COMFORT-AIRE HRC09A1CAMSCFL User guide

Category
Heat pumps
Type
User guide
Heat Controller • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
ENGINEERING
DESIGN GUIDE
HRC Series
Commercial Console
Water-Source Heat Pumps
60Hz
Design Guide HRC SERIES Heat Controller
2
Heat Controller HRC SERIES Design Guide
Table of Contents
*Page Number
Unit Features ..................................................................................4
Selection Procedure ............................................................................5
HRC Series Nomenclature .......................................................................7
Performance Data – AHRI/ASHRAE/ISO 13256-1 .....................................................8
Performance Data – Selection Notes ...............................................................9
Performance Data – HRC09 .....................................................................10
Performance Data – HRC12 .....................................................................11
Performance Data – HRC15 .....................................................................12
Performance Data – HRC18 .....................................................................13
Performance Data Correction Tables ..............................................................14
Blower Performance & Electrical Data .............................................................15
Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Console Cabinet Dimensions Size 09 -15 - Bottom Return - Left Hand Piping ...............................17
Console Cabinet Dimensions Size 09 - 15 - Front Return - Left Hand Piping ................................18
Console Cabinet Dimensions Size 09 - 15 - Bottom Return - Right Hand Piping .............................19
Console Cabinet Dimensions Size 09 - 15 - Front Return - Right Hand Piping ..............................20
Console Bottom Return Chassis Dimensions Size 09 - 15 ..............................................21
Console Front Return Chassis Dimensions Size 09 - 15 ...............................................22
Piping Detail Size 09-15 ........................................................................23
Console Cabinet Dimensions Size 18 - Bottom Return - Left Hand Piping ..................................24
Console Cabinet Dimensions Size 18 - Front Return - Left Hand Piping ...................................25
Console Cabinet Dimensions Size 18 - Bottom Return - Right Hand Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Console Chassis Dimensions Size 18 - Front Return - Right Hand Piping ..................................27
Console Bottom Return Chassis Dimensions Size 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Console Chassis Dimensions Size 18 ..............................................................29
Piping Detail Size 18 ...........................................................................30
HRC Series Wiring Diagram Matrix ...............................................................31
Typical Wiring Diagram – Manual & Auto Change Over HRC Units with CXM Controller .......................32
Typical Wiring Diagram – Remote Mounted Thermostat HRC Units with CXM Controller ......................33
Typical Wiring Diagram – HRC Units with CXM & LON Controller ........................................34
Typical Wiring Diagram – HRC Units with CXM & MPC Controller ........................................35
Typical Wiring Diagram – Manual & Auto Change Over HRC Units with DXM Controller .......................36
Typical Wiring Diagram – Remote Mounted Thermostat HRC Units with DXM Controller ......................37
Typical Wiring Diagram – HRC Units with DXM & LON Controller ........................................38
Typical Wiring Diagram – HRC Units with DXM & MPC Controller ........................................39
Engineering Specications ......................................................................40
Revision History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
3
Design Guide HRC SERIES Heat Controller
CONSOLE (HRC) SERIES
WITH HFC-410A REFRIGERANT
The Series (HRC) console unit provides a high efciency
WSHP “ductless” solution for spaces where individual,
quiet control of the heating and cooling system is
important. HRC units are especially ideal where ceiling
height and space are limited, or when preserving the
integrity of an existing structure. The HRC Series
exceeds ASHRAE 90.1 efciencies, yet maintains small
cabinet dimensions. Using
HFC-410A
refrigerant, the
console not only protects the environment, it does so
while delivering unprecedented comfort, efciency, and
reliability.
Available in sizes 3/4 ton (2.64 kW) through 1-1/2 tons
(5.3 kW) with numerous cabinet, water piping and control
choices, the HRC Series offers a wide range of units for
most any installation. The HRC has an extended range
refrigerant circuit, capable of ground loop (geothermal)
applications as well as water loop (boiler-tower) appli-
cations. Standard features are many. Microprocessor
controls, galvanized steel cabinet, polyester powder coat
paint and TXV refrigerant metering device are just some
of the features of the exible HRC series.
Compressors are mounted on specially engineered
sound-tested EPDM grommets for quiet operation.
Options such as coated air coil, DDC controls, internal
pump and factory-installed water solenoid valves allow
customized design solutions.
The HRC Series console water-source heat pumps
are designed to meet the challenges of today’s HVAC
demands with a low cost/high value “ductless” solution.
UNIT FEATURES
Sizes 09 (3/4 ton, 2.64 kW) through 18 (1-1/2 ton, 5.3 kW
Environmentally-friendly (HFC-410A) zero ozone
depletion refrigerant
High Efficiency Rotary compressors
Exceeds ASHRAE 90.1 efficiencies
Two-piece chassis/cabinet design
Galvanized steel cabinet with durable Polar Ice powder
coat finish and black “matte” finish on subbase
Slope top/aluminum rigid bar supply air grille
UltraQuiet Option
TXV metering device
Extended range (20 to 120°F, -6.7 to 48.9°C) operation
Advanced digital auto change-over unit mounted controls
with temperature display and high/low fan speed
selection
Remote-mounted controls available
Microprocessor controls standard (optional DXM and/or
DDC controls)
LonWorks, BACnet, Modbus and Johnson N2
compatibility options for DDC controls
Right or left-hand piping arrangement
Front or bottom return air configuration
Unit Performance Sentinel
performance
monitoring system
Eight Safeties Standard
Wide variety of options including coated air coil, flow
regulator, motorized water valve, stainless steel
drain pan, locking control door, disconnect switch,
and internal pump. (Pump option requires extended
cabinet).
Accessory
Louvered, painted black “matte” finish subbase
decorative grille for field-installation.
Unit Features
4
Heat Controller HRC SERIES Design Guide
To convert Inch-Pound (English) to SI (Metric)
Air Flow Correction Table
400 CFM per ton of cooling capacity is nominal rated airflow for all models (bold print)
Use multipliers directly with unit data for correcting unit performance at other airflows than nominal
Entering Air Correction Tables
Entering air corrections should be multiplied directly to unit performance data to derive performance at entering air condition other
than ARI/ISO/ASHRAE 13256-1
ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Clg- 80.6ϒF DB/66.2ϒF WB and Htg- 68ϒF DB/59ϒF WB shown in bold
Discontinued Standards ARI 320, 325, and 330 used entering air conditions of Clg- 80ϒF DB/67ϒF WB and Htg- 70ϒF DB
Cooling Corrections
Sens Clg Cap Multiplier - Entering DB ϒF
Ent Air
WB ϒF
Total Clg
Cap
70 75 80 80.6 85 90 95
Power Heat of
Rej
60 0.852 0.828 0.980 1.097 1.129 ***0.996 0.878
65 0.974 0.595 0.808 1.004 1.017 1.194 **0.998 0.979
66.2 1.000 0.539 0.767 0.967 1.000 1.152 **1.000 1.000
67 1.004 0.501 0.740 0.939 0.955 1.124 1.233 1.276 1.002 1.010
70 1.034 0.636 0.810 0.844 1.016 1.136 1.220 1.005 1.029
75 1.069 0.514 0.612 0.826 0.973 1.127 1.010 1.058
Heating Corrections
Ent Air
DB ϒF
Htg Cap Power
Heat of
Ext
60 1.059 0.947 1.100
65 1.019 0.981 1.032
68 1.000 1.000 1.000
70 0.995 1.010 0.989
75 0.980 1.037 0.960
80 0.967 1.063 0.934
Total Cap Sens Cap Power Heat of Rej
1.019 0.902 0.964 1.007
1.013 0.928 0.976 1.003
1.007 0.953 0.988 1.000
1.004 0.977 0.994 1.000
1.000 1.000 1.000 1.000
0.998 1.023 1.006 1.000
0.997 1.047 1.012 1.000
Cooling
CFM Per Ton
of Clg
% of
Nominal
300 75%
325 81%
350 88%
375 94%
400 100%
425 106%
450 113%
Airflow
Htg Cap Heat of ExtPower
0.957 1.061 0.922
0.968 1.040 0.946
0.979 1.020 0.970
0.989 1.010 0.985
1.000 1.000 1.000
1.0110.997 1.015
1.021 0.994 1.030
Heating
Air Flow Water Flow Ext Static Pressure Water Pressure Drop
Airflow (L/s) = CFM x 0.472 Water Flow (L/s) = gpm x 0.0631 ESP (Pa) = ESP (in of wg) x 249 PD (kPa) = PD (ft of hd) x 2.99
Reference Calculations
BTUH = BTU( British Thermal Unit) per hour
CFM = airow, cubic feet/minute
COP = coefcient of performance = BTUH output/BTUH input
DB = dry bulb temperature (°F)
EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)
EER = energy efciency ratio = BTUH output/Watt input
MPT = male pipe thread
ESP = external static pressure (inches w.g.)
EWT = entering water temperature
GPM = water ow in U.S. gallons/minute
HE = total heat of extraction, BTUH
HC = air heating capacity, BTUH
HR = total heat of rejection, BTUH
HWC = hot water generator (desuperheater) capacity, Mbtuh
FPT = female pipe thread
KW = total power unit input, kilowatts
LAT = leaving air temperature, °F
LC = latent cooling capacity, BTUH
LWT = leaving water temperature, °F
MBTUH = 1000 BTU per hour
S/T = sensible to total cooling ratio
SC = sensible cooling capacity, BTUH
TC = total cooling capacity, BTUH
WB = wet bulb temperature (°F)
WPD = waterside pressure drop (psi & ft. of hd.)
Conversion Table - to convert inch-pound (English) to S-I (Metric)
Legend and Glossary of Abbreviations
LWT = EWT -
HE
GPM x 500
LAT = EAT +
HC
CFM x1.08
LWT = EWT +
HR
GPM x 500
LAT (DB) = EAT (DB) -
SC
CFM x1.08
LC = TC - SC
S/T =
SC
TC
Heating
Cooling
Selection Procedure
5
Design Guide HRC SERIES Heat Controller
Selection Procedure
Step 1 Determine the actual heating and cooling loads at the
desired dry bulb and wet bulb conditions.
Step 2 Obtain the following design parameters: Entering water
temperature, water ow rate in GPM, air ow in CFM,
water ow pressure drop and design wet and dry bulb
temperatures. Air ow CFM should be between 300 and
450 CFM per ton. Unit water pressure drop should be
kept as close as possible to each other to make water
balancing easier. Go to the appropriate tables and nd
the proper indicated water ow and water temperature.
Step 3 Select a unit based on total and sensible cooling
conditions. Select a unit which is closest to, but no
larger than, the actual cooling load.
Step 4 Enter tables at the design water ow and water
temperature. Read the total and sensible cooling
capacities (Note: interpolation is permissible,
extrapolation is not).
Step 5 Read the heating capacity. If it exceeds the design
criteria it is acceptable. It is quite normal for Water-
Source Heat Pumps to be selected on cooling capacity
only since the heating output is usually greater than the
cooling capacity.
Step 6 Determine the correction factors associated with the
variable factors of dry bulb and wet bulb.
Corrected Total Cooling = tabulated total cooling
x wet bulb correction.
Corrected Sensible Cooling = tabulated sensible cooling
x wet/dry bulb correction.
Step 7 Compare the corrected capacities to the load
requirements. Normally if the capacities are within 10%
of the loads, the equipment is acceptable. It is better
to undersize than oversize, as undersizing improves
humidity control, reduces sound levels and extends the
life of the equipment.
Step 8 When completed, calculate water temperature rise
and assess the selection. If the units selected are not
within 10% of the load calculations, then review what
effect changing the GPM, water temperature and/or air
ow and air temperature would have on the corrected
capacities. If the desired capacity cannot be achieved,
select the next larger or smaller unit and repeat the
procedure. Remember, when in doubt, undersize
slightly for best performance.
Example Equipment Selection For Cooling
Step 1 Load Determination:
Assume we have determined that the appropriate cooling load
at the desired dry bulb 80°F and wet bulb 65°F conditions is as
follows:
Total Cooling.........................................................10,200 BTUH
Sensible Cooling.....................................................8,350 BTUH
Entering Air Temp.........................80°F Dry Bulb/65°F Wet Bulb
Step 2 Design Conditions:
Similarly, we have also obtained the following design
parameters:
Entering Water Temp..........................................................90°F
Water Flow (Based upon 12°F rise in temp.)...............2.3 GPM
Air Flow........................................................................350 CFM
Step 3, 4 & 5 HP Selection:
After making our preliminary selection (HRC12), we enter the
tables at design water ow and water temperature and read
Total Cooling, Sens. Cooling and Heat of Rej. capacities:
Total Cooling.........................................................10,800 BTUH
Sensible Cooling.....................................................9,200 BTUH
Heat of Rejection..................................................13,900 BTUH
Step 6 & 7 Entering Air and Airow Corrections:
Next, we determine our correction factors.
Table Ent Air Air Flow Corrected
Corrected Total Cooling = 10,800 x 0.976 x 0.954 =10,056
Corrected Sens Cooling = 9,200 x 1.071 x 0.927 = 9,134
Corrected Heat of Reject = 13,900 x 0.979 x 0.958 = 13,037
Step 8 Water Temperature Rise Calculation & Assessment:
Actual Temperature Rise....................................................11.3°F
When we compare the Corrected Total Cooling and Corrected
Sensible Cooling gures with our load requirements stated
in Step 1, we discover that our selection is within +/- 10%
of our sensible load requirement. Furthermore, we see that
our Corrected Total Cooling gure is slightly undersized as
recommended, when compared to the actual indicated load.
6
Heat Controller HRC SERIES Design Guide
HRC Series Nomenclature
*Requires extended unit - see cabinet dimensions.
7
Design Guide HRC SERIES Heat Controller
Performance Data – AHRI/ASHRAE/ISO 13256-1
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Cooling 77°F Heating 32°F
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
HRC09
8,600 13.3 11,400 4.6 9,200 18.6 9,500 4.0 8,800 14.9 7,300 3.3
HRC12
11,300 12.8 14,100 4.5 12,500 18.7 11,800 3.9 11,800 14.5 9,300 3.3
HRC15
13,700 12.8 17,500 5.1 15,700 19.4 14,600 4.0 14,500 14.7 11,400 3.3
HRC18
15,600 12.2 20,100 4.5 17,200 17.9 16,500 3.9 16,100 13.8 13,200 3.3
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
All air ow is rated on high speed, Units factory shipped on medium and low motor taps.
All ratings based upon operation at lower voltage of dual voltage rated models
ASHRAE/AHRI/ISO 13256-1. English (I-P) Units
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°C
Capacity
kW
EER
W/W
Capacity
kW
COP
Capacity
kW
EER
W/W
Capacity
kW
COP
Capacity
kW
EER
W/W
Capacity
kW
COP
HRC09
2.52 3.9 3.34 4.6 2.70 5.5 2.78 4.0 2.58 4.4 2.14 3.3
HRC12
3.31 3.8 4.13 4.5 3.66 5.5 3.46 3.9 3.46 4.3 2.73 3.3
HRC15
4.02 3.8 5.13 5.1 4.60 5.7 4.28 4.0 4.25 4.3 3.34 3.3
HRC18
4.57 3.6 5.89 4.5 5.04 5.3 4.84 3.9 4.72 4.0 3.87 3.3
Cooling capacities based upon 27°C DB, 19°C WB entering air temperature
Heating capacities based upon 20°C DB, 15°C WB entering air temperature
All air ow is rated on high speed, Units factory shipped on medium and low motor taps.
All ratings based upon operation at lower voltage of dual voltage rated models
ASHRAE/AHRI/ISO 13256-1. Metric (S-I) Units
8
Heat Controller HRC SERIES Design Guide
Performance Data – Selection Notes
For operation in the shaded area when water is used in lieu of
an antifreeze solution, the LWT (Leaving Water Temperature)
must be calculated. Flow must be maintained to a level such
that the LWT is maintained above 42°F [5.6°C] when the
JW3 jumper is not clipped (see example below). Otherwise,
appropriate levels of a proper antifreeze solution should be
used in systems with leaving water temperatures of 42ºF
[5.6°C] or below and the JW3 jumper should be clipped. This
is due to the potential of the refrigerant temperature being as
low as 32°F [0°C] with 40°F [4.4°C] LWT, which may lead to a
nuisance cutout due to the activation of the Low Temperature
Protection. JW3 should never be clipped for standard range
equipment or systems without antifreeze.
Example:
At 50°F EWT (Entering Water Temperature) and 1.5 gpm/ton, a
3 ton unit has a HE of 22,500 Btuh. To calculate LWT, rearrange
the formula for HE as follows:
HE = TD x GPM x 500, where HE = Heat of Extraction (Btuh);
TD = temperature difference (EWT - LWT) and GPM = U.S.
Gallons per Minute.
TD = HE / (GPM x 500)
TD = 22,500 / (4.5 x 500)
TD = 10°F
LWT = EWT - TD
LWT = 50 - 10 = 40°F
In this example, a higher ow rate will be required for EWTs at or below 50°F without antifreeze. At 2 gpm/ton, the calculation
above results in a TD of 7.5. LWT = 50 - 7.5 = 42.5°F, which is above 42°F EWT, and is acceptable for this application.
EWT
°F
GPM
WPD* Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT TC SC
Sens/Tot
Ratio
kW HR EER HC kW HE LAT COP
20
1.9 3.7 8.5
Operation Not Recommended
5.5 0.50 3.8 91.0 3.22
30
1.0 1.4 3.2 9.7 6.9 0.71 0.36 10.9 26.7 6.0 0.51 4.3 93.1 3.44
1.4 2.2 5.1 9.8 6.9 0.70 0.33 10.9 29.9 6.3 0.52 4.5 94.1 3.55
1.9 3.3 7.6 9.9 6.9 0.70 0.31 10.9 31.7 6.4 0.52 4.7 94.8 3.62
40
1.0 1.0 2.3 9.4 6.8 0.72 0.41 10.8 22.9 6.9 0.53 5.1 96.5 3.79
1.4 1.5 3.5 9.6 6.9 0.71 0.37 10.9 25.8 7.2 0.54 5.4 97.9 3.91
1.9 2.1 4.9 9.7 6.9 0.71 0.36 10.9 27.4 7.4 0.55 5.6 98.6 3.97
50
1.0 0.9 2.1 9.0 6.7 0.74 0.46 10.6 19.6 7.8 0.56 5.9 100.0 4.10
1.4 1.4 3.2 9.3 6.8 0.73 0.42 10.8 22.1 8.2 0.57 6.3 101.6 4.23
1.9 2.0 4.6 9.5 6.8 0.72 0.40 10.8 23.4 8.4 0.57 6.5 102.4 4.30
60
1.0 0.8 1.8 8.6 6.5 0.76 0.52 10.4 16.6 8.7 0.58 6.7 103.6 4.39
1.4 1.3 3.0 8.9 6.6 0.74 0.48 10.5 18.8 9.2 0.59 7.2 105.4 4.53
1.9 1.9 4.4 9.1 6.7 0.74 0.46 10.6 20.0 9.4 0.60 7.4 106.3 4.61
70
1.0 0.7 1.6 8.1 6.3 0.78 0.58 10.1 14.0 9.6 0.61 7.6 107.1 4.67
1.4 1.2 2.8 8.5 6.5 0.76 0.53 10.3 15.9 10.2 0.62 8.1 109.1 4.82
1.9 1.8 4.2 8.6 6.5 0.76 0.51 10.4 16.9 10.5 0.63 8.3 110.2 4.90
80
1.0 0.7 1.6 7.6 6.1 0.79 0.65 9.8 11.8 10.6 0.63 8.4 110.7 4.93
1.4 1.1 2.5 8.0 6.2 0.78 0.60 10.0 13.3 11.1 0.64 9.0 112.9 5.10
1.9 1.6 3.7 8.1 6.3 0.78 0.57 10.1 14.2 11.5 0.65 9.3 114.1 5.19
85
1.0 0.6 1.4 7.4 5.9 0.80 0.68 9.7 10.8 11.0 0.64 8.9 112.5 5.06
1.4 1.0 2.3 7.7 6.1 0.79 0.63 9.9 12.2 11.6 0.65 9.4 114.8 5.24
1.9 1.5 3.5 7.9 6.2 0.78 0.61 10.0 13.0 12.0 0.66 9.7 116.1 5.33
90
1.0 0.6 1.4 7.2 5.8 0.81 0.72 9.6 9.9 11.5 0.65 9.3 114.2 5.19
1.4 1.0 2.3 7.5 6.0 0.80 0.67 9.8 11.1 12.1 0.66 9.9 116.7 5.38
1.9 1.4 3.2 7.6 6.1 0.79 0.64 9.8 11.9 12.5 0.67 10.2 118.0 5.48
100
1.0 0.5 1.2 6.7 5.5 0.81 0.81 9.5 8.3
Operation Not Recommended
1.4 0.9 2.1 7.0 5.7 0.81 0.75 9.6 9.3
1.9 1.3 3.0 7.2 5.8 0.81
0.72 9.6 9.9
110
1.0 0.5 1.2 6.4 5.2 0.81 0.91 9.5 7.0
1.4 0.9 2.1 6.6 5.4 0.81 0.84 9.5 7.8
1.9 1.3 3.0 6.7 5.5 0.81 0.81 9.5 8.3
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and
66.2°F WB in cooling and 68°F DB in heating.
Table does not reect fan or pump power corrections for ARI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit (standard on residential models).
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in shaded areas.
9
Design Guide HRC SERIES Heat Controller
Performance Data – HRC09
EWT
°F
GPM
WPD* Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT TC SC
Sens/
Tot
Ratio
kW HR EER HC kW HE LAT COP
20
2.2 5.0 11.6
Operation not recommended
6.3 0.67 4.0 86.6 2.72
30
1.1 1.6 3.7 9.2 6.7 0.73 0.44 10.7 20.6 6.9 0.69 4.6 88.2 2.94
1.6 2.6 6.0 8.9 6.6 0.74 0.43 10.4 20.7 7.2 0.69 4.8 89.0 3.04
2.2 4.5 10.4 8.8 6.5 0.74 0.43 10.2 20.6 7.3 0.69 5.0 89.4 3.11
40
1.1 1.4 3.2 9.4 6.9 0.73 0.47 11.1 19.9 7.9 0.70 5.5 90.9 3.29
1.6 2.3 5.3 9.3 6.8 0.73 0.45 10.9 20.5 8.3 0.71 5.9 91.8 3.41
2.2 4.2 9.7 9.2 6.7 0.73 0.45 10.7 20.6 8.5 0.71 6.1 92.4 3.48
50
1.1 1.2 2.8 9.5 7.0 0.74 0.51 11.3 18.5 8.9 0.72 6.5 93.7 3.63
1.6 2.2 5.1 9.5 6.9 0.73 0.49 11.1 19.5 9.3 0.73 6.9 94.7 3.76
2.2 3.8 8.8 9.4 6.9 0.73 0.47 11.1 19.9 9.6 0.73 7.1 95.4 3.84
60
1.1 1.1 2.5 9.4 7.1 0.76 0.56 11.3 16.7 10.0 0.74 7.5 96.4 3.95
1.6 2.1 4.9 9.5 7.0 0.74 0.53 11.3 17.9 10.4 0.75 7.9 97.6 4.08
2.2 3.7 8.5 9.5 7.0 0.74 0.51 11.2 18.6 10.7 0.75 8.1 98.3 4.16
70
1.1 1.0 2.3 9.0 7.1 0.79 0.62 11.2 14.5 11.0 0.76 8.4 99.0 4.23
1.6 2.0 4.6 9.3 7.1 0.77 0.58 11.3 15.9 11.4 0.77 8.8 100.2 4.36
2.2 3.5 8.1 9.4 7.1 0.76 0.56 11.3 16.7 11.7 0.77 9.1 101.0 4.43
80
1.1 1.0 2.3 8.5 7.0 0.82 0.69 10.9 12.3 11.9 0.78 9.2 101.4 4.47
1.6 1.9 4.4 8.8 7.1 0.80 0.65 11.1 13.7 12.3 0.79 9.6 102.6 4.58
2.2 3.2 7.4 9.0 7.1 0.79 0.62 11.2 14.5 12.6 0.80 9.9 103.4 4.64
85
1.1 1.0 2.2 8.1 6.9 0.84 0.73 10.6 11.1 12.3 0.79 9.6 102.5 4.56
1.6 1.9 4.4 8.5 7.0 0.82 0.68 10.9 12.5 12.7 0.80 10.0 103.6 4.66
2.2 3.1 7.2 8.8 7.0 0.80 0.66 11.0 13.3 13.0 0.81 10.2 104.3 4.71
90
1.1 0.9 2.1 7.8 6.7 0.87 0.77 10.4 10.1 12.7 0.80 10.0 103.5 4.66
1.6 1.9 4.4 8.2 6.9 0.84 0.72 10.7 11.4 13.1 0.81 10.3 104.6 4.74
2.2 3.0 6.9 8.5 7.0 0.82 0.69 10.9 12.2 13.3 0.82 10.5 105.2 4.77
100
1.1 0.9 2.1 6.9 6.3 0.91 0.86 9.8 7.9
Operation not recommended
1.6 1.8 4.2 7.4 6.6 0.89 0.81 10.2 9.1
2.2 2.9 6.7 7.7 6.7
0.87 0.78 10.4 9.9
110
1.1 0.9 2.1 5.8 5.6 0.97 0.96 9.1 6.0
1.6 1.8 4.2 6.4 6.0 0.94 0.91 9.5 7.0
2.2 2.9 6.7 6.7 6.2 0.92 0.87 9.7 7.7
120
1.1 0.9 2.1 4.5 4.6 1.00 1.07 8.2 4.2
1.6 1.8 4.2 5.1 5.1 1.00 1.02 8.6 5.0
2.2 2.8 6.5 5.5 5.4 0.98 0.98 8.9 5.6
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not reect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in the shaded areas.
Performance capacities shown in thousands of Btuh350 CFM Nominal (Rated) Airow
*WPD Adder for
Motorized Valve,
HRC09
(Cv = 4.9,
MOPD = 150 psi)
GPM
WPD Adder
PSI FT
1.1 0.3 0.6
1.6 0.6 1.3
2.2 1.2 2.7
10
Heat Controller HRC SERIES Design Guide
Performance Data – HRC12
Performance capacities shown in thousands of Btuh450 CFM Nominal (Rated) Airow
EWT
°F
GPM
WPD* Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT TC SC
Sens/
Tot
Ratio
kW HR EER HC kW HE LAT COP
20
3.0 7.8 18.0
Operation not recommended
7.3 0.79 4.7 85.1 2.71
30
1.5 2.1 4.9 12.6 8.2 0.65 0.56 14.5 22.4 8.1 0.81 5.4 86.7 2.96
2.3 4.5 10.4 12.4 8.0 0.65 0.53 14.2 23.3 8.5 0.81 5.7 87.5 3.06
3.0 6.8 15.7 12.3 8.0 0.65 0.52 14.0 23.6 8.7 0.82 5.9 87.9 3.12
40
1.5 2.0 4.6 12.7 8.4 0.67 0.61 14.7 20.7 9.4 0.83 6.7 89.4 3.35
2.3 4.2 9.7 12.6 8.2 0.65 0.58 14.6 21.9 9.9 0.83 7.1 90.4 3.48
3.0 6.1 14.1 12.6 8.2 0.65 0.56 14.5 22.4 10.2 0.84 7.3 90.9 3.56
50
1.5 1.8 4.2 12.5 8.7 0.70 0.67 14.8 18.7 10.8 0.85 8.0 92.3 3.74
2.3 3.8 8.8 12.6 8.5 0.68 0.63 14.8 20.0 11.4 0.86 8.5 93.5 3.91
3.0 5.8 13.4 12.7 8.4 0.67 0.61 14.7 20.7 11.7 0.86 8.8 94.1 4.00
60
1.5 1.7 3.9 12.1 9.0 0.74 0.73 14.6 16.6 12.2 0.87 9.3 95.1 4.14
2.3 3.7 8.5 12.4 8.8 0.71 0.69 14.7 17.9 12.9 0.87 9.9 96.5 4.32
3.0 5.2 12.0 12.5 8.7 0.70 0.67 14.8 18.6 13.2 0.88 10.2 97.2 4.41
70
1.5 1.5 3.5 11.6 9.2 0.79 0.80 14.4 14.5 13.6 0.88 10.6 97.9 4.50
2.3 3.5 8.1 12.0 9.1 0.76 0.76 14.5 15.8 14.3 0.89 11.2 99.4 4.69
3.0 4.9 11.3 12.1 9.0 0.74 0.73 14.6 16.5 14.6 0.90 11.6 100.1 4.79
80
1.5 1.4 3.2 11.0 9.2 0.83 0.89 14.1 12.5 14.8 0.90 11.8 100.5 4.84
2.3 3.2 7.4 11.4 9.2 0.81 0.83 14.3 13.7 15.5 0.91 12.4 101.9 5.01
3.0 4.8 11.1 11.6 9.2 0.79 0.81 14.4 14.4 15.8 0.91 12.7 102.6 5.10
85
1.5 1.4 3.1 10.7 9.1 0.85 0.93 13.9 11.5 15.4 0.90 12.3 101.6 4.98
2.3 3.1 7.2 11.1 9.2 0.83 0.88 14.1 12.7 16.0 0.91 12.9 102.9 5.13
3.0 4.7 10.7 11.3 9.2 0.81 0.85 14.2 13.4 16.3 0.92 13.1 103.5 5.20
90
1.5 1.3 3.0 10.4 9.1 0.87 0.98 13.7 10.6 15.9 0.91 12.8 102.7 5.11
2.3 3.0 6.9 10.8 9.2 0.85 0.92 13.9 11.7 16.5 0.92 13.3 103.9 5.25
3.0 4.5 10.4 11.0 9.2 0.84 0.89 14.1 12.3 16.7 0.92 13.6 104.4 5.31
100
1.5 1.3 3.0 9.7 8.7 0.90 1.08 13.4 9.0
Operation not recommended
2.3 2.9 6.7 10.1 9.0 0.88 1.02 13.6 9.9
3.0 4.3 9.9 10.3 9.0
0.88 0.99 13.7 10.5
110
1.5 1.2 2.8 9.0 8.2 0.91 1.20 13.1 7.5
2.3 2.9 6.7 9.4 8.5 0.90 1.13 13.3 8.4
3.0 4.2 9.7 9.6 8.7 0.90 1.09 13.4 8.8
120
1.5 1.2 2.8 8.4 7.5 0.89 1.33 12.9 6.3
2.3 2.8 6.5 8.7 7.9 0.91 1.25 13.0 7.0
3.0 4.1 9.5 8.9 8.1 0.91 1.21 13.1 7.4
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not reect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in the shaded areas.
*WPD Adder for
Motorized Valve,
HRC12
(Cv = 4.9,
MOPD = 150 psi)
GPM
WPD Adder
PSI FT
1.5 0.5 1.0
2.3 1.2 2.7
3.0 2.2 5.0
11
Design Guide HRC SERIES Heat Controller
Performance Data – HRC15
Performance capacities shown in thousands of Btuh520 CFM Nominal (Rated) Airow
EWT
°F
GPM
WPD* Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT TC SC
Sens/Tot
Ratio
kW HR EER HC kW HE LAT COP
20
3.7 5.1 11.8
Operation not recommended
8.9 0.92 5.8 85.9 2.86
30
1.9 1.5 3.5 16.9 11.0 0.65 0.62 19.0 27.1 10.0 0.94 6.8 87.8 3.11
2.8 3.0 6.9 16.5 10.4 0.63 0.58 18.5 28.6 10.5 0.95 7.2 88.6 3.22
3.7 4.7 10.9 16.3 10.1 0.62 0.56 18.2 29.2 10.7 0.96 7.5 89.1 3.28
40
1.9 1.2 2.8 16.9 11.4 0.67 0.70 19.3 24.1 11.7 0.98 8.4 90.8 3.51
2.8 2.6 6.0 16.9 11.2 0.65 0.65 19.1 26.2 12.3 0.99 8.9 91.9 3.64
3.7 4.3 9.9 16.9 11.0 0.65 0.62 19.0 27.1 12.6 0.99 9.2 92.4 3.71
50
1.9 1.0 2.3 16.6 11.5 0.69 0.79 19.3 21.0 13.4 1.01 10.0 93.9 3.91
2.8 2.3 5.3 16.9 11.5 0.68 0.73 19.4 23.1 14.1 1.02 10.7 95.2 4.06
3.7 3.9 9.0 16.9 11.4 0.67 0.70 19.3 24.2 14.5 1.03 11.0 95.9 4.15
60
1.9 0.9 2.1 15.9 11.3 0.71 0.89 18.9 17.9 15.2 1.04 11.7 97.1 4.29
2.8 2.1 4.9 16.4 11.4 0.70 0.82 19.2 19.9 16.0 1.05 12.4 98.5 4.46
3.7 3.5 8.1 16.6 11.5 0.69 0.79 19.3 21.0 16.4 1.06 12.8 99.3 4.56
70
1.9 0.9 2.1 15.0 10.9 0.73 0.99 18.4 15.2 16.9 1.06 13.3 100.1 4.66
2.8 2.0 4.6 15.6 11.2 0.72 0.92 18.8 16.9 17.8 1.08 14.1 101.6 4.84
3.7 3.3 7.6 15.9 11.3 0.71 0.89 18.9 17.9 18.2 1.08 14.5 102.5 4.93
80
1.9 0.9 2.1 14.0 10.5 0.75 1.10 17.8 12.7 18.5 1.09 14.8 103.0 4.99
2.8 1.8 4.2 14.6 10.8 0.74 1.03 18.2 14.2 19.4 1.10 15.6 104.5 5.17
3.7 3.1 7.2 15.0 10.9 0.73 1.00 18.4 15.0 19.8 1.10 16.1 105.3 5.26
85
1.9 0.9 2.0 13.4 10.3 0.77 1.16 17.4 11.6 19.2 1.10 15.5 104.3 5.14
2.8 1.8 4.0 14.1 10.5 0.75 1.09 17.8 13.0 20.1 1.11 16.3 105.8 5.31
3.7 3.0 6.9 14.4 10.7 0.74 1.05 18.0 13.8 20.5 1.11 16.7 106.5 5.40
90
1.9 0.8 1.8 12.9 10.0 0.78 1.22 17.0 10.5 20.0 1.11 16.2 105.6 5.29
2.8 1.7 3.9 13.5 10.3 0.76 1.15 17.5 11.8 20.8 1.12 17.0 107.0 5.45
3.7 2.9 6.7 13.9 10.5 0.75 1.11 17.7 12.5 21.2 1.12 17.3 107.7 5.53
100
1.9 0.8 1.8 11.7 9.6 0.82 1.35 16.3 8.7
Operation not recommended
2.8 1.6 3.7 12.4 9.8 0.80 1.27 16.7 9.7
3.7 2.8 6.5 12.7 10.0 0.78 1.23 17.0 10.3
110
1.9 0.8 1.8 10.6 9.2 0.87 1.48 15.7 7.2
2.8 1.6 3.7 11.2 9.4 0.84 1.40 16.0 8.0
3.7 2.7 6.2 11.5 9.5 0.83 1.37 16.2 8.4
120
1.9 0.7 1.6 9.6 9.0 0.94 1.62 15.1 5.9
2.8 1.5 3.5 10.1 9.1 0.90 1.54 15.4 6.5
3.7 2.7 6.2 10.4 9.2 0.88 1.51 15.5 6.9
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not reect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in the shaded areas.
*WPD Adder for
Motorized Valve,
HRC15
(Cv = 4.9,
MOPD = 150 psi)
GPM
WPD Adder
PSI FT
1.9 0.7 1.7
2.8 1.7 4.0
3.7 3.3 7.6
12
Heat Controller HRC SERIES Design Guide
Performance Data – HRC18
Performance capacities shown in thousands of Btuh620 CFM Nominal (Rated) Airow
EWT
°F
GPM
WPD* Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT TC SC
Sens/
Tot
Ratio
kW HR EER HC kW HE LAT COP
20
4.5 7.5 17.3
Operation not recommended
13.9 1.24 9.8 90.8 3.29
30
2.3 2.2 5.1 18.6 12.3 0.66 0.72 21.0 25.7 15.3 1.28 11.0 92.8 3.51
3.4 4.4 10.2 17.6 11.6 0.66 0.69 19.9 25.3 15.7 1.28 11.3 93.4 3.57
4.5 6.9 15.9 16.9 11.1 0.66 0.68 19.3 24.8 15.8 1.29 11.5 93.7 3.61
40
2.3 2.0 4.6 19.3 13.2 0.68 0.80 22.1 24.2 16.6 1.30 12.2 94.8 3.74
3.4 4.1 9.5 19.0 12.8 0.67 0.75 21.6 25.3 16.9 1.30 12.4 95.2 3.79
4.5 6.3 14.6 18.8 12.5 0.67 0.73 21.3 25.6 17.0 1.31 12.6 95.4 3.81
50
2.3 1.8 4.2 19.1 13.5 0.70 0.90 22.2 21.4 17.5 1.31 13.0 96.1 3.91
3.4 3.8 8.8 19.3 13.3 0.69 0.84 22.2 23.1 17.7 1.31 13.2 96.4 3.95
4.5 6.0 13.9 19.4 13.2 0.68 0.81 22.1 23.9 17.8 1.31 13.3 96.5 3.97
60
2.3 1.6 3.7 18.4 13.3 0.72 1.01 21.8 18.2 18.2 1.31 13.8 97.2 4.07
3.4 3.6 8.3 18.9 13.4 0.71 0.94 22.1 20.1 18.5 1.31 14.0 97.6 4.12
4.5 5.6 12.9 19.1 13.5 0.70 0.91 22.2 21.0 18.6 1.31 14.2 97.8 4.15
70
2.3 1.5 3.5 17.2 12.8 0.75 1.13 21.1 15.3 19.3 1.32 14.8 98.8 4.27
3.4 3.4 7.9 17.9 13.1 0.73 1.06 21.5 17.0 19.7 1.33 15.2 99.5 4.36
4.5 5.2 12.0 18.2 13.3 0.73 1.02 21.7 17.9 20.0 1.33 15.5 99.9 4.40
80
2.3 1.4 3.2 15.9 12.1 0.76 1.25 20.2 12.7 21.0 1.35 16.4 101.3 4.55
3.4 3.2 7.4 16.7 12.6 0.75 1.18 20.7 14.1 21.8 1.37 17.1 102.6 4.68
4.5 5.0 11.6 17.0 12.7 0.75 1.14 21.0 14.9 22.3 1.38 17.6 103.3 4.75
85
2.3 1.4 3.1 15.3 11.7 0.77 1.32 19.8 11.6 22.2 1.38 17.6 103.2 4.73
3.4 3.1 7.15 16.0 12.2 0.76 1.25 20.3 12.9 23.3 1.40 18.6 104.9 4.88
4.5 4.9 11.35 16.4 12.4 0.76 1.21 20.6 13.6 24.0 1.42 19.2 105.9 4.97
90
2.3 1.3 3.0 14.6 11.3 0.77 1.39 19.4 10.5 23.5 1.40 18.7 105.1 4.91
3.4 3.0 6.9 15.3 11.8 0.77 1.32 19.8 11.6 24.9 1.43 20.0 107.2 5.08
4.5 4.8 11.1 15.7 12.0 0.76 1.28 20.1 12.3 25.7 1.45 20.8 108.4 5.18
100
2.3 1.3 3.0 13.5 10.5 0.78 1.53 18.8 8.8
Operation not recommended
3.4 2.9 6.7 14.1 10.9 0.78 1.46 19.1 9.6
4.5 4.6 10.6 14.4 11.1
0.77 1.42 19.2 10.1
110
2.3 1.2 2.8 12.8 9.8 0.77 1.67 18.5 7.6
3.4 2.8 6.5 13.1 10.1 0.77 1.60 18.6 8.2
4.5 4.5 10.4 13.3 10.3 0.78 1.56 18.7 8.5
120
2.3 1.2 2.8 12.6 9.4 0.74 1.82 18.9 6.9
3.4 2.8 6.5 12.6 9.5 0.76 1.75 18.6 7.2
4.5 4.4 10.2 12.7 9.7 0.76 1.71 18.5 7.4
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not reect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in the shaded areas.
*WPD Adder for
Motorized Valve,
HRC18
(Cv = 4.9,
MOPD = 150 psi)
GPM
WPD Adder
PSI FT
2.3 0.2 0.6
3.4 0.6 1.3
4.5 1.1 2.5
13
Design Guide HRC SERIES Heat Controller
Performance Data Correction Tables
Air Flow Correction Table
Entering Air Correction Table
Airow Cooling Heating
% of
Rated
Total
Capacity
Sensible
Capacity
Power
Heat of
Rejection
Heating
Capacity
Power
Heat of
Extraction
73%
0.946 0.898 0.971 0.951 0.967 1.084 0.937
78%
0.954 0.927 0.976 0.958 0.976 1.062 0.954
83%
0.964 0.953 0.981 0.967 0.983 1.042 0.968
89%
0.974 0.974 0.987 0.977 0.990 1.026 0.981
94%
0.987 0.990 0.993 0.988 0.995 1.012 0.991
100%
1.000 1.000 1.000 1.000 1.000 1.000 1.000
106%
1.015 1.002 1.008 1.014 1.004 0.991 1.007
111%
1.031 0.996 1.016 1.028 1.006 0.985 1.011
Cooling
Entering
Air WB°F
Total
Capacity
Sensible Cooling Capacity Multiplier -
Entering DB °F
Power
Heat of
Rejection
65 70 75 80 80.6 85 90
60
0.926 0.632 0.820 1.004 1.182 * * * 1.003 0.931
65
0.976 0.615 0.856 1.071 1.095 1.260 * 1.000 0.979
66.2
0.990 0.555 0.807 1.030 1.055 1.224 * 1.000 0.992
67
1.000 0.507 0.765 1.000 1.017 1.188 * 1.000 1.000
70
1.039 0.620 0.865 0.893 1.076 1.252 1.001 1.032
75
1.113 0.566 0.597 0.805 1.013 1.002 1.089
* = Sensible capacity equals total capacity
AHRI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 80.6°F DB/66.2°F WB, 1
and Heating - 68°F DB/59°F WB entering air temperature
Heating
Entering
Air DB°F
Heating
Capacity
Power
Heat of
Extraction
60
1.036 0.910 1.068
65
1.019 0.955 1.035
68
1.008 0.982 1.014
70
1.000 1.000 1.000
75
0.980 1.046 0.964
80
0.960 1.091 0.927
Antifreeze Correction Table
Antifreeze Type
Antifreeze
%
Cooling Heating
WPD
Corr. Fct.
EWT 30°F
EWT 90°F EWT 30°F
Total Cap Sens Cap Power Htg Cap Power
Water
0 1.000 1.000 1.000 1.000
Propylene Glycol
5 0.995 0.995 1.003 0.989 0.997 1.070
15 0.986 0.986 1.009 0.968 0.990 1.210
25 0.978 0.978 1.014 0.947 0.983 1.360
Methanol
5 0.997 0.997 1.002 0.989 0.997 1.070
15 0.990 0.990 1.007 0.968 0.990 1.160
25 0.982 0.982 1.012 0.949 0.984 1.220
Ethanol
5 0.998 0.998 1.002 0.981 0.994 1.140
15 0.994 0.994 1.005 0.944 0.983 1.300
25 0.986 0.986 1.009 0.917 0.974 1.360
Ethylene Glycol
5 0.998 0.998 1.002 0.993 0.998 1.040
15 0.994 0.994 1.004 0.980 0.994 1.120
25 0.988 0.988 1.008 0.966 0.990 1.200
14
Heat Controller HRC SERIES Design Guide
Standard Unit With Secondary Pump
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
QTY RLA LRA
HRC09
0 115/60/1 104-126 1 8.0 46.5 0.5 8.5 10.5 20 8.8 11.3 20
1 208-230/60/1 197-254 1 4.5 23.0 0.4 4.9 6.0 15 5.3 6.4 15
8 265/60/1 239-292 1 5.0 19.0 0.4 5.4 6.7 15 6.2 7.5 15
HRC12
0 115/60/1 104-126 1 9.5 50.0 0.5 10.0 12.4 20 11.5 13.8 20
1 208-230/60/1 197-254 1 4.7 25.0 0.6 5.3 6.5 15 5.7 7.3 15
8 265/60/1 239-292 1 4.2 22.0 0.4 4.6 5.7 15 5.4 6.5 15
HRC15
1 208-230/60/1 197-254 1 5.6 30.0 0.8 6.4 7.8 15 7.2 8.6 15
8 265/60/1 239-292 1 4.7 28.5 0.6 5.3 6.5 15 6.2 7.3 15
HRC18
1 208-230/60/1 197-254 1 6.8 38.0 0.7 7.5 9.2 15 8.3 10.0 15
8 265/60/1 239-292 1 6.2 29.0 0.6 6.8 8.4 15 7.6 9.2 15
Blower Performance & Electrical Data
Blower Performance
Electrical Data
Model
Rated
CFM
SCFM
Low
Speed
Medium
Speed
High
Speed
HRC09
350 270 310 350
HRC12
450 290 360 450
HRC15
520 360 440 520
HRC18
620 400 500 620
Fan speed is user selectable
All airow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units
All units AHRI/ISO/ASHRAE 13256-1 rated on high fan speed
All units are designed and rated for zero external static pressure (non-ducted) application
15
Design Guide HRC SERIES Heat Controller
Physical Data
Model 09 12 15 18
Compressor (1 Each)
Factory Charge HFC-410A (oz) [kg] 28 [0.794] 29 [0.822] 33 [0.907] 39 [1.105]
Blower Wheel
Blower Wheel Size (dia x w) -
(in) [mm] - Qty 2
5.25 x 6.25 [133 x 159]
Water Connection Size
O.D. Sweat (in) [mm] 1/2 [12.7] 3/4 [19.1]
Optional FPT Fittings (in) 1/2 3/4
Optional MPT Fittings (in) 1/2 3/4
Coax Volume
Volume US Gal
[Liters]
.09
[.34]
.09
[.34]
.23
[.87]
.26
[.98]
Condensate Connection Size
I.D. Vinyl Hose (In) [mm] 5/8 [15.9]
Air Coil Size
Dimensions (h x w) - (in) [mm]
8 x 26
[203 x 660]
10 x 26
[254 x 660]
10 x 32
[254 x 812]
Filter Size
Bottom Return (in) [mm] 1 - 10 x 30 x 1 [254 x 762 x 25] 1 - 10 x 36 x 1 [254 x 914 x 25]
Front Return (In) [mm] 1 - 7 x 29.5 x 1/8 [178 x 749 x 3.2] 1 - 7 x 35.5 x 1/8 [178 x 902 x 3.2]
Cabinet Size
Bottom Return (Std. 5” Base)
(W x H x D) - (In) [mm]
48 x 26 x 12 [1219 x 660 x 305] 54 x 26 x 12 [1372 x 660 x 305]
Front Return (No Subbase)
(W x H x D) - (In) [mm]
48 x 21 x 12 [1219 x 533 x 305] 54 x 21 x 12 [1372 x 533 x 305]
Cabinet Size
Weight - Operating, (lbs) [kg] 175 [79] 180 [82] 190 [86.2] 220 [99.8]
Weight - Packaged, (lbs) [kg] 185 [83.9] 190 [86] 200 [90.8] 232 [105.2]
* Data not available at time of publication.
All units have rubber grommet compressor mountings and TXV expansion devices.
Unit Maximum Water Working Pressure
Options
Max Pressure PSIG [kPa]
Base Unit
500 [3,445]
Internal Secondary Pump (ISP)
145 [999]
Internal Motorized Water Valve (MWV)
300 [2,068]
Internal Auto Flow Valve
500 [3,445]
Use the lowest maximum pressure rating when multiple options are combined.
Optional Factory Installed Auto Flow Regulator GPM [LPS]
Model 2.25 GPM/Ton 3 GPM/Ton
9
2.0 [.126] 2.5 [.158]
12
2.5
[.158] 3.0 [.189]
15
3.0
[.189] 3.5 [.221]
18
3.5
[.221] 4.0 [.252]
Use the lowest maximum pressure rating when multiple options are combined.
16
Heat Controller HRC SERIES Design Guide
Console Cabinet Dimensions Size 09 -15 - Bottom Return - Left Hand Piping
30°
11.50
(292)
.12
(3)
4.90
(125)
3.50
(89)
25.90
(658)
DAMPER OPENING
40.98
A
(1041)
1.63
(41)
1 1.75
(298)
D
0.59
(15)
21.00
(533)
4.90
(125)
REAR VIEW
Ai
Sub-base
r
Inlet
Discharge
Air
12.00
(305)
Rev.: 10/03/08B
BOTTOM VIEW
11.0
(279)
FRONT VIEW
Control Access Door
AIR INLET AREA
A
C
B
F
Left Hand Bottom Return
Notes:
1.50
(38)
3.53
(90)
1.75
(44)
3.00
(76)
0.75
(19)
Bottom Access for
Piping and Electric
(Note 2)
L.H.
Rear Access
For Piping
and Electric
(NOTE 2)
10.00
(254)
1.00
(25)
1.00
(25)
E
20.00
(508)
SIDE
VIEW
Filter located inside and at
Discharge Air Grille
top of air inlet area. Rotate
filter latch forward, filter rack
can be pulled forward 3” to 4”
for filter access.
1. All Dimensions are in inches (mm).
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow regulator, motorized water valve, and disconnect box are not shown.
4. Filter is 1”(25) thick fiberglass throwaway.
6.88
(174)
2.12 (54)
Fixed
Back
Wrapper
Removable
Cabinet
A B C D E F
Standard
Unit
48.00
(1219)
1.75
(44.5)
33.50
(851)
9.90
(251)
4.50
(114)
5.00
(127)
Extended
Unit
54.00
(1372)
11.50
(292)
34.50
(876)
22.90
(582)
10.50
(267)
11.00
(279)
Secondary circulation
pump models will
have extended unit.
17
Design Guide HRC SERIES Heat Controller
Console Cabinet Dimensions Size 09 - 15 - Front Return - Left Hand Piping
°
L.H. Rear
Access for
Piping and
Electric (NOTE 2)
Notes:
1. All Dimensions are in inches (mm).
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow regulator, motorized water valve, and disconnect box are not shown.
4. Filter is a cleanable polypropylene mesh.
3.50
(89)
21.00
(533)
12.00
(305)
40.98
(1041)
.50
(13)
.75
(19)
D
1.00
(25)
1.00
(25)
21.00
(533)
Bottom Access for
Piping and Electric
(Note 2)
Fixed Back
Wrapper
Removable
Cabinet
11.50
(292)
A
B
Left Hand Front Return
43.70
(1110)
7.90
(201)
11.00
(279)
1.50
(38)
A
C
Discharge Air Grille
A B C D
Standard
Unit
48.00
(1219)
4.50
(114)
5.00
(127)
4.12
(105)
Extended
Unit
54.00
(1372)
10.50
(267)
11.00
(279)
10.12
(257)
Secondary circulation
pump models will
have extended unit.
18
Heat Controller HRC SERIES Design Guide
Console Cabinet Dimensions Size 09 - 15 - Bottom Return - Right Hand Piping
30
11.50
(292)
4.90
(125)
3.50
(89)
25.90
(658)
DAMPER OPENING
A
1.63
(41)
40.98
(1041)
11.75
(298)
D
0.59
(15)
21.00
(533)
4.90
(125)
REAR VIEW
Air
Inlet
Discharge
Sub-base
Removable
Cabinet
Fixed Back
Wrapper
Air
1.75
(44)
3.00
(76)
2.12 (54)
Bottom Access for
Piping and Electric
(Note 2)
1.00
(25)
1.00
(25)
E
12.00
(305)
10.00
(254)
BOTTOM VIEW
FRONT VIEW
Control
Discharge Air
Grille
Access Door
AIR INLET AREA
A
C
F
B
Right Hand Bottom Return
3.53
.12
(3)
(90)
SIDE
VIEW
Rev.: 10/03/08B
˚
Filter located inside and at
top of air inlet area. Rotate
filter latch forward, filter rack
can be pulled forward 3” to 4”
for filter access
Notes:
R.H.
Rear Access
for Piping
and Electric
(Note 2)
1. All Dimensions are in inches (mm).
2. Access is reduced if optional disconnect box is selected.
3. Optional autoflow regulator, motorized water valve, and disconnect box are not shown.
4. Filter is 1”(25) thick fiberglass throwaway.
6.88
(174)
.75 (19)
1.50
(38)
11.00
(279)
A B C D E F
Standard
Unit
48.00
(1219)
1.75
(44.5)
33.50
(851)
9.90
(251)
4.50
(114)
5.00
(127)
Extended
Unit
54.00
(1372)
1.75
(44.5)
33.72
(856)
12.85
(326)
10.50
(267)
11.00
(279)
Secondary circulation
pump models will
have extended unit.
19
Design Guide HRC SERIES Heat Controller
Console Cabinet Dimensions Size 09 - 15 - Front Return - Right Hand Piping
30
3.50
(89)
21.00
(533)
21.00
(533)
REAR VIEW
Discharge
Air
1.00
(25)
1.00
(25)
B
12.00
(305)
11.0
(279)
FRONT VIEW
Control Access Door
Discharge
Air Grille
A
C
43.70
(1110)
Right Hand Front Return
7.90
(201)
Bottom Access
for Piping
and Electric
12.00
(305)
BOTTOM VIEW
A
SIDE
VIEW
Air
Inlet
Filter located behind return
air grille and requires removal of
cabinet front for access.
˚
Notes:
1. All dimensions are in inches (mm).
2. Access is reduced if optional disconnect box is selected
3. Optional autoflow regulator, motorized water valve, and disconnect box are not shown.
4. Filter is a cleanable polypropylene mesh.
.50
(13)
11.50
(292)
.75
(19)
D
A B C D
Standard
Unit
48.00
(1219)
4.50
(114)
5.00
(127)
4.12
(105)
Extended
Unit
54.00
(1372)
10.50
(267)
11.00
(279)
10.12
(257)
40.98
(1041)
1.50
(38)
R.H.
Rear Access
for Piping
and Electric
(Note 2)
Removable
Cabinet
Fixed Back
Wrapper
Secondary circulation
pump models will
have extended unit.
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

COMFORT-AIRE HRC09A1CAMSCFL User guide

Category
Heat pumps
Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI