If the unit has some problems and does not work normally, error code is shown on the OUTDOOR UNIT
MAIN PCB.
Display Explanation Error Source
E101
Communication error between the indoor and outdoor units
(when indoor unit cannot receive signals)
COMM KIT
OUTDOOR UNIT
E108
Duplicate channel addresses - overlapping of unit channel
addresses on a system.
OUTDOOR UNIT
E109 Communication error due to indoor unit address incomplete.
COMM KIT
OUTDOOR UNIT
E111
Modbus communication error
(when COMM KIT cannot receive signals)
COMM KIT
OUTDOOR UNIT
E162 EEPROM H/W ERROR COMM KIT
E177 Emergency Error
COMM KIT
OUTDOOR UNIT
E201
COMM KIT/OUTDOOR UNIT communication error
(Matching error)
OUTDOOR UNIT
E202 COMM KIT/OUTDOOR UNIT communication error (3 min) OUTDOOR UNIT
E203 Communication error between INVERTER and MAIN MICOM (6 min) OUTDOOR UNIT
E221 OUTDOOR UNIT temperature sensor error OUTDOOR UNIT
E231 Condenser temperature sensor error OUTDOOR UNIT
E251 Discharge temperature sensor error OUTDOOR UNIT
E320 OLP sensor error OUTDOOR UNIT
E403
Detection of OUTDOOR UNIT compressor freezing
(During cooling operation)
OUTDOOR UNIT
E404
Protection of OUTDOOR UNIT when it is overload
(during Safety Start, Normal operation state)
OUTDOOR UNIT
E407 Comp down due to high pressure OUTDOOR UNIT
E416 Discharge of a compressor is overheated OUTDOOR UNIT
E425 Power source line missing error (only for 3-phase model) OUTDOOR UNIT
E440 Heating operation blocked (outdoor temperature over 35°C) OUTDOOR UNIT
E441 Cooling operation blocked (outdoor temperature under 9°C) OUTDOOR UNIT
E458 OUTDOOR UNIT fan1 error OUTDOOR UNIT
E461 [Inverter] Compressor startup error OUTDOOR UNIT
EHS004-00_IM_MONO COMM KIT OEM_EU_EN_.indd 12 2020-01-15 오후 4:06:41