FORM 145.18-EG2 (317)
18
JOHNSON CONTROLS
TABLE 10 - VPCS36 - EC MOTOR (ECM) - COOLING AIRFLOW: 1100 CFM AND HEATING AIRFLOW: 1250 CFM
EWT GPM
WPD COOLING HEATING
PSI FT TC SC SHR KW HR EER HTG KW HE LAT COP
20 9.0 11.7 27.1 22.3 2.18 15.8 84.5 3.0
30
4.5 3.1 7.2 43.9 29.9 0.68 1.27 47.3 34.7 25.8 2.21 19.3 87.1 3.4
6.8 7.1 16.4 44.3 30.1 0.68 1.19 47.5 37.1 26.4 2.22 19.8 87.5 3.5
9.0 10.9 25.2 44.6 30.3 0.68 1.15 47.6 38.9 26.8 2.22 20.2 87.8 3.5
40
4.5 2.9 6.8 42.7 29.5 0.69 1.47 46.8 29.1 29.0 2.25 22.3 89.5 3.8
6.8 6.6 15.3 43.1 29.8 0.69 1.40 47.0 30.8 29.9 2.26 23.2 90.1 3.9
9.0 10.2 23.6 43.4 29.9 0.69 1.36 47.1 31.9 30.5 2.26 23.8 90.6 3.9
50
4.5 2.7 6.3 41.5 29.0 0.70 1.66 46.2 25.0 32.7 2.29 25.8 92.2 4.2
6.8 6.2 14.3 41.9 28.9 0.69 1.60 46.4 26.2 33.8 2.30 27.0 93.1 4.3
9.0 9.5 21.9 42.1 29.1 0.69 1.56 46.6 27.1 34.7 2.31 27.8 93.7 4.4
60
4.5 2.5 5.8 40.2 28.5 0.71 1.86 45.6 21.6 36.7 2.33 29.7 95.1 4.6
6.8 5.7 13.2 40.6 28.4 0.70 1.79 45.8 22.6 38.2 2.35 31.2 96.3 4.8
9.0 8.8 20.3 40.9 28.6 0.70 1.75 45.9 23.3 39.3 2.36 32.2 97.1 4.9
70
4.5 2.3 5.4 38.8 27.6 0.71 2.07 45.0 18.8 40.9 2.38 33.8 98.3 5.0
6.8 5.3 12.1 39.3 27.9 0.71 2.00 45.2 19.6 42.8 2.40 35.6 99.7 5.2
9.0 8.1 18.7 39.5 28.1 0.71 1.96 45.3 20.2 44.2 2.42 37.0 100.8 5.4
80
4.5 2.1 4.9 37.4 27.3 0.73 2.30 44.3 16.3 45.5 2.43 38.1 101.7 5.5
6.8 4.8 11.1 37.8 27.2 0.72 2.22 44.5 17.0 47.7 2.46 40.3 103.4 5.7
9.0 7.4 17.0 38.1 27.4 0.72 2.18 44.6 17.5 49.4 2.48 41.9 104.6 5.8
90
4.5 1.9 4.4 35.8 26.5 0.74 2.57 43.6 14.0 50.2 2.49 42.7 105.2 5.9
6.8 4.4 10.0 36.3 26.5 0.73 2.48 43.8 14.6 52.8 2.52 45.2 107.1 6.1
9.0 6.7 15.4 36.6 26.7 0.73 2.43 44.0 15.1 54.8 2.55 47.1 108.6 6.3
100
4.5 1.7 3.9 34.1 25.9 0.76 2.88 43.0 11.9
6.8 3.9 9.0 34.6 26.0 0.75 2.78 43.2 12.5
9.0 6.0 13.8 34.9 26.2 0.75 2.72 43.3 12.8
110
4.5 1.5 3.5 32.3 25.2 0.78 3.24 42.4 10.0
6.8 3.4 7.9 32.8 25.3 0.77 3.13 42.6 10.5
9.0 5.3 12.2 33.2 25.5 0.77 3.06 42.7 10.8
• Cooling Performance is tabulated at 80.6 °F DB and 66.2 °F WB entering air. Heating performance tabulated at 68 F EAT
• Tabulated data does not include AHRI/ISO corrections for fan and pump power.°
• All capacities are expressed in MBH.
• Insulated water circuit is recommended for operation below 60 °F EWT.
• Operation below 60 °F EWT is based on 15% methanol.
• See performance correction tables for conditions beyond what is listed.
• Extrapolation is not permissible.
• Shaded areas indicate conditions where operation is not recommended.
• All performance is based on 208V on 208-230V units.
Performance Data - EC Motor (Cont'd)