Toshiba RAV-SM2244AT7 User manual

Category
Split-system air conditioners
Type
User manual
R410A
FILE NO. A09-004
SERVICE MANUAL
AIR-CONDITIONER
SPLIT TYPE
OUTDOOR UNIT
<DIGITAL INVERTER>
RAV-SM2244AT8-E RAV-SM2804AT8-E
RAV-SM2244AT8Z-E RAV-SM2804AT8Z-E
RAV-SM2244AT8ZG-E RAV-SM2804AT8ZG-E
RAV-SM2244AT7 RAV-SM2804AT7
RAV-SM2244AT7Z RAV-SM2804AT7Z
RAV-SM2244AT7ZG RAV-SM2804AT7ZG
PRINTED IN JAPAN, Jun, 2009 ToMo
– 2 –
Adoption of New Refrigerant
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional
refrigerant R22 in order to prevent destruction of the ozone layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to
have a service person do it. Do not attempt it yourself.
The cleaning diagram for the air filter is there for the service person, and not for the customer.
CONTENTS
SAFETY CAUTION ............................................................................................ 4
1. SPECIFICATIONS .................................................................................... 11
1-1. Indoor Unit......................................................................................................... 11
1-2. Outdoor Unit...................................................................................................... 24
1-3. Operation Characteristic Curve....................................................................... 25
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)....................................... 27
2-1. Outdoor Unit...................................................................................................... 27
3. OUTDOOR UNIT REFRIGERANTING CYCLE DIAGRAM ...................... 31
4. WIRING DIAGRAM................................................................................... 33
4-1. Outdoor Unit...................................................................................................... 33
5. SPECIFICATIONS OF ELECTRICAL PARTS .......................................... 34
5-1.Outdoor Unit ......................................................................................................... 34
6. REFRIGERANT R410A ............................................................................ 35
6-1. Safety During Installation/Servicing ............................................................... 35
6-2. Refrigerant Piping Installation....................................................................... 35
6-3. Tools .................................................................................................................. 39
6-4. Recharging of Refrigerant................................................................................ 39
6-5. Brazing of Pipes................................................................................................ 40
6-6. Instructions for Re-use Piping of R22 or R407C ............................................ 42
3
7. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS ........... 45
7-1. Outdoor Unit Control ........................................................................................ 45
7-2. Outline of Main Controls .................................................................................. 49
8. TROUBLESHOOTING .............................................................................. 55
8-1. Summary of Troubleshooting........................................................................... 55
8-2. Troubleshooting................................................................................................ 57
9. SETUP AT LOCAL SITE AND OTHERS .................................................. 80
9-1. Calling of Error History .................................................................................... 80
9-2. Group Control Operation ................................................................................. 80
9-3. Outdoor Unit...................................................................................................... 82
10. ADDRESS SETUP.................................................................................... 89
10-1. Address Setup Procedure................................................................................ 89
10-2. Address Setup & Group Control...................................................................... 90
10-3. Remote Controller Wiring................................................................................. 93
10-4. Address Setup (Manual setting from remote controller)............................... 94
10-5. Confirmation of Indoor Unit No. Position ....................................................... 95
11. INSTALLATION MANUAL ........................................................................ 97
12. REPLACEMENT OF
THE SERVICE P.C. BOARD (4316V392) MCC-1599 ............................. 110
13. HOW TO EXCHANGE COMPRESSOR .................................................. 111
13-1. Exchanging Procedure of Compressor (Outline)......................................... 111
13-2. Exchange of Compressor .............................................................................. 111
14. DETACHMENTS ..................................................................................... 112
14-1. Outdoor Unit.................................................................................................... 112
15. EXPLODED VIEWS AND PARTS LIST .................................................. 124
15-1. Outdoor Unit.................................................................................................... 124
15-2. Inverter Assembly........................................................................................... 126
15-3. Outdoor Unit.................................................................................................... 128
15-4. Inverter Assembly........................................................................................... 130
– 4 –
SAFETY CAUTION
The important contents concerned to the safety are described on the product itself and on this Service Manual.
Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
[Explanation of illustrated marks]
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions
(Refer to the Parts disassembly diagram (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
Indication
DANGER
WARNING
CAUTION
Explanation
Indicates contents assumed that an imminent danger causing a death or serious injury of
the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the
repair engineers, the third parties, and the users due to troubles of the product after work
when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage () may be caused on the
repair engineers, the third parties, and the users due to troubles of the product after work
when an incorrect work has been executed.
Mark Explanation
Indicates prohibited items (Forbidden items to do)
The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do)
The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (Including danger/warning)
The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
Turn off breaker.
Execute discharge
between terminals.
Prohibition
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric
shock is caused by high voltage resulted in a death or injury.
During operation, a high voltage with 400V or higher of circuit () at secondary circuit of the
high-voltage transformer is applied.
If touching a high voltage with the naked hands or body, an electric shock is caused even if using an
electric insulator.
Attach a plate indicating “WORKING” or others on the breaker so that you don’t accidentally turn
on the breaker during work.
: For details, refer to the electric wiring diagram.
When removing the front panel or cabinet, execute short-circuit and discharge between
high-voltage capacitor terminals.
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury.
After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor.
Do not turn on the breaker under condition that the front panel and cabinet are removed.
An electric shock is caused by high voltage resulted in a death or injury.
DANGER
5
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
Refrigerant
Assembly/Cabling
Before troubleshooting or repair work, check the earth wire is connected to the earth
terminals of the main unit, otherwise an electric shock is caused when a leak occurs.
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (
).
If unspecified parts are used, a fire or electric shock may be caused.
: For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except
the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts.
Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead wires with crimp contact, etc, put the closed end side
upward and then apply a water-cut method, otherwise a leak or production of fire is
caused at the users side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire
before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room.
When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may
catch the inflammables.
Check the used refrigerant name and use tools and materials of the parts which
match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a
position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the
service port is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A.
For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the
refrigerating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in
the refrigerating cycle changes resulted in change of air conditioner characteristics or
refrigerant over the specified standard amount is charged and an abnormal high pressure is
applied to the inside of the refrigerating cycle resulted in cause of breakage or injury.
Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute
vacuuming, and then newly recharge the specified amount of liquid refrigerant.
In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant
or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the
refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire
such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with
recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a
serious accident such as breakage or injury is caused.
After repair work, surely assemble the disassembled parts, and connect and lead the
removed wires as before. Perform the work so that the cabinet or panel does not
catch the inner wires.
If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or
fire is caused at users side.
WARNING
6
After the work has finished, be sure to use an insulation tester set (500V Megger) to
check the resistance is 2M or more between the charge section and the non-charge
metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at users side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates.
A case of leakage of the refrigerant and the closed room full with gas is dangerous because
a shortage of oxygen occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber
gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down and
tighten the service valve, otherwise the refrigerant gas may leak into the room.
The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking
stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such
as a multi air conditioner in a sub-room, it is necessary that the density does not the
limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric
shock or fire is caused.
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused.
For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test
run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused.
Before test run, install the front panel and cabinet.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable.
If check is not executed, a fire, an electric shock or an injury is caused.
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
Check after repair
Check after reinstallation
WARNING
Put on gloves
Cooling check
Be sure to put on the gloves () and a long sleeved shirt:
otherwise an injury may be caused with the parts, etc.
() Heavy gloves such as work gloves
When the power was turned on, start to work after the equipment has been
sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating
operation, a burn may be caused.
CAUTION
7
New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22).
Accompanied with change of refrigerant, the refrigerating oil has been also changed.
Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the
refrigerating cycle of the air conditioner with new refrigerant during installation work or service work.
If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident.
Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
1) Do not mix the other refrigerant or refrigerating oil.
For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of
the former refrigerant in order to prevent mixture of them.
2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are
specified for R410A.
3) In the installation time, use clean pipe materials and work with great attention so that water and others do
not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc.
Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4) For the earth protection, use a vacuum pump for air purge.
5) R410A refrigerant is azeotropic mixture type refrigerant.
Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the
refrigerant changes and then characteristics of the air conditioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used.
It is necessary to select the most appropriate pipes to conform to the standard.
Use clean material in which impurities adhere inside of pipe or joint to a minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type.
When using a long copper pipe for R410A, it is recommended to select Copper or copper-base pipe without
seam and one with bonded oil amount 40mg/10m or less.
Also do not use crushed, deformed, discolored (especially inside) pipes.
(Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2) Joint
The flare joint and socket joint are used for joints of the copper pipe.
The joints are rarely used for installation of the air conditioner. However clear impurities when using them.
8
4. Tools
1. Required Tools for R410A
Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary,
etc. Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
(Note) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary
as the general tools.
1) Vacuum pump. Use vacuum pump by attaching vacuum pump adapter.
2) Torque wrench 8) Spanner or Monkey wrench
3) Pipe cutter 9) Hole core drill
4) Reamer 10) Hexagon wrench (Opposite side 4mm)
5) Pipe bender 11) Tape measure
6) Level vial 12) Metal saw
7) Screwdriver (+, )
Also prepare the following equipments for other installation method and run check.
1) Clamp meter 3) Insulation resistance tester (Megger)
2) Thermometer 4) Electroscope
No.
Q
R
S
T
U
V
W
X
Y
Used tool
Flare tool
Copper pipe gauge for
adjusting projection margin
Torque wrench
Gauge manifold
Charge hose
Vacuum pump adapter
Electronic balance for
refrigerant charging
Refrigerant cylinder
Leakage detector
Usage
Pipe flaring
Flaring by conventional
flare tool
Tightening of flare nut
Evacuating, refrigerant
charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge
Gas leakage check
R410A
air conditioner installation
Existence of Whether conven-
new equipment tional equipment
for R410A can be used
Yes (Note)
Yes (Note)
Yes No
Yes No
Yes No
Yes Yes
Yes No
Yes No
Conventional air
conditioner installation
Whether conventional
equipment can be used
Yes
(Note)
No
No
Yes
Yes
No
Yes
9
n Combination Pattern (Indoor Unit / Outdoor Unit)
<RAV-SM2244AT series>
Simultaneous twin
4-way air discharge
cassette type
RAV-SM1104UT-E
RAV-SM1104UT-E
Concealed
duct type
RAV-SM1102BT-E
RAV-SM1102BT-E
Ceiling type
RAV-SM1102CT-E
RAV-SM1102CT-E
Simultaneous triple
4-way air discharge
cassette type
RAV-SM804UT-E
RAV-SM804UT-E
RAV-SM804UT-E
Concealed
duct type
RAV-SM802BT-E
RAV-SM802BT-E
RAV-SM802BT-E
Ceiling type
RAV-SM802CT-E
RAV-SM802CT-E
RAV-SM802CT-E
High wall type
(2 series)
RAV-SM802KRT-E
RAV-SM802KRT-E
RAV-SM802KRT-E
Simultaneous double twin
4-way air discharge
cassette type
RAV-SM564UT-E
RAV-SM564UT-E
RAV-SM564UT-E
RAV-SM564UT-E
Compact 4-way
cassette (600×600) type
RAV-SM562MUT-E
RAV-SM562MUT-E
RAV-SM562MUT-E
RAV-SM562MUT-E
Slim duct type
RAV-SM564SDT-E
RAV-SM564SDT-E
RAV-SM564SDT-E
RAV-SM564SDT-E
Concealed
duct type
RAV-SM562BT-E
RAV-SM562BT-E
RAV-SM562BT-E
RAV-SM562BT-E
Ceiling type
RAV-SM562CT-E
RAV-SM562CT-E
RAV-SM562CT-E
RAV-SM562CT-E
High wall type
(2 series)
RAV-SM562KRT-E
RAV-SM562KRT-E
RAV-SM562KRT-E
RAV-SM562KRT-E
<RAV-SM2804AT series>
Simultaneous twin
4-way air discharge
cassette type
RAV-SM1404UT-E
RAV-SM1404UT-E
Concealed
duct type
RAV-SM1402BT-E
RAV-SM1402BT-E
Ceiling type
RAV-SM1402CT-E
RAV-SM1402CT-E
Simultaneous triple
4-way air discharge
cassette type
RAV-SM804UT-E
RAV-SM804UT-E
RAV-SM804UT-E
Concealed
duct type
RAV-SM802BT-E
RAV-SM802BT-E
RAV-SM802BT-E
Ceiling type
RAV-SM802CT-E
RAV-SM802CT-E
RAV-SM802CT-E
High wall type
(2 series)
RAV-SM802KRT-E
RAV-SM802KRT-E
RAV-SM802KRT-E
Simultaneous double twin
4-way air discharge
cassette type
RAV-SM804UT-E
RAV-SM804UT-E
RAV-SM804UT-E
RAV-SM804UT-E
Concealed
duct type
RAV-SM802BT-E
RAV-SM802BT-E
RAV-SM802BT-E
RAV-SM802BT-E
Ceiling type
RAV-SM802CT-E
RAV-SM802CT-E
RAV-SM802CT-E
RAV-SM802CT-E
High wall type
(2 series)
RAV-SM802KRT-E
RAV-SM802KRT-E
RAV-SM802KRT-E
RAV-SM802KRT-E
10
Slimultaneous twin
Simultaneous triple
Simultaneous double twin
RAV-SM2244AT series
SM110 SM110
SM80 SM80 SM80
SM56 SM56 SM56 SM56
Branch kit
RBC-TWP101E
RBC-TRP100E
RBC-DTWP101E
Slimultaneous twin
Simultaneous triple
Simultaneous double twin
RAV-SM2804AT series
SM140 SM140
SM80 SM80 SM80
SM80 SM80 SM80 SM80
Branch kit
RBC-TWP101E
RBC-TRP100E
RBC-DTWP101E
– 11 –
1. SPECIFICATIONS
1-1. Indoor Unit
1-1-1. 4-Way Cassette Type
<Twin type>
: IEC standard
Indoor unit 1 RAV-SM 1104UT-E 1404UT-E 1104UT-E 1404UT-E
Model Indoor unit 2 RAV-SM 1104UT-E 1404UT-E 1104UT-E 1404UT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0
Heating capacity (kW) 22.4 27.0 22.4 27.0
Power supply 3 phase 380 – 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 10.09 – 9.24 13.24 – 12.12 10.09 13.24
Power consumption (kW) 6.24 8.19 6.24 8.19
Cooling Power factor (%) 94 94 94 94
EER 3.21 2.81 3.21 2.81
Electrical
Energy efficiency class AC
Running current (A) 9.41 – 8.61 12.09 – 11.07 9.41 12.09
characteristics
Power consumption (kW) 5.82 7.48 5.82 7.48
Heating Power factor (%) 94 94 94 94
COP 3.85 3.61 3.85 3.61
Energy efficiency class AA
Maximum current (A) 18 22 18 22
Fan Turbo fan Turbo fan Turbo fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 33.5/24.0/19.5 35.0/24.0/20.5 33.5/24.0/19.5 35.0/24.0/20.5
Motor (W) 68 72 68 72
Sound pressure level H/M/L (dB•A) 43 / 38 / 33 44 / 38 / 34 43 / 38 / 33 44 / 38 / 34
Sound power level H/M/L (dB•A) 58 / 53 / 48 59 / 53 / 49 58 / 53 / 48 59 / 53 / 49
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Outdoor lower (m) 30 30 30 30
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit – Pipe branch
Gas side (mm) 28.6 28.6 28.6 28.6
Connecting pipe
Liquid side (mm) 12.7 12.7 12.7 12.7
Pipe branch – Indoor unit
Gas side (mm) 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5
Sound pressure level Cooling / Heating (dB•A) 56 / 57 57 / 58 56 / 57 57 / 58
Sound power level Cooling / Heating (dB•A) 72 / 74 74 / 75 72 / 74 74 / 75
12
: IEC standard
1-1-2. Duct Type
<Twin type>
Indoor unit 1 RAV-SM 1102BT-E 1402BT-E 1102BT-E 14002BT-E
Model Indoor unit 2 RAV-SM 1102BT-E 1402BT-E 1102BT-E 1402BT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0
Heating capacity (kW) 22.4 27.0 22.4 27.0
Power supply 3 phase 380 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 10.54 15.44 14.13 11.51 15.44
Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41
Electrical
Energy efficiency class CE——
Running current (A) 10.34 9.47 12.80 11.72 10.34 12.80
characteristics
Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41
Energy efficiency class BB——
Maximum current (A) 18 22 18 22
Fan Centrifugal Centrifugal Centrifugal Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 27.0/23.0/18.9 33.0/28.0/23.1 27.0/23.0/18.9 33.0/28.0/23.1
Motor (W) 120 120 120 120
Sound pressure level H/M/L (dBA) 42 / 39 / 36 44 / 41 / 38 42 / 39 / 36 44 / 41 / 38
Sound power level H/M/L (dBA) 57 / 54 / 51 59 / 56 / 53 57 / 54 / 51 59 / 56 / 53
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Outdoor lower (m) 30 30 30 30
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit Pipe branch
Gas side (mm) 28.6 28.6 28.6 28.6
Connecting pipe
Liquid side (mm) 12.7 12.7 12.7 12.7
Pipe branch Indoor unit
Gas side (mm) 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5
Sound pressure level Cooling / Heating (dBA) 56 / 57 57 / 58 56 / 57 57 / 58
Sound power level Cooling / Heating (dBA) 72 / 74 74 / 75 72 / 74 74 / 75
13
1-1-3. Ceiling Type
<Twin type>
Indoor unit 1 RAV-SM 1102CT-E 1402CT-E 1102CT-E 1402CT-E
Model Indoor unit 2 RAV-SM 1102CT-E 1402CT-E 1102CT-E 1402CT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0
Heating capacity (kW) 22.4 27.0 22.4 27.0
Power supply 3 phase 380 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 10.54 15.44 14.13 11.51 15.44
Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41
Electrical
Energy efficiency class CE——
Running current (A) 10.34 9.47 12.80 11.72 10.34 12.80
characteristics
Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41
Energy efficiency class BB——
Maximum current (A) 18 22 18 22
Fan Centrifugal Centrifugal Centrifugal Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 27.5/24.0/21.2 30.0/26.0/23.1 27.5/24.0/21.2 30.0/26.0/23.1
Motor (W) 120 120 120 120
Sound pressure level H/M/L (dBA) 41 / 38 / 35 43 / 40 / 37 41 / 38 / 35 43 / 40 / 37
Sound power level H/M/L (dBA) 56 / 53 / 50 58 / 55 / 52 56 / 53 / 50 58 / 55 / 52
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Outdoor lower (m) 30 30 30 30
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit Pipe branch
Gas side (mm) 28.6 28.6 28.6 28.6
Connecting pipe
Liquid side (mm) 12.7 12.7 12.7 12.7
Pipe branch Indoor unit
Gas side (mm) 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5
Sound pressure level Cooling / Heating (dBA) 56 / 57 57 / 58 56 / 57 57 / 58
Sound power level Cooling / Heating (dBA) 72 / 74 74 / 75 72 / 74 74 / 75
: IEC standard
14
1-1-4. 4-Way Cassette Type
<Triple type>
Indoor unit 1 RAV-SM 804UT-E 804UT-E 804UT-E 804UT-E
Model
Indoor unit 2 RAV-SM 804UT-E 804UT-E 804UT-E 804UT-E
Indoor unit 3 RAV-SM 804UT-E 804UT-E 804UT-E 804UT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0
Heating capacity (kW) 22.4 27.0 22.4 27.0
Power supply 3 phase 380 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 10.54 15.44 14.13 11.51 15.44
Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41
Electrical
Energy efficiency class CE——
Running current (A) 10.34 9.47 12.80 11.72 10.34 12.80
characteristics
Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41
Energy efficiency class BB——
Maximum current (A) 18 22 18 22
Fan Turbo fan Turbo fan Turbo fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 20.5/16.0/13.5 20.5/16.0/13.5 20.5/16.0/13.5 20.5/16.0/13.5
Motor (W) 20 20 20 20
Sound pressure level H/M/L (dBA) 35 / 31 / 28 35 / 31 / 28 35 / 31 / 28 35 / 31 / 28
Sound power level H/M/L (dBA) 50 / 46 / 43 50 / 46 / 43 50 / 46 / 43 50 / 46 / 43
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Outdoor lower (m) 30 30 30 30
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit Pipe branch
Gas side (mm) 28.6 28.6 28.6 28.6
Connecting pipe
Liquid side (mm) 12.7 12.7 12.7 12.7
Pipe branch Indoor unit
Gas side (mm) 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5
Sound pressure level Cooling / Heating (dBA) 56 / 57 57 / 58 56 / 57 57 / 58
Sound power level Cooling / Heating (dBA) 72 / 74 74 / 75 72 / 74 74 / 75
: IEC standard
15
1-1-5. Duct Type
<Triple type>
Indoor unit 1 RAV-SM 802BT-E 802BT-E 802BT-E 802BT-E
Model
Indoor unit 2 RAV-SM 802BT-E 802BT-E 802BT-E 802BT-E
Indoor unit 3 RAV-SM 802BT-E 802BT-E 802BT-E 802BT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0
Heating capacity (kW) 22.4 27.0 22.4 27.0
Power supply 3 phase 380 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 10.54 15.44 14.13 11.51 15.44
Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41
Electrical
Energy efficiency class CE——
Running current (A) 10.34 9.47 12.80 11.72 10.34 12.80
characteristics
Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41
Energy efficiency class BB——
Maximum current (A) 18 22 18 22
Fan Centrifugal Centrifugal Centrifugal Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 19.0/16.2/13.3 19.0/16.2/13.3 19.0/16.2/13.3 19.0/16.2/13.3
Motor (W) 120 120 120 120
Sound pressure level H/M/L (dBA) 40 / 37 / 34 40 / 37 / 34 40 / 37 / 34 40 / 37 / 34
Sound power level H/M/L (dBA) 55 / 52 / 49 55 / 52 / 49 55 / 52 / 49 55 / 52 / 49
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Outdoor lower (m) 30 30 30 30
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit Pipe branch
Gas side (mm) 28.6 28.6 28.6 28.6
Connecting pipe
Liquid side (mm) 12.7 12.7 12.7 12.7
Pipe branch Indoor unit
Gas side (mm) 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5
Sound pressure level Cooling / Heating (dBA) 56 / 57 57 / 58 56 / 57 57 / 58
Sound power level Cooling / Heating (dBA) 72 / 74 74 / 75 72 / 74 74 / 75
: IEC standard
16
1-1-6. Ceiling Type
<Triple type>
: IEC standard
Indoor unit 1 RAV-SM 802CT-E 802CT-E 802CT-E 802CT-E
Model
Indoor unit 2 RAV-SM 802CT-E 802CT-E 802CT-E 802CT-E
Indoor unit 3 RAV-SM 802CT-E 802CT-E 802CT-E 802CT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0
Heating capacity (kW) 22.4 27.0 22.4 27.0
Power supply 3 phase 380 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 10.54 15.44 14.13 11.51 15.44
Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41
Electrical
Energy efficiency class CE——
Running current (A) 10.34 9.47 12.80 11.72 10.34 12.80
characteristics
Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41
Energy efficiency class BB——
Maximum current (A) 18 22 18 22
Fan Centrifugal Centrifugal Centrifugal Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 18.5/16.7/14.6 18.5/16.7/14.6 18.5/16.7/14.6 18.5/16.7/14.6
Motor (W) 60 60 60 60
Sound pressure level H/M/L (dBA) 38 / 36 / 33 38 / 36 / 33 38 / 36 / 33 38 / 36 / 33
Sound power level H/M/L (dBA) 53 / 51 / 48 53 / 51 / 48 53 / 51 / 48 53 / 51 / 48
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Outdoor lower (m) 30 30 30 30
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit Pipe branch
Gas side (mm) 28.6 28.6 28.6 28.6
Connecting pipe
Liquid side (mm) 12.7 12.7 12.7 12.7
Pipe branch Indoor unit
Gas side (mm) 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5
Sound pressure level Cooling / Heating (dBA) 56 / 57 57 / 58 56 / 57 57 / 58
Sound power level Cooling / Heating (dBA) 72 / 74 74 / 75 72 / 74 74 / 75
17
1-1-7. High Wall Type
<Triple type>
: IEC standard
Indoor unit 1 RAV-SM 802KRT-E 802KRT-E 802KRT-E 802KRT-E
Model
Indoor unit 2 RAV-SM 802KRT-E 802KRT-E 802KRT-E 802KRT-E
Indoor unit 3 RAV-SM 802KRT-E 802KRT-E 802KRT-E 802KRT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0
Heating capacity (kW) 22.4 27.0 22.4 27.0
Power supply 3 phase 380 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 10.54 15.44 14.13 11.51 15.44
Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41
Electrical
Energy efficiency class CE——
Running current (A) 10.34 9.47 12.80 11.72 10.34 12.80
characteristics
Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41
Energy efficiency class BB——
Maximum current (A) 18 22 18 22
Fan Cross flow fan Cross flow fan Cross flow fan Cross flow fan
Fan unit Standard air flow H/M/L (m³/min.) 18.5/14.6/12.2 18.5/14.6/12.2 18.5/14.6/12.2 18.5/14.6/12.2
Motor (W) 30 30 30 30
Sound pressure level H/M/L (dBA) 45 / 41 / 36 45 / 41 / 36 45 / 41 / 36 45 / 41 / 36
Sound power level H/M/L (dBA) 60 / 56 / 51 60 / 56 / 51 60 / 56 / 51 60 / 56 / 51
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Outdoor lower (m) 30 30 30 30
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit Pipe branch
Gas side (mm) 28.6 28.6 28.6 28.6
Connecting pipe
Liquid side (mm) 12.7 12.7 12.7 12.7
Pipe branch Indoor unit
Gas side (mm) 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5
Sound pressure level Cooling / Heating (dBA) 56 / 57 57 / 58 56 / 57 57 / 58
Sound power level Cooling / Heating (dBA) 72 / 74 74 / 75 72 / 74 74 / 75
18
1-1-8. 4-Way Cassette Type
<Double twin type>
: IEC standard
Indoor unit 1 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E
Indoor unit 2 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E
Model Indoor unit 3 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E
Indoor unit 4 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E
Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7
Cooling capacity (kW) 20.0 23.0 20.0 23.0
Heating capacity (kW) 22.4 27.0 22.4 27.0
Power supply 3 phase 380 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 10.54 15.44 14.13 11.51 15.44
Power consumption (kW) 7.12 9.55 7.12 9.55
Cooling Power factor (%) 94 94 94 94
EER 2.81 2.41 2.81 2.41
Electrical
Energy efficiency class CE——
Running current (A) 10.34 9.47 12.80 11.72 10.34 12.80
characteristics
Power consumption (kW) 6.40 7.92 6.40 7.92
Heating Power factor (%) 94 94 94 94
COP 3.50 3.41 3.50 3.41
Energy efficiency class BB——
Maximum current (A) 18 22 18 22
Fan Turbo fan Turbo fan Turbo fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 17.5/14.5/13.0 20.5/16.0/13.5 17.5/14.5/13.0 20.5/16.0/13.5
Motor (W) 14 20 14 20
Sound pressure level H/M/L (dBA) 32 / 29 / 28 35 / 31 / 28 32 / 29 / 28 35 / 31 / 28
Sound power level H/M/L (dBA) 47 / 44 / 43 50 / 46 / 43 47 / 44 / 43 50 / 46 / 43
Outdoor unit
Max. total length (m) 70 70 70 70
Outer dimension
Min. length (m) 7.5 7.5 7.5 7.5
Height difference
Outdoor lower (m) 30 30 30 30
Outdoor high (m) 30 30 30 30
Fan Propeller fan Propeller fan Propeller fan Propeller fan
Fan unit Standard air flow high (m³/min.) 133 133 133 133
Motor (W) 100 + 100 100 + 100 100 + 100 100 + 100
Outdoor unit Pipe branch
Gas side (mm) 28.6 28.6 28.6 28.6
Connecting pipe
Liquid side (mm) 12.7 12.7 12.7 12.7
Pipe branch Indoor unit
Gas side (mm) 15.9 15.9 15.9 15.9
Liquid side (mm) 9.5 9.5 9.5 9.5
Sound pressure level Cooling / Heating (dBA) 56 / 57 57 / 58 56 / 57 57 / 58
Sound power level Cooling / Heating (dBA) 72 / 74 74 / 75 72 / 74 74 / 75
19
Indoor unit 1 RAV-SM562MUT-E RAV-SM562MUT-E
Indoor unit 2 RAV-SM562MUT-E RAV-SM562MUT-E
Model Indoor unit 3 RAV-SM562MUT-E RAV-SM562MUT-E
Indoor unit 4 RAV-SM562MUT-E RAV-SM562MUT-E
Outdoor unit RAV-SM2244AT8-E RAV-SM2244AT7
Cooling capacity (kW) 20.0 20.0
Heating capacity (kW) 22.4 22.4
Power supply 3 phase 380 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 10.54 11.51
Power consumption (kW) 7.12 7.12
Cooling Power factor (%) 94 94
EER 2.81 2.81
Electrical
Energy efficiency class C
Running current (A) 10.34 9.47 10.34
characteristics
Power consumption (kW) 6.40 6.40
Heating Power factor (%) 94 94
COP 3.50 3.50
Energy efficiency class B
Maximum current (A) 18 18
Fan Turbo fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 13.3 / 11.2 / 9.1 13.3 / 11.2 / 9.1
Motor (W) 60 60
Sound pressure level H/M/L (dBA) 43 / 39 / 34 43 / 39 / 34
Sound power level H/M/L (dBA) 58 / 54 / 49 58 / 54 / 49
Outdoor unit
Max. total length (m) 70 70
Outer dimension
Min. length (m) 7.5 7.5
Height difference
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Fan Propeller fan Propeller fan
Fan unit Standard air flow high (m³/min.) 133 133
Motor (W) 100 + 100 100 + 100
Outdoor unit
Gas side (mm) 28.6 28.6
First pipe branch
Liquid side (mm) 12.7 12.7
Connecting pipe
First pipe branch
Gas side (mm) 15.9 15.9
Second pipe branch
Liquid side (mm) 9.5 9.5
Second pipe branch
Gas side (mm) 12.7 12.7
Indoor unit
Liquid side (mm) 6.4 6.4
Sound pressure level Cooling / Heating (dBA) 56 / 57 56 / 57
Sound power level Cooling / Heating (dBA) 72 / 74 72 / 74
1-1-9. Compact 4-Way Cassette (600 × 600) Type
<Double twin type>
: IEC standard
20
1-1-10. Slim Duct Type
<Double twin type>
: IEC standard
Indoor unit 1 RAV-SM564SDT-E RAV-SM564SDT-E
Indoor unit 2 RAV-SM564SDT-E RAV-SM564SDT-E
Model Indoor unit 3 RAV-SM564SDT-E RAV-SM564SDT-E
Indoor unit 4 RAV-SM564SDT-E RAV-SM564SDT-E
Outdoor unit RAV-SM2244AT8-E RAV-SM2244AT7
Cooling capacity (kW) 20.0 20.0
Heating capacity (kW) 22.4 22.4
Power supply 3 phase 380 415V 50Hz 3 phase 380V 60Hz
Indoor unit
Running current (A) 11.51 10.54 11.51
Power consumption (kW) 7.12 7.12
Cooling Power factor (%) 94 94
EER 2.81 2.81
Electrical
Energy efficiency class C
Running current (A) 10.34 9.47 10.34
characteristics
Power consumption (kW) 6.40 6.40
Heating Power factor (%) 94 94
COP 3.50 3.50
Energy efficiency class B
Maximum current (A) 18 18
Fan Centrifugal fan Centrifugal fan
Standard air flow H/M/L (m³/min.) 13.0 / 11.3 / 9.7 13.0 / 11.3 / 9.7
Fan unit Motor (W) 60 60
Extermal
Standard (at shipment) (Pa) 10 10
static pressure
Set up for tap exchange (Pa) 10 / 20 / 35 / 50 10 / 20 / 35 / 50
Sound pressure level
Under air inlet H/M/L (dBA) 45 / 40 / 36 45 / 40 / 36
Back air inlet H/M/L (dBA) 33 / 31 / 28 33 / 31 / 28
Sound power level
Under air inlet H/M/L (dBA) 60 / 55 / 51 60 / 55 / 51
Back air inlet H/M/L (dBA) 48 / 46 / 43 48 / 46 / 43
Outdoor unit
Max. total length (m) 70 70
Outer dimension
Min. length (m) 7.5 7.5
Height difference
Outdoor lower (m) 30 30
Outdoor high (m) 30 30
Fan Propeller fan Propeller fan
Fan unit Standard air flow high (m³/min.) 133 133
Motor (W) 100 + 100 100 + 100
Outdoor unit
Gas side (mm) 28.6 28.6
First pipe branch
Liquid side (mm) 12.7 12.7
Connecting pipe
First pipe branch
Gas side (mm) 15.9 15.9
Second pipe branch
Liquid side (mm) 9.5 9.5
Second pipe branch
Gas side (mm) 12.7 12.7
Indoor unit
Liquid side (mm) 6.4 6.4
Sound pressure level Cooling / Heating (dBA) 56 / 57 56 / 57
Sound power level Cooling / Heating (dBA) 72 / 74 72 / 74
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133

Toshiba RAV-SM2244AT7 User manual

Category
Split-system air conditioners
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI