User Manual Refrigeration Regulators
Note: if no key is pressed for at least 40 seconds, the instrument will
exit the parameter modification without memorising the changes made.
During the display and modification of the parameters, the instrument
will go on working with the parameters set previously.
If “password 1” is enabled (access password for the protection of the settings
entered – see system menu), and the “OK” key is pressed from normal status,
the message “- - - ” will appear. To proceed with the setting of the parameters,
enter the password previously set (a numerical value from 0 to 255) with
the “up” ( )keys “down” ( ) and press “OK” to confirm.
If the password has been entered correctly, the label of the first menu will appear.
Otherwise the system will return to normal status.
Advanced programming
2Access is gained to advanced programming from normal status by holding down
the “up” ( )and “down” ( ) keys together for at least 3 seconds.
Note: to restore the default values set in the factory, switch on the
instrument while holding down the “OK” key.
The parameters are grouped into eight menus by type:
1) Regulation (marked [REG]): set point, differential
2) Output (marked [OUT]): output drive times
3) Digital input (marked [ING]): function, delay time
4) Allarme (marked [ALR]): output status in probe alarm, minimum/maximum shift,
differential, delay time, buzzer enable
5) Display (marked [DSP]): set point limits, probe offset, resolution, measurement
unit, measurement filter
6) Sensore (marked [SNS]): sensor type, sensor parameters
7) Sistema (marked [SYS]): password, modification enable, operating mode
8) Refrigrazione (marked [REF]): defrost interval, defrost time, defrost parameters
All the parameters in the eight menus and their values are listed in the section that
follows.
- Use the key “up” ( )to scroll through the eight menus in sequence
- Press “OK” to enter the menu required
- It is possible to scroll through the list of parameters inside each menu
can be modified by pressing the “up” ( ).
To display the parameter value, press “OK” (if “OK” is pressed a second time,
the parameter label is displayed again)
- To change the parameter value, hold down “OK” for at least 3 seconds
- The parameter value will start to flash and it can be increased or decreased by
pressing the “up” ( )and “down” ( ) keys
- Press “OK” to confirm the value set