Brackets
EBM Cables
ON
OFF
Battery Circuit Breaker
Figure 11. EBM Connections
EBM MAINTENANCE
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
24
Recycling t he Used Battery or UPS
Contact your local recycling or hazardous waste center for information
on proper disposal of the used battery or UPS.
WARNING
S Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper
disposal of batteries is required. Refer to your local codes for disposal requirements.
S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.
CAUTION
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed,
lead-acid batteries and must be disposed of properly. For more information, contact your
local recycling/reuse or hazardous waste center.
CAUTION
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper
disposal, contact your local recycling/reuse o r hazardous waste center.
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
25
Chapter 4 Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor or the Help Desk at one of the following telephone numbers
and ask for a UPS technical representative.
United States:
1-800-356-5737 or 1-919-870-3149
Canada: 1-800-461-9166 ext 260
All other countries: Call your local service representative
Please have the following information ready when you call the Help
Desk:
S Model number
S Serial number
S Version number (if available)
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization
(RMA) Number. This number must appear on the outside of the package
and o n t he Bill Of Lading (if applicable). Use the original packaging or
request packaging from the Help Desk or distributor. Units damaged in
shipment as a result of improper packaging are not covered under
warranty. A replacement or repair unit will be shipped, freight prepaid for
all warrantied units.
NOTE For critical applications, immediate replacement may be available. Call the Help
Desk
for the dealer or distributor nearest you.
SERVICE AND SUPPORT
EATON Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide S 164201378 Rev C www.power-
ware.com
26
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30

Eaton Powerware 5125 Two-in-One EBM User manual

Category
Toys
Type
User manual

Eaton Powerware 5125 Two-in-One EBM is a device that can be added to the 2400/3000 VA Powerware 5125 uninterruptible power system (UPS) to extend the available battery time. The EBM can provide up to 110 minutes of battery runtime at full load and 229 minutes at half load when used with the 2400 VA UPS, and up to 90 minutes of battery runtime at full load and 190 minutes at half load when used with the 3000 VA UPS. The EBM is also hot-swappable, meaning that it can be replaced without powering down the UPS. This makes it ideal for use in critical applications where downtime is unacceptable.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI