OrderofInstallation
TouseACSmart5,youneedtoestablishenvironmentformutualcommunicationbetweenACSmart5anddevices(indoorunit,ERV,DI/DO,DOKIT,Heating,AHU,I/O
module)andregisterthecorrespondingdevicesthroughthefunctionsofACSmart5.
TouseACSmart5,itshallbeinstalledinthefollowingorder.
STEP1.Installationenvironmentinspectionanddeviceaddresssetting
BeforeinstallingACSmart5,checknetworkcompositionwithinterfacingdevicesandassignnon-overlappingaddresstotheconnecteddevices.
STEP2.PI485setting
InstallPI485andsetDIPswitch.
STEP3.PI485andACSmart5connection
ConnectPI485andACSmart5throughRS-485cable.
STEP4.Log-inanddeviceregistration
LogintoACSmart5andregisterdevicewithaddressset.
CAUTION
TheinstallationofACSmart5mustbedonebyaprofessional.Besuretocontactaqualifiedengineerfortheinstallation.Ifyouhaveaquestionor
requestregardingtheinstallation,contactaninstallationprofessionalatanauthorizedLGservicecenterorLGElectronics.
NOTE
MaximumnodenumberswhichcanbeconnectedtoRS485communicationline.
•MultiV
Maximumof16nodescanbeconnectedto1RS485line.
•Multi/Single
Maximumof32nodescanbeconnectedto1RS485line.
•ERV
Maximumof32nodescanbeconnectedto1RS485line.
UserManual