Samsung MIM-B12 Installation guide

Type
Installation guide
SIM_MIM-B12_EN_IM_26745A-04.indd 10 2014-05-09 오후 5:31:43
SIM (Serial Input Module)
MIM-B12
Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung product.
This manual is made with 100% recycled paper.
KO EN ZH
DB98-26745A-04
SIM_MIM-B12_EN_IM_26745A-04.indd 11 2014-05-09 오후 5:31:43
E-2
Safety Precautions
Make sure to read the following safety precautions carefully before installation.
(Refer to the optional installation of the installation manual.)
The installation must be carried out by
a licensed installer or contact the service
center.
It could cause malfunction, water
leakage, electric shock or fire.
Install the unit in a place where it is
strong enough to hold the unit weight.
When installed in a place where it is
not strong enough to withhold the
product weight, the unit could fall
and damaged.
Do not attempt to repair or disassemble
the unit on your own.
Consult the qualified personnel or
service center when the unit is
needed to repair to avoid
malfunction, electric shock or fire.
Make sure to install the unit correctly in
accordance with the installation manual.
Incorrect installation of the unit
could cause electric shock or fire.
Make sure to use the power source with
separate wiring for installation.
It could cause fire or damaged.
Do not attempt to move the unit or
reinstall it on your own.
It could cause electric shock or fire.
Ensure that all electric works should be
done by an authorized installer and in
accordance with the local requirements
and the installation manual.
Incorrect installation of the unit could
cause malfunction, electric shock and
fire if unauthorized personnel install
the unit.
Consult the service center when
you need to dispose of the unit.
This indicates the possibility of serious injury or death.
WARNING
WARNING
This indicates the possibility of serious injury or damage to
environments when operated incorrectly.
CAUTION
SIM_MIM-B12_EN_IM_26745A-04.indd 2 2014-05-09 오후 5:31:41
E-3
ENGLISH
Do not install the unit in a place where it
is exposed to inflammable gas leakage.
It could cause fire or explosion.
Do not install the unit near dangerous
places where it is exposed to machine
oil or steam.
It could cause the part damaged or
malfunction if you use the unit in a
place exposed to machine oil, steam
and sulfide gas.
Never spill any kind of liquid into the
unit.
It could cause electric shock or fire.
Make sure to avoid tension when
connecting the wires to the unit.
It could cause fire by disconnecting
the wires.
Install the unit in a place where the
temperature is between 0°C and 39°C
and not exposed to direct sunlight.
It could get electric shock or
malfunction of the unit.
Avoid installing the unit in a place
where acidity or alkali liquid or
distinctive spray is used.
It could cause electric shock or
malfunction of the unit.
Avoid putting the button of the unit in
contact with sharp-edged items.
It could cause electric shock or
accessories damaged.
Do not connect the wires to the terminal.
It could cause fire.
Make sure not to give shock other products when installing the unit in a place
such as hospital.
It could cause malfunction of the unit.
Safety Precautions
CAUTION
SIM_MIM-B12_EN_IM_26745A-04.indd 3 2014-05-09 오후 5:31:41
E-4
Installing the SIM (Serial Input Module)
SIM (Serial Input Module)
Accessories
Installation
Manual
1
The SIM must be installed by a qualified installer.
Make sure the main power is turned off before
installing the SIM.
The wires must be installed according to the national
electrical wiring regulations.
Caution
SIM_MIM-B12_EN_IM_26745A-04.indd 4 2014-05-09 오후 5:31:41
E-5
ENGLISH
Installing the SIM (Serial Input Module)
SIM (Serial Input Module) Structure
Comm. (RS-485 power meter)
Power
Power
Meter
Power
ELB
or
NFB
System A/C
Outdoor unit
1 Way
Cassette type
Duct type
4 Way
Cassette type
Split type
SIM
(Power meter I/M)
DMS S-NET 3
Install indoors and inside of the distribution kit
Power meter, SIM(Power meter I/M), ELB or NFB should be
installed indoors and inside the distribution kit which is
proper to the electric equipment standard.
Caution
SIM_MIM-B12_EN_IM_26745A-04.indd 5 2014-05-09 오후 5:31:41
E-6
Installing the SIM (Serial Input Module)(Continued)
SIM (Serial Input Module) Structure
1
Unscrew the 4 screws on the SIM (Serial Input Module) to
open the cover.
2
Connect a DC 12V adaptor to the power terminal on the
SIM. The following adaptor should be used.
The following adaptor should be purchased separately.
3
Connect the power meter communication cables to the
terminals labeled CH1 to Ch8
on SIM.
At most 8 power meters
can be connected to one SIM.
Only selected RS-485 type
power meters from
the following suppliers can be used with SIM.
(Omni System, Korea Micronics, LS Industrial,
Hansuk Tech)
4
Connect the C1, C2 communication cable from SIM to
the C1, C2 terminal on DMS.
5
Reassemble the SIM.
Note At most 8 power meters of SIM can be connected to
one DMS.
Input Power
110V/220V
Input Frequency
50/60H
z
Rated Output
DC 12V±5% 1A
Connector Internal Diameter
1.1
mm
±0.1
Connector External Diameter
3.5
mm
±0.1
Power
cable
(DC 12V)
SIM I/M
communication
cable
Connect
to DMS
SIM_MIM-B12_EN_IM_26745A-04.indd 6 2014-05-09 오후 5:31:42
E-7
ENGLISH
Installing the SIM (Serial Input Module)(Continued)
Setting the SIM (Serial Input Module) address
1
Unscrew the 4 screws on the SIM (Serial Input Module) to
open the cover.
2
Use the rotary switch (DS01) on SIM to set the
communication address.
The address of SIM can be set from 0 to 7.
The default switch is set as '0'.
The address of SIM is set according to the switch setting
when powered on. If the rotary switch is adjusted after the
power is supplied, the adjusted address is not reflected.
To set the adjusted address for rotary switch, unplug the
power cable and plug it again.
Caution
Power
cable
(DC 12V)
SIM I/M
communication
cable
Connect
to DMS
SIM_MIM-B12_EN_IM_26745A-04.indd 7 2014-05-09 오후 5:31:42
E-8
Once tracking is completed, you can check the
information of the power meter value connected
to the channels using the K1 and K2 buttons.
Display Window
Installing the SIM (Serial Input Module)(Continued)
SIM (Serial Input Module) Startup Order
7-Segment LED display
All on
SIM (Serial Input Module) address
ex) 00
SIM (Serial Input Module) program version
ex) version 12.3
The channel which is tracking is displayed.
Displayed until tracking is complete
The power consumed by each channel is displayed
ex) 456.7kW
The following order is displayed when SIM is powered on.
SIM_MIM-B12_EN_IM_26745A-04.indd 8 2014-05-09 오후 5:31:42
E-9
ENGLISH
Installing the SIM (Serial Input Module)(Continued)
Reference
Reference Color Status
LED01 Red
Turns on when power is on
LED02 Yellow
Turns on when communicating with DMS
LED03 Green
Flickers when communicating with the power meter on CH1
LED04 Green
Flickers when communicating with the power meter on CH2
LED05 Green
Flickers when communicating with the power meter on CH3
LED06 Green
Flickers when communicating with the power meter on CH4
LED07 Green
Flickers when communicating with the power meter on CH5
LED08 Green
Flickers when communicating with the power meter on CH6
LED09 Green
Flickers when communicating with the power meter on CH7
LED10 Green
Flickers when communicating with the power meter on CH8
Buttons
Reference Status
K1
Next channel (only connected channels are shown)
K2
Previous channel (only connected channels are shown)
K3
Reset
K4
Not used
K5
Not used
K6
Not used
K1K3K5
LED01 LED02 LED03 LED04 LED05 LED06 LED07 LED08 LED09 LED10
K2K4K6
DIS2 DIS3 DIS4
Power Cable
(DC12V)
SIM I/M
communication
cable
Connect to
DMS
Buttons
LED display
SIM (Serial Input Module) LED display and buttons
SIM_MIM-B12_EN_IM_26745A-04.indd 9 2014-05-09 오후 5:31:42