Siemens SIMATIC NET CP 1243-1 IEC Operating Instructions Manual

Type
Operating Instructions Manual

This manual is also suitable for

CP 1243-1 DNP3, CP 1243-1 IEC
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
SIMATIC NET
S7-1200 - Telecontrol
CP 1243-1 DNP3,
CP 1243-1 IEC
Operating Instructions
02/2014
C79000
-G8976-C312-02
Preface
Application and properties
1
Requirements for use
2
LEDs and connectors
3
Installation, connecting up,
commissioning
4
Configuration and operation
5
Diagnostics and upkeep
6
Technical specifications
7
Approvals
A
Dimension drawings
B
Documentation references
C
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
C79000-G8976-C312-02
02/2014 Technical data subject to change
Copyright © Siemens AG 2013 - 2014.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
CP 1243-1 DNP3, CP 1243-1 IEC
Operating Instructions, 02/2014, C79000-G8976-C312-02
3
Preface
Validity of this manual
This document contains information on the following telecontrol products:
CP 1243-1 DNP3
Article number6GK7 243-1JX30-0XE0
Hardware product version 1
Firmware version V1.1
The CP 1243-1 DNP3 is the communications processor for connecting SIMATIC S7-1200
to control centers using the DNP3 protocol.
CP 1243-1 IEC
Article number6GK7 243-1PX30-0XE0
Hardware product version 1
Firmware version V1.1
The CP 1243-1 IEC is the communications processor for connecting SIMATIC S7-1200 to
control centers using the IEC 60870-5 protocol.
Figure 1 CP 1243-1 DNP3
Preface
CP 1243-1 DNP3, CP 1243-1 IEC
4 Operating Instructions, 02/2014, C79000-G8976-C312-02
The CP 1243-1 IEC has the same outer design as the CP 1243-1 DNP3 apart from the
inscriptions for the product name, article number, firmware version and possibly hardware
product version.
At the top right behind the hinged cover of the module housing, you will see the hardware
product version printed as a placeholder "X" after the article number. If the printed text is, for
example, "X 2 3 4", "X" would be the placeholder for hardware product version 1.
Product names and abbreviations
In this document, you will find the following designations used for the product being
described here:
CP
Simplified naming of the two following products:
CP 1243-1 DNP3
CP 1243-1 IEC
This short form is used in this manual if the property being described in the particular
context applies to both modules.
DNP3-CP
Short form for the CP 1243-1 DNP3 (6GK7 243-1JX30-0XE0)
IEC-CP
Short form for the CP 1243-1 IEC (6GK7 243-1PX30-0XE0)
Purpose of the manual
This manual describes the properties of both these modules and supports you when
installing and commissioning them.
The required configuration steps are described as an overview and there are explanations of
the relationship between firmware functions and configuration.
You will also find information about the diagnostics options of the device.
New in this issue
Inclusion of the CP 1243-1 IEC
New firmware version of the DNP3 CP with bugs fixed
Make sure that the DNP3 CP with firmware version V1.0 or V1.1 is compatible with the
firmware of the CPU, refer to the section Hardware requirements (Page 17).
Editorial revision
As a supplement to the STEP 7 information system, note the information on the functions
and parameters in the section Notes on configuring individual functions (Page 42).
Preface
CP 1243-1 DNP3, CP 1243-1 IEC
Operating Instructions, 02/2014, C79000-G8976-C312-02
5
Replaced documentation
This manual replaces the manual release 07/2013.
Current manual release on the Internet
You will also find the current version of this manual on the Internet pages of Siemens
Industry Online Support in the directory of the relevant CP. This is located below the
directory with the following entry ID:
16514597 (http://support.automation.siemens.com/WW/view/en/16514597)
Required experience
To install, commission and operate the CP, you require experience in the following areas:
Automation engineering
Setting up the SIMATIC S7-1200
SIMATIC STEP 7 Basic / Professional
DNP3 protocol or protocol according to IEC 60870-5
Requirements for use of the module
You will find the requirements for using the module in the section Hardware requirements
(Page 17).
Sources of information and other documentation
You will find an overview of further reading and references in the Appendix of this manual.
SIMATIC NET glossary
Explanations of many of the specialist terms used in this documentation can be found in the
SIMATIC NET glossary.
You will find the SIMATIC NET glossary here:
SIMATIC NET Manual Collection or product DVD
The DVD ships with certain SIMATIC NET products.
On the Internet under the following entry ID:
50305045 (http://support.automation.siemens.com/WW/view/en/50305045)
Preface
CP 1243-1 DNP3, CP 1243-1 IEC
6 Operating Instructions, 02/2014, C79000-G8976-C312-02
License conditions
Note
Open source software
Read the license conditions for open source software carefu
lly before using the product. The
acceptance of the disclaimers of liability and warranty it contains is a clear precondition of
the use of open source software.
You will find license conditions in the following documents on the supplied data medium:
DOC_OSS-S7CMCP_74.pdf
DOC_OSS-CP1243-1DNP3-IEC_76.pdf
Security information
Siemens provides automation and drive products with industrial security functions that
support the secure operation of plants or machines. They are an important component in a
holistic industrial security concept. With this in mind, our products undergo continuous
development. We therefore recommend that you keep yourself informed with respect to our
product updates. Please find further information and newsletters on this subject at:
http://support.automation.siemens.com.
To ensure the secure operation of a plant or machine it is also necessary to take suitable
preventive action (e.g. cell protection concept) and to integrate the automation and drive
components into a state-of-the-art holistic industrial security concept for the entire plant or
machine. Any third-party products that may be in use must also be taken into account.
Please find further information at: http://www.siemens.com/industrialsecurity
Training, Service & Support
You will find information on Training, Service & Support in the multi--language document
"DC_support_99.pdf" on the data medium supplied with the documentation.
CP 1243-1 DNP3, CP 1243-1 IEC
Operating Instructions, 02/2014, C79000-G8976-C312-02
7
Table of contents
Preface ................................................................................................................................................... 3
1 Application and properties ....................................................................................................................... 9
1.1 Communications services .............................................................................................................. 9
1.2 Other services and properties ...................................................................................................... 10
1.3 Configuration limits and performance data .................................................................................. 12
1.4 DNP3 device profile ..................................................................................................................... 13
1.5 Configuration examples ............................................................................................................... 14
1.5.1 Configuration with 1 subnet ......................................................................................................... 14
1.5.2 Configuration with connections over the Internet ......................................................................... 14
1.5.3 Configuration with a redundant control center ............................................................................. 16
2 Requirements for use ............................................................................................................................ 17
2.1 Hardware requirements ............................................................................................................... 17
2.2 Software requirements ................................................................................................................. 18
3 LEDs and connectors ............................................................................................................................ 19
3.1 Opening the covers of the housing .............................................................................................. 19
3.2 LEDs ............................................................................................................................................ 20
3.3 Electrical connections .................................................................................................................. 23
3.3.1 Power supply ................................................................................................................................ 23
3.3.2 Ethernet interface X1P1 ............................................................................................................... 23
4 Installation, connecting up, commissioning ............................................................................................ 25
4.1 Important notes on using the device ............................................................................................ 25
4.1.1 Notices on use in hazardous areas.............................................................................................. 25
4.1.2 Notices regarding use in hazardous areas according to ATEX ................................................... 26
4.1.3 Notices regarding use in hazardous areas according to UL HazLoc ........................................... 27
4.2 Installation .................................................................................................................................... 27
4.3 Installing, connecting up and commissioning .............................................................................. 29
5 Configuration and operation .................................................................................................................. 31
5.1 Note on operation ........................................................................................................................ 31
5.2 Addressing and network configuration ......................................................................................... 31
5.3 Configuration in STEP 7 .............................................................................................................. 32
5.4 Configuring datapoints and messages (e-mails) ......................................................................... 33
5.5 Datapoint types ............................................................................................................................ 35
5.6 CPU scan cycle ............................................................................................................................ 38
5.7 Types of transmission, event classes, triggers ............................................................................ 39
Table of contents
CP 1243-1 DNP3, CP 1243-1 IEC
8 Operating Instructions, 02/2014, C79000-G8976-C312-02
5.8 Notes on configuring individual functions .................................................................................... 42
5.8.1 Communication types and SNMP ............................................................................................... 42
5.8.2 Ethernet interface (X1) > Advanced options ............................................................................... 43
5.8.3 Partner stations ........................................................................................................................... 46
5.8.4 Partner stations > Security options (DNP3) ................................................................................ 48
5.8.5 Communication with the CPU ..................................................................................................... 49
5.8.6 Data point configuration .............................................................................................................. 50
5.8.6.1 "General" parameter group ......................................................................................................... 50
5.8.6.2 Threshold value trigger and Analog value preprocessing ........................................................... 50
5.8.6.3 "Analog value preprocessing" parameter group ......................................................................... 51
5.8.6.4 Analog value preprocessing ........................................................................................................ 51
5.8.6.5 Threshold value trigger ............................................................................................................... 54
5.8.7 Configuring messages ................................................................................................................ 55
6 Diagnostics and upkeep ........................................................................................................................ 59
6.1 Diagnostics options ..................................................................................................................... 59
6.2 Downloading firmware ................................................................................................................. 59
6.3 Module replacement .................................................................................................................... 62
7 Technical specifications ........................................................................................................................ 63
A Approvals ............................................................................................................................................. 65
B Dimension drawings .............................................................................................................................. 69
C Documentation references .................................................................................................................... 71
Index .................................................................................................................................................... 73
CP 1243-1 DNP3, CP 1243-1 IEC
Operating Instructions, 02/2014, C79000-G8976-C312-02
9
Application and properties
1
1.1
Communications services
Communications services
The following communications services are supported:
DNP3-CP
DNP3 protocol
Communication is based on the DNP3 SPECIFICATION Version 2.x (2007/2009).
The CP is a communications processor of the SIMATIC S7-1200 for system connection to
control centers using the DNP3 protocol for telecontrol applications.
An S7-1200 with CP 1243-1 DNP3 operates as a DNP3 station (Outstation).
The CP supports the implementation level 1 - 4 (DNP3 Application Layer protocol Level).
You will find a description of the other functions in the section Partner stations (Page 46).
S7 communication and PG/OP communication with the following functions:
PUT/GET as client and server for data exchange with remote stations (S7-
300/400/1200/1500)
PG functions
Operator control and monitoring functions (HMI)
IEC-CP
Protocol IEC 60870-5
Communication is based on the specification IEC 60870-5 Part 1 - 5 (1990 - 1995) and
part 104 (2000).
The CP is a communications processor of the SIMATIC S7-1200 for system connection to
control centers using the IEC 60870-5 protocol for telecontrol applications.
An S7-1200 with CP 1243-1 IEC operates as a substation (slave).
S7 communication and PG/OP communication with the following functions:
PUT/GET as client and server for data exchange with remote stations (S7-
300/400/1200/1500)
PG functions
Operator control and monitoring functions (HMI)
Status IDs of data points
The status IDs listed in the following tables are transferred for each data point in each frame
in 1 byte.
The meaning relates to the bit status in the last row of each table.
Application and properties
1.2 Other services and properties
CP 1243-1 DNP3, CP 1243-1 IEC
10 Operating Instructions, 02/2014, C79000-G8976-C312-02
Table 1- 1 DNP3: Byte assignment of the status byte for DNP3 data points
Bit
7
6
5
4
3
2
1
0
Flag name
- - - LOCAL_-
FORCED
DISCONTI-
NUITY
OVER_-
RANGE
RESTART ONLINE
Meaning
- - - Local
operator
control
Counted
value
overflow
before
reading the
value
Value
range
exceeded,
analog
value
Value not
updated
after start
Value is
invalid
Bit status
(always 0)
(always 0)
(always 0)
1
1
1
1
1
Table 1- 2 IEC: Byte assignment of the status byte for IEC data points
Bit
7
6
5
4
3
2
1
0
Flag name
- - SB
substituted
- CY
carry
OV
overflow
NT
not topical
IV
invalid
Meaning
- - Substitute
value
- Counted
value
overflow
before
reading the
value
Value
range
exceeded,
analog
value
Value not
updated
Value is
invalid
Bit status
(always 0)
(always 0)
1
(always 0)
1
1
1
0
1.2
Other services and properties
Other services and properties
Data point configuration
Due to the data point configuration in STEP 7, programming program blocks in order to
transfer the process data is unnecessary. The individual data points are processed one-
to-one in the control system.
Security functions (DNP3 only)
The DNP3 CP can use the security functions specified in the DNP3 protocol and
therefore secure communication in the DNP3 network, including the following:
Secure authentication (SA) of the communications partner
The DNP3 CP checks whether the communications partner has the right to access the
DNP3 CP.
Formation of the Message Authentication Code (MAC) using symmetrical (pre-shared
key, PSK) or asymmetrical cryptography (public/private keys)
Use of IPsec for transferring the key
Logging of security events: Successful and failed authentication, key exchange,
statistical counters
You enable the security functions in the STEP 7 configuration with the required options.
Application and properties
1.2 Other services and properties
CP 1243-1 DNP3, CP 1243-1 IEC
Operating Instructions, 02/2014, C79000-G8976-C312-02
11
IP configuration - IPv4 and IPv6
The essential features of IP configuration for the CP:
The CP supports IP addresses according to IPv4 and IPv6.
An IPv6 address can be used in addition to an IPv4 address.
Address assignment:
The IP address, the subnet mask and the address of a gateway can be set manually
in the configuration.
As an alternative, the IP address can be obtained from a DHCP server or by other
means outside the configuration.
Time-of-day synchronization over Industrial Ethernet
The CP can the have its local time of day synchronized by the partner (master) as UTC
time.
The time of day can be read from the CPU. The mechanisms are described in the STEP
7 information system.
For information on the format of the time stamp, refer to the section Datapoint types
(Page 35).
Redundancy
The CP can communicate with a redundant control system (master).
Storage of events
The CP can store events of different classes and transfer them together to the master.
Data transfer is on request or triggered
The sending of data to the master can be triggered in two ways:
At the request of the master
Triggered by various selectable criteria
Messages / e-mail
With configured events in the process image of the CPU, the CP can send messages as
e-mails. The data of the events to be sent by e-mail are configured using PLC tags.
Analog value processing
Analog values can be preprocessed on the CP according to various methods.
Application and properties
1.3 Configuration limits and performance data
CP 1243-1 DNP3, CP 1243-1 IEC
12 Operating Instructions, 02/2014, C79000-G8976-C312-02
Online functions
From an engineering station (ES) on which STEP 7 is installed, you can use the online
functions of STEP 7 via the CP to access the S7-1200 CPU if the station is located in the
same IP subnet. The following online functions are available:
Downloading project or program data from the STEP 7 project to the station
Querying diagnostics data on the station
Downloading firmware files to the CP
For a remote station located in a different IP subnet or that can be reached via the
Internet, these functions can only be used if the ES is connected to the station via a VPN
tunnel (for example via a SCALANCE S).
SNMP
As an SNMP agent, the CP supports data queries using SNMP (Simple Network
Management Protocol) in version V1.
For more detailed information, refer to section Communication types and SNMP
(Page 42).
1.3
Configuration limits and performance data
Number of CMs/CPs per station
In each S7-1200 station, up to three CMs/CPs can be plugged in and configured; this means
a maximum of three identical CP 1243-1 DNP3 or three identical CP 1243-1 IEC modules.
Connection resources
TCP connections to masters (DNP3 or IEC)
The CP can establish connections to up to 4 masters. These can be single or redundant
masters.
In the case of 4 redundant masters, this would be 8 physical devices addressed using
different IP addresses.
Online functions / TeleService
1 connection resource is reserved for online functions / TeleService.
S7 connections
8 connection resources for S7 connections (PUT/GET)
PG/OP connections
1 connection resource for PG connections
3 connection resources for OP connections
Application and properties
1.4 DNP3 device profile
CP 1243-1 DNP3, CP 1243-1 IEC
Operating Instructions, 02/2014, C79000-G8976-C312-02
13
Number of data points for the data point configuration
The maximum number of configurable data points is 200.
User data
The data to be transferred by the CP is assigned to various data points in the STEP 7
configuration. The size of the user data per data point depends on the data type of the
relevant data point.
With the DNP3 CP, contiguous memory areas can be transferred up to a size of 64 bytes
using data point types of the object groups 110 (Octet String) and 111 (Octet String Event).
You will find details in the information system of STEP 7 and in the section Datapoint types
(Page 35).
Frame memory (send buffer)
The CP has a frame memory (send buffer) for data points configured as an event.
The send buffer has a maximum size of 64000 events divided into equal parts for all
configured communications partners. The size of the frame memory can be set in STEP 7,
refer to the section Communication with the CPU (Page 49).
You will find details of how the send buffer works (storing and sending events) as well as the
options for transferring data in the section Types of transmission, event classes, triggers
(Page 39).
Messages / e-mail
Up to 10 messages can be configured in STEP 7 and sent as e-mails.
1.4
DNP3 device profile
Detailed information on DNP3 attributes in the DNP3 device profile
You will find a detailed overview of the attributes and properties specified in the DNP3
protocol and supported by the CP in the DNP3 device profile.
You will find the DNP3 device profile of the CP 1243-1 DNP3 on the Internet pages of
Siemens Industry Online Support under the following entry ID:
82856876 (http://support.automation.siemens.com/WW/view/en/82856876)
Application and properties
1.5 Configuration examples
CP 1243-1 DNP3, CP 1243-1 IEC
14 Operating Instructions, 02/2014, C79000-G8976-C312-02
1.5
Configuration examples
1.5.1
Configuration with 1 subnet
Configuration example with a non-redundant control center
The following example describes a configuration with a non-redundant control center in
which all nodes are located in 1 IP subnet.
In this example, the DNP3 protocol is used; in other words, the stations are equipped with a
CP 1243-1 DNP3.
A configuration in which the IEC protocol is used would have the same setup apart from the
CP type (here CP 1243-1 IEC).
Figure 1-1 Configuration example with a non-redundant control center and stations in one IP subnet
The S7-1200 stations are connected to the Internet via the CP and connected to the control
center.
When using the DNP3 protocol, for example, SIMATIC PCS 7 TeleControl or the system of a
third-party provider can be used as the control center. If you use SIMATIC PCS 7
TeleControl as the DPN3 master in the control center, you require the necessary DPN3
driver.
1.5.2
Configuration with connections over the Internet
Configuration example with connections over the Internet
The following example contains a configuration with a non-redundant control center.
In this example, the DNP3 protocol is used; in other words, the stations are equipped with a
CP 1243-1 DNP3.
Application and properties
1.5 Configuration examples
CP 1243-1 DNP3, CP 1243-1 IEC
Operating Instructions, 02/2014, C79000-G8976-C312-02
15
A configuration in which the IEC protocol is used would have the same setup apart from the
CP type (here CP 1243-1 IEC).
The S7-1200 stations are connected to the Internet via the CP and connected to the control
center.
When using the DNP3 protocol, for example, SIMATIC PCS 7 TeleControl or the system of a
third-party provider can be used as the control center. If you use SIMATIC PCS 7
TeleControl as the DPN3 master in the control center, you require the necessary DPN3
driver.
Figure 1-2 Configuration example with connections over the Internet
Options of the Internet connection
There are various ways of configuring the Internet connection:
DSL modem + SCALANCE S
This is the configuration of the example shown in the figure.
In this case, use a standard DSL modem. With the security module SCALANCE S, you
establish the VPN connection.
DSL router with VPN capability
In such a configuration, use a DSL router with VPN capability.
Mobile wireless router
If the station needs to be connected to the Internet using mobile wireless (GSM network /
GPRS), the SIMATIC NET router SCALANCE M87x is used.
Application and properties
1.5 Configuration examples
CP 1243-1 DNP3, CP 1243-1 IEC
16 Operating Instructions, 02/2014, C79000-G8976-C312-02
Addressing
Refer to the information in the section Addressing and network configuration (Page 31).
1.5.3
Configuration with a redundant control center
Configuration example with a redundant control center
The following example contains a configuration with a redundant control center and
connections via the Internet.
In this example, the DNP3 protocol is used; in other words, the stations are equipped with a
CP 1243-1 DNP3.
A configuration in which the IEC protocol is used would have the same setup apart from the
CP type (here CP 1243-1 IEC).
Figure 1-3 Configuration example with a redundant DNP3 master station
Addressing of the redundant DNP3 master
The two devices of the redundant DNP3 master in the control center are addressed by the
DNP3 CP using one DNP3 address but two different IP addresses.
CP 1243-1 DNP3, CP 1243-1 IEC
Operating Instructions, 02/2014, C79000-G8976-C312-02
17
Requirements for use
2
2.1
Hardware requirements
The following setups do not take into account rails, housing, cabling and other accessories.
Depending on the configuration of your plant, you require the following devices and firmware
versions.
Application example: Project with 1 subnet
The following setup assumes that the master and stations are located in 1 IP subnet, see
also the section Configuration with 1 subnet (Page 14).
In the S7-1200 station:
DNP3
When using a DNP3 CP with firmware version V1.0: A CPU with firmware version
V3.0.
When using a DNP3 CP with firmware version V1.1: A CPU with firmware version
V3.0 or V4.0.
IEC
IEC CP
CPU with firmware version V3.0 or V4.0
In the master station:
PC for compatible DNP3 or IEC master
With redundantly designed master stations, the hardware needs to be doubled.
When using online functions: Engineering station with STEP 7 (see following section)
Application example: Distributed project connections over the Internet
In the remote S7-1200 station:
The following set up assumes that the master and stations communicate via the Internet, see
also the section Configuration with connections over the Internet (Page 14).
DNP3
When using a DNP3 CP with firmware version V1.0: A CPU with firmware version
V3.0.
When using a DNP3 CP with firmware version V1.1: A CPU with firmware version
V3.0 or V4.0.
DSL router + SCALANCE S
See also the reference in the section "Notes on the DSL router" below.
Requirements for use
2.2 Software requirements
CP 1243-1 DNP3, CP 1243-1 IEC
18 Operating Instructions, 02/2014, C79000-G8976-C312-02
IEC
IEC CP
CPU with firmware version V3.0 or V4.0
DSL router + SCALANCE S
See also the reference in the section "Notes on the DSL router" below.
In the master station:
Compatible DNP3 or IEC master
DSL router + SCALANCE S
See also the reference in the section "Notes on the DSL router" below.
When using online functions: Engineering station with STEP 7 (see following section)
Notes on the DSL router
You will find the requirements for communication and the configuration options in the section
Configuration with connections over the Internet (Page 14).
2.2
Software requirements
Configuration software
To configure the modules, the following configuration tool is required:
DNP3 CP with firmware version V1.0:
STEP 7 Basic ab V12.0 SP1
DNP3 CP with firmware version V1.1:
STEP 7 Basic V13.0
IEC CP with firmware version V1.1:
STEP 7 Basic V13.0
Software for online functions
STEP 7 in the version specified above
CP 1243-1 DNP3, CP 1243-1 IEC
Operating Instructions, 02/2014, C79000-G8976-C312-02
19
LEDs and connectors
3
3.1
Opening the covers of the housing
Location of the display elements and the electrical connectors
The LEDs for the detailed display of the module statuses are located behind the upper cover
of the module housing.
The Ethernet connector is located behind the lower hinged cover of the module.
Opening the covers of the housing
Open the upper or lower cover of the housing by pulling it down or up as shown by the
arrows in the illustration. The covers extend beyond the housing to give you a grip.
Figure 3-1 Opening the covers of the housing
LEDs and connectors
3.2 LEDs
CP 1243-1 DNP3, CP 1243-1 IEC
20 Operating Instructions, 02/2014, C79000-G8976-C312-02
3.2
LEDs
LEDs of the module
The module has various LEDs for displaying the status:
LED on the front panel
The "DIAG" LED that is always visible shows the basic statuses of the module.
LEDs below the upper cover of the housing
The LEDs below the upper cover provide more detailed information on the module status.
Table 3- 1
LED on the front panel
LED / colors
Name
Meaning
(red / green)
DIAG
Basic status of the module
Table 3- 2
LEDs below the upper cover of the housing
LED (color)
Name
Meaning
(green)
LINK
Status of the connection to Industrial Ethernet
(green)
CONNECT
Status of the connections to masters
(green)
VPN
- inactive -
(green)
SERVICE
Status of a connection for online functions
LED colors and illustration of the LED statuses
The LED symbols in the following tables have the following significance:
Table 3- 3
Meaning of the LED symbols
Symbol
-
LED status
OFF
ON (steady light)
Flashing
Not relevant
Note
LED colors when the module starts up
When
the module starts up, all its LEDs are lit for a short time. Multicolored LEDs display a
color mixture. At this point in time, the color of the LEDs is not clear.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74

Siemens SIMATIC NET CP 1243-1 IEC Operating Instructions Manual

Type
Operating Instructions Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI