Lochinvar ProtoNode FPC-N34 Startup Manual

Type
Startup Manual

This manual is also suitable for

ProtoNodeFPCN34andProtoNode
FPCN35
Startup
Guide
ForInterfacingLochinvar
Products:
Lochinvar’sArmor®,SYNC™/ArmorX2,Knight®/Knig htXL®,
FTXL,
Crest®,CopperFinII®andPowerFin
boilers
ToBuildingAutomation
Systems:
BACnetMS/TP,BACnet/IP,ModbusTCP/IP,MetasysN2
and
LonWorks
APPLICABILITY&EFFECTIVITY
ExplainsProtoNodeFPCN34andFPCN35hardwareandhowtoinstallit.
TheinstructionsareeffectivefortheaboveasofAugust2014
DocumentRevision:
10
Auto
Selector
TemplateRevision:
23
INS70085LochinvarProtoNodeStartupGuide Page2 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
TechnicalSupport:
ThankyouforpurchasingtheProtoNodeforLochinvarBoilers.
PleasecallLochinvarforTechnicalsupportoftheProtoNodeproduct.
FieldServerdoesnotprovidedirectsupport. IfLochinvarneedstoescalatetheconcern,theywillcontact
FieldServerforassistance.
SupportContactInformation:
Lochinvar,LLC
300MaddoxSimpsonPkwy.
Lebanon,TN37090
LochinvarService:
18007222101
Email:2tec[email protected]
Website:www.lochinvar.co m
INS70085LochinvarProtoNodeStartupGuide Page3 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
AQuickStart
guide
1. Recordtheinformationabouttheunit. (Section2.1)
2. Setthedevice’sModbusRTUserialsettings(i.e.baudrate,parity,stopbits)andModbusNodeIDforeach
ofthedevicesthatwillbeconnectedtoProtoNodeFPCN34orFPCN35. (Section2.2)
3. SelectastoredconfigurationandsetfieldprotocolMACaddress/NodeID/DeviceInstance,andbaudrate.
(Section2.3)
4. ConnectProtoNode’s6pinRS485connectortotheModbusRS485networkthatisconnectedtoeachof
thedevices. (Section3.2)
5. ConnectFPCN34ProtoNode’s3pinRS485porttotheFieldProtocolcabling,
orconnectFPCN35ProtoNode’s2pinLonWorksporttotheFieldProtocolcabling. (Section3.4)
6. ConnectPowertoProtoNode’s6pinconnector. (Section3.5)
7. BACnet/IPorModbusTCP/IP/IP(FPCN34): UsetheProtoNode’sembeddedtoolwhichisaccessedwitha
browser,referredtointhismanualastheWebConfigurator,tochangetheIPaddress. Nochangestothe
configurationfilearenecessary. (Section4)
8. LonWorks(FPCN35):TheProtoNodemustbecommissionedonthe LonWorksNetwork.Thisneedstobe
donebytheLonWorksadministratorusingaLonWorksCommissioningtool. (Section6)
INS70085LochinvarProtoNodeStartupGuide Page4 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
Certifications
BTLMARKBACNETTESTING
LAB
O
R
ATORY
The BTL Mark on ProtoNode FPCN34 is a symbol that indicates that a product has
passed a series of rigorous tests conducted by an independent laboratory which
verifies that the product correctly implements the BACnet features claimed in the
listing.The mark is a symbol of a highquality
BACnet product.Go to
http://www.bacnetinternational.net/btl/ for more information about the BACnet
TestingLaboratory.
LONMARKC
ER
T
IFI
C
A
T
I
ON
LonMark International is the recognized authority for certification, education, and
promotionofinteroperabilitystandardsforthebenefitof manufacturers,integrators
and end users. LonMark International has developed extensive product certification
standardsandteststoprovidetheintegratoranduserwithconfidencethatproducts
from multiple manufacturers utilizing LonMark devices work
together. FieldServer
Technologies has more LonMark Certified gateways than any other gateway
manufacturer, including the ProtoCessor, ProtoCarrier and ProtoNode for OEM
applicationsandthefullfeatured,configurablegateways.
INS70085LochinvarProtoNodeStartupGuide Page5 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
TAB LE O F CONTENTS
1
Introduction
...................................................................................................................................................
7
1.1 ProtoNodeGateway......................................................................................................................................7
2 BACnet/LonWorksSetupforProtoCessorProtoNode
FPCN34/FPCN35.......................................................
7
2.1 RecordIdentification
Data
.............................................................................................................................7
2.2 ConfiguringDevice
Communications
............................... ..............................................................................7
2.2.1 SetModbusCOMsettingonallofthedevicesconnectedtotheProtoNode
..........................................7
2.2.2 SetModbusRTUNodeIDforeachofthedevicesattachedtothe
ProtoNode........................................8
2.3 SelectingStoredConfigurations,SettingtheMacAddress,DeviceInstance,Node_ID,andBaud
Rate
.......9
2.3.1 SelectingConfigurationFilesforDevices:“SbankDIPSwitchesS0
S3
................................................9
2.3.1.1 BACnetMS/TPandBACnetIPDIPSwitchSettings
.........................................................................9
2.3.1.2 LonWorksDIPSwitchSettings
......................................................................................................11
2.3.2 BACnetMS/TP(FPCN34):SettingtheMACAddressBACnet
Networks................................................11
2.3.3 BACnetMS/TPandBACnet/IP(FPCN34):SettingtheDevice
Instance.................................................12
2.3.3.1 BACnetMS/TPorBACnet/IP: AssigningSpecificDeviceInstances
..............................................12
2.3.4 MetasysN2andModbusTCP/IP(FPCN34):Settingthe
NodeID
.........................................................12
2.3.5 BACnetMS/TP(FPCN34):SettingtheSerialBaudRate(DIPSwitchB0
B3).......................................13
2.3.5.1 BaudRateDIPSwitchSelection
....................................................................................................13
3 InterfacingProtoNodetoDevices
................................................................................................................14
3.1 ProtoNodeFPCN34and FPCN35ShowingConnection
Ports
....................................................................14
3.2 DeviceCon nectionstoProtoNode...............................................................................................................15
3.2.1 EndofLineTerminationSwitchfortheModbusRS485portonthe
ProtoNode
...................................16
3.2.2 Lochinvar’sArmor,SYNC/ArmorX2,Knight/KnightXL,Crest,CopperFinIIandFTXL LowVoltage
ModbusRTUConnectionWiringtothe
ProtoNode:
............................................................................................17
3.3 BACnetMS/TPorMetasysN2(FPCN34):WiringFieldPorttoRS485
Network
........................................18
3.4 LonWorks(FPCN35):WiringFieldPorttoLonWorksNetwork..................................................................19
3.5 ConnectingPowerto
ProtoNode
................. ................................................................................................20
4
B
ACnet/IPandModbusTCP/IP:ChangetheProtonodeIP
Address..............................................................
21
4.1
ConnectthePCtoProtoNodeviathe Ethernet
Port
...................................................................................21
4.2
BACnetMS/
T
PandBACnet/IP: Setting Node
_
Offset to Assign Specific Device Instances.........................22
4.3
AccessingtheFS
T
WebGUIfromthe Web Configurator ............................................................................23
4.4
BACnet/IPandModbusTCP/IP:Setting IP Address for Field
Network
........................................................24
5 Howtostarttheinstallationover:clearingprofiles
.....................................................................................
25
6 LonWorks(FPCN35):CommissioningProtoNodeonaLonWorks
Network..................................................
26
6.1 CommissioningProtoNodeFPCN35onaLonWorksNetwork...................................................................26
6.1.1 InstructionstoUploadXIFFilefromProtoNodeFPCN35UsingFSGUIWeb
Server
.............................26
7 CASBACnetExplorerforValidatingProtoNodeintheField
.........................................................................
28
7.1 DownloadingtheCASExplorerandRequestinganActivationKey.............................................................28
7.2 CASBACnet
Setup
........................................................................................................................................29
7.2.1 CASBACnetMS/TPSetup.......................................................................................................................29
7.2.2 CASBACnetBACnet/IP
Setup
.................................................................................................................29
AppendixA.Troubleshooting
..............................................................................................................................
30
AppendixA.1.ViewingDiagno stic
information
.......................................................................................................30
AppendixA.2.CheckWiringandSettings................................................................................................................31
AppendixA.3.TakeDiagnosticCaptureWiththeFieldServerUtilities......................................................... ..........31
AppendixA.4.BACnet/IP:SettingNetwork_NumberformorethanoneProtoNodeonSubnet...........................34
AppendixA.5.LEDDiagnosticsforModbusRTUCommunicationsBetweenProtoNodean d
Devices
...................34
AppendixB.VendorInformation‐
Lochinvar
.......................................................................................................
35
AppendixB.1.SyncModbusRTUMappingstoBACnetMS/TP,BACnet/IP,MetasysN2and
LonWorks
................35
AppendixB.2.KnightModbusRTUMappingstoBACnetMS/TP,BACnet/IP,MetasysN2and
LonWorks
.............36
INS70085LochinvarProtoNodeStartupGuide Page6 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
AppendixB.3.CrestModbusRTUMappingstoBACnetMS/TP,BACnet/IP,MetasysN2and
LonWorks
...............38
AppendixB.4.CopperFinIIModbusRTUMappingstoBACnetMS/TP,BACnet/IP,MetasysN2andLonWorks..39
AppendixB.5.Powe rFinModbusRTUMappingstoBACnetMS/TP,BACnet/IP,MetasysN2and
LonWorks
.......41
AppendixB.6.FTXLModbusRTUMappingstoBACnetMS/TP,BACnet/IP,MetasysN2andLonWorks................42
AppendixC.“A”BankDIPSwitchSettings
...........................................................................................................
44
AppendixC.1.“A”BankDIPSwitchSettingsforMACAddressor
NodeID
.............................................................44
AppendixD.Reference
........................................................................................................................................
47
AppendixD.1.Specifications...................................................................................................................................47
AppendixD.1.1. CompliancewithULRegulations............................................................................................47
AppendixE.Limited2YearWarranty
..................................................................................................................
48
LIST OF FIGURES
Figure1:ProtoCessorPartNumbers.............................................................................................................................7
Figure2:ModbusRTUCOMSettings............................................................................................................................7
Figure3:Lochinvar’sModbusCOMboardshowingserialDIP
Switches
.......................................................................8
Figure4:SBankDIP
Switches
........................................................................................................................................9
Figure5:LocationforProtoCessorsmallABankofDIPswitches...............................................................................10
Figure6:MACAddressDIP
Switches
...........................................................................................................................11
Figure7:BaudRateDIP
Switches
................................................................................................................................13
Figure8:BaudRate......................................................................................................................................................13
Figure9:ProtoNodeBACnetFPCN34(upper)andProtoNodeFPCN35(lower).......................................................14
Figure10:PowerandRS485
Connections
..................................................................................................................15
Figure11:ModbusRS485EndOfLineTerminationSwitchontheProtoNodeN34(left)and.................................16
Figure12:LowVoltageModbusRTUConnectionWiringtotheProtoNode..............................................................17
Figure13:ConnectionfromProtoNodetoRS485FieldNetwork..............................................................................18
Figure14:RS485EOLSwitch......................................................................................................................................18
Figure15:
LonWorks
Terminal
.....................................................................................................................................19
Figure16: Requiredcurrentdrawforthe
ProtoNode
................................................................................................20
Figure17:Power
Connections
.....................................................................................................................................20
Figure18:WebConfiguratorscreen............................................................................................................................22
Figure19:WebConfiguratorscreenwithActiveProfiles............................................................................................23
Figure20:ChangingIPAddressviaFSTWeb
GUI
........................................................................................................24
Figure21:LonWorksServicePin
Location
...................................................................................................................26
Figure22:SampleofFserver.XIFFileBeing
Generated
...............................................................................................27
Figure23:DownloadingtheCAS
Explorer
...................................................................................................................28
Figure24:RequestingCASActivation
Key
...................................................................................................................28
Figure25:ViewingDiagnostic
Errors
...........................................................................................................................30
Figure26:EthernetPortLocation................................................................................................................................31
Figure27:WebConfiguratorshowingsettingthenetworknumberforBACnet/IP...................................................34
Figure28:Diagnostic
LEDs
...........................................................................................................................................34
Figure29:
Specifications
..............................................................................................................................................47
INS70085LochinvarProtoNodeStartupGuide Page7 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
1 INTRODUCTION
1.1 ProtoNode Gateway
ProtoNode is an external, high performance Building Automation multiprotocol gateway that has been
preprogrammed for Lochinvar’s products (hereafter called “device”) to various building automation
protocols. These protocols include BACnet®
1
MS/TP,BACnet/IP,Metasys®
2
N2 by JCI, ModbusTCP/IP, and
LonWorks®
3
.ConfigurationsforthevariousprotocolsarestoredwithintheProtoNodeandareselectablevia
DIPswitchesforfastandeasyinstallation.
Itisnotnecessarytodownloadanyconfigurationfilestosupporttherequiredapplications.
2 BACNET/LONWOR KSSETUPFORPROTOCESSORPROTONODEFPC‐ N34/FPC‐ N35
2.1
Record Identification D ata
Each ProtoNodehas aunique part numberlocated on theundersideof the unit.This number shouldbe
recorded,asitmayberequiredfortechnicalsupport.Thenumbersareasfollows:
Model
PartNumber
ProtoNodeFPCN34 FPCN340614
ProtoNodeFPCN35 FPCN351034010615
Figure1:ProtoCessorPartNumbers
FPCN34unitshavethefollowing3ports:RS485+Ethernet+RS485.
FPCN35unitshavethefollowing3ports:LonWorks+Ethernet+RS485
2.2 Configuring Device Communicati ons
2.2.1 Set Modbus COM setting on all of the devices connected to the ProtoNode


Set each Lochinvar Device’s Modbus RTU CO M setting to match Figure 2 via the DIP switches on the

Device’sModbuscard.
SettheDIPswitch1toONand210toOFFpositionontheModbusCOMboard.ThiswillsettheLochinvar
boilerfor9600,8,2,N,andNodeIDof1. (Seefigure3)
SerialPortSetting
Device
Protocol ModbusRTU
BaudRate 9600
Parity None
DataBits 8
StopBits 2
Figure2:ModbusRTUCOMSettings
1
BACnetisaregisteredtrademarkofASHRAE
2
MetasysisaregisteredtrademarkofJohnsonControlsInc.
4
LonWorksisaregisteredtrademarkofEchelonCorporation
INS70085LochinvarProtoNodeStartupGuide Page8 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
Figure3:Lochinvar’sModbusCOMboardshowingserialDIPSwitches
2.2.2 Set Modbus RTU Node‐ ID for each of the devices attached to the ProtoNode
SettheModbusNodeIDforeachofthedevic esattachedtoProtoNode.
TheModbusNodeID’sneedtobeuniquelyassigned,startingwithavalueof1forthefirstdevice.
ModbusNodeIDvaluesforadditionaldevicesmustbesequential(2,3,4,…).
INS70085LochinvarProtoNodeStartupGuide Page9 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
2.3 Selecting Stored Configurations, Setting the Mac Address, Device Instance,
Node_ID, and Baud Rate
2.3.1 SelectingConfigurationFilesforDevices:SbankDIPSwitchesS0S3
The S bank of DIP switches (S0‐S3) are used to select and load a configuration file from a group of
pretested/preloaded configuration files which are stored in the ProtoNode FPCN34 (BACnet MS/TP,
BACnet/IP,ModbusTCP/IP,MetasysN2)andtheProtoNode FPCN35(LonWorks).
S0 S1 S2
S3
S0S3DIPSwitches
SBankDIPSwitchLocation
Figure4:SBankDIP
Swit
c
h
e
s
2.3.
1.1
BACn
et
MS/
TP and
BA
Cnet IP DIP Switch
Sett
ing
s
The following chart describes S0‐S3 DIP Switch configuration settings for device applications to support
BACnetMS/TPandBACnet/IPonaProtoNodeFPCN34
TosetSYN C,Knight/KnightXL/Armor/WallMount/WallHung,Crest,CopperFinII,PowerFinandFTXLDIP
switchsettings,thecoverdoesnotneedtoberemoved.TheProtoCessorSmallABankofDIPswitchesare
alloff.Thisthedefaultpositionwhenshipped.
RemovetheProtoNodecovertosetProtoCessorSmallDIPswitchsettings.(SeeFigure3)

Cover
doesn’t
need
to
be
Removed
ProtoCarrierDIPSwitches
Profile‐FPCN340614
S0
S1
S2

S3

BACnetIP/BACnetMS
T
P/Modbus TCP/IP SYNC Deg
_
C Off Off Off Off
BACnetIP/BACnetMS
T
P/Modbus TCP/IP Knight/Knight
XL/Armor/WallMount/WallHungDeg_C
On Off Off Off
BACnetIP/BACnetMS
T
P/Modbus TCP/IPCrest Deg
_
C
Off
On
Off
Off
BACnetIP/BACnetMS
T
P/Modbus TCP/IPCopperFin II Deg_C
On
On
Off
Off
BACnetIP/BACnetMS
T
P/Modbus TCP/IP Power Fin Deg
_
C
Off
Off
On
Off
BACnetIP/BACnetMS
T
P/Modbus TCP/IP F
T
XL Deg
_
C
On
Off
On
Off
BACnetIP/BACnetMS
T
P/Modbus TCP/IP SYNC Deg
_
F
Off
On
On
Off
BACnetIP/BACnetMS
T
P/Modbus TCP/IP Knight/Knight
XL/Armor/WallMount/WallHungDeg_F
On
On
On
Off
BACnetIP/BACnetMS
T
P/Modbus TCP/IPCrest Deg
_
F
Off
Off
Off
On
BACnetIP/BACnetMS
T
P/Modbus TCP/IPCopperFin II Deg_F
On
Off
Off
On
BACnetIP/BACnetMS
T
P/Modbus TCP/IP Power Fin Deg
_
F
Off
On
Off
On
BACnetIP/BACnetMS
T
P/Modbus TCP/IP F
T
XL Deg
_
F
On
On
Off
On
INS70085LochinvarProtoNodeStartupGuide Page10 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
RemoveCovertoSelectABankDIPSwitches
S0
S1
S2
S3
A1
A2
A3
A4
A5
A6
A7
A8
MetasysN2SYNCDeg
_
C
Off
Off
On
On
Off
Off
Off
Off
Off
Off
Off
Off
MetasysN2Knight/KnightXL/Armor/Wall
Mount/WallHungDeg_C
On
Off
On
On
Off
Off
Off
Off
Off
Off
Off
Off
MetasysN2CrestDeg
_
C
Off
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
MetasysN2CopperFinIIDeg
_
C On On On On Off Off Off Off Off Off Off Off
MetasysN2PowerFinDeg
_
C Off Off Off Off On Off Off Off Off Off Off Off
MetasysN2F
T
XLDeg
_
C On Off Off Off On Off Off Off Off Off Off Off
MetasysN2SYNCDeg
_
F Off On Off Off On Off Off Off Off Off Off Off
MetasysN2Knight/KnightXL/Armor/Wall
Mount/WallHungDeg_F
On On Off Off On Off Off Off Off Off Off Off
MetasysN2CrestDeg
_
F
Off
Off
On
Off
On
Off
Off
Off
Off
Off
Off
Off
MetasysN2CopperFinIIDeg
_
F
On
Off
On
Off
On
Off
Off
Off
Off
Off
Off
Off
MetasysN2PowerFinDeg
_
F
Off
On
On
Off
On
Off
Off
Off
Off
Off
Off
Off
MetasysN2F
T
XLDeg
_
F
On
On
On
Off
On
Off
Off
Off
Off
Off
Off
Off
Tosetselecttheseconfigurations,opentheProtoNodeandselecttheAbankofswitches(A1orA2orA3)
onthesmallProtoCessormodulethatsitsontopoftheProtoCarrier(insidetheProtoNode).
ProtoCessorA1DIPswitchstartsonthebottomoftheAbankof
DIPswitchesbelow.
ProtoCessorA3A8DIPswitchesaredisabled.
A1andA2DIPSwitches
SBankDIPSwitches
Figure5:LocationforProtoCessorsmallABankofDIPswitches
NOTE:WhensettingDIPSwitches,pleaseensurethatpowertotheboardisOFF.
INS70085LochinvarProtoNodeStartupGuide Page11 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
2.3.
1.2
LonWork
s
DI
P
S
wit
ch
S
etti
ngs
Thefollo wingchartdescribestheDIPswitchsettingstosupportLonWorksonaProtoNodeFPCN35.
Profile‐FPCN351034010615
S0
S1
S2

S3

LonWorksSYNC
Off
Off
Off
Off
LonWorksKnight/KnightXL/Armor/Wall Mount/Wall Hung
On
Off
Off
Off
LonWorksCrest
Off
On
Off
Off
LonWorksCopperFinII
On
On
Off
Off
LonWorksPowerFin
Off
Off
On
Off
LonWorksF
T
XL
On
Off
On
Off
NOTE:WhensettingDIPSwitches,pleaseensurethatpowertotheboardis
OFF.
2.3.2 BACnet MS/TP (FPC‐ N34): Setting the MAC Address BACnet Networks
Only1MACaddressissetforProtoNoderegardlessofhowmanydevicesareconnectedto
ProtoNode.
SettheBACnetMS/TPMACaddressesof theProtoNodetoavalue between1 to127(MACMaster
Addresses);thisissothattheBMSFrontEndcanfindtheProtoNodeviaBACnetauto
discovery.
Note: Never set a BACnet MS/TP MAC Addressfrom 128 to 255. Addresses from 128 to 255 are
SlaveAddressesandcannotbediscoveredbyBMSFrontEndsthatsupportautodiscoveryofBACnet
MS/TPdevices.
SetDIPswitchesA0A7toassignMACAddressforBACnetMS/TPfortheProtoNodeFPCN34.
PleaserefertoAppendixC.1forthecompleterangeofMACAddressesandDIPswitchsettings.
Figure6:MACAddressDIP
Swi
tc
h
e
s
NOTE:WhensettingDIPSwitches,pleaseensurethatpowertotheboardisOFF.
INS70085LochinvarProtoNodeStartupGuide Page12 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
2.3.3 BACnet MS/TP and BACnet/IP (FPC‐ N34): Setting the Device Instance
TheABankofDIPswitchesarealsousedtosettheBACnetDeviceInstances.
TheBACnetDeviceInstancecanrangefrom1to4,194,303.
The BACnet device instances will be calculated by taking the Node_Offset(default is 50,000) found in
WebConfigurator (Section 2.3.2.1) andadding ittothevalueoftheABankDIPswitches (MAC
address).Whenmore than onedeviceisconnectedto the ProtoNode,thesubsequentBACnetDevice
Instancenumbers
willbesequentialfromthefirst/previousdevice.
Forexample:
Giventhat: DeviceInstance=Node_Offset+MACaddress
o DefaultNode_O ffsetvalue=50,000
o ABankDIPswitch(MACaddress)=11
ThentheDeviceInstancevaluesforthedevicesare:
o TheDeviceInstance=50,011
2.3.
3.1
BACn
et
MS/
TP or
B
ACn
et/I
P:
A
ssign
ing
Sp
ec
ific
D
evi
c
e
In
stanc
es
WiththedefaultNode_Offsetvalueof50,000theDeviceInstancesvaluesgeneratedwillbewithinthe
rangeof50,000to50,127.
ThevaluesallowedforaBACnetDeviceInstancecan rangefrom1to4,194,303.
ToassignaspecificDeviceInstance(orrange),changetheNode_Offsetvalue.
MethodsforchangingtheNode_OffsetvalueareprovidedinSection4.2
o Thisstepcannotbeperformeduntilaftertheunitisconnectedandpowered.
2.3.4 Metasys N2 and Modbus TCP/IP (FPC ‐ N34): Setting the Node‐ ID
SetDIP switchesA0 A7to assign NodeID for MetasysN2and ModbusTCP/IP for the ProtoNode
FPCN34.
Metasys N2 and Modbus TCP/IP NodeID Addressing:Metasys N2 and Modbus TCP/IP NodeID’s
rangefrom1255
PleaserefertoAppendixC.1forthefullrangeofaddressesforsettingNodeID.
INS70085LochinvarProtoNodeStartupGuide Page13 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
2.3.5 BACnet MS/TP (FPC‐ N34): Setting the Serial Baud Rate (DIP Switch B0 B3)
DIPSwitchesB0B3canbeusedtosettheserialbaudratetomatchthebaudrateprovidedbythe
BuildingManagementSystemforBACnetMS/TP.
DIPSwitchesB0B3aredisabledonProtoNodeFPCN35(FPCN35LonWorks).
The baudrate on ProtoNodefor MetasysN2 is set for 9600.DIP SwitchesB0 B3are disabledfor
MetasysN2onProtoNodeFPCN34.
B0 B1 B2 B3
Figure7:BaudRateDIP
Swit
c
h
e
s
NOTE:WhensettingDIPSwitches,pleaseensurethatpowertotheboardisOFF.
2.3.
5.1 Baud
Rat
e
DI
P
S
wit
ch
S
el
ection
Baud B0 B1 B2 B3
9600 On On On Off
19200 Off Off Off On
38400 On On Off On
57600 Off Off On On
76800 On Off On On
Figure8:BaudRate
INS70085LochinvarProtoNodeStartupGuide Page14 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
3 INTERFACING PROTONO DE TO DEVICES
3.1 ProtoNode FPC‐ N34 and FPC‐
N35 Showing Connection Ports
Figure9:ProtoNodeBACnetFPCN34(upper)andProtoNodeFPCN35(lower)
INS70085LochinvarProtoNodeStartupGuide Page15 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
3.2 Device Connections to ProtoNode
ProtoNode6PinPhoenixconnectorforRS485Devices
The6pinPhoenixconnectoristhesameforProtoNodeFPCN34(BACnet)andFPCN35(LonWorks).
Pins1through3areforModbusRS485devices.
o TheRS485GND(Pin3)isnottypicallyconnected.
Pins4through6 areforpower. Donotconnectpower(waituntilSection3.5.
DevicePins ProtoNodePin# Pinassignment
PinRS485+
Pin
1
RS485 +
PinRS485‐
Pin
2
RS485
PinGND
Pin
3
RS485 GND
PowerIn(+)
Pin
4
V
+
PowerIn() Pin
5
V
FrameGround Pin
6
FRAME GND
Figure10:PowerandRS485Connections
INS70085LochinvarProtoNodeStartupGuide Page16 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
3.2.1 End of Line Termination Switch for the Modbus RS‐ 485 port on the ProtoNode
OnlongRS485cablingruns,theRS485trunkmustbeproperlyterminatedateachend.
TheProtoNodehasanEndOfLine(EOL)bluejumper. ThedefaultsettingforthisBlueEOLswitchis
OFFwiththejumperstradd lingthepinsclosesttotheinsideoftheboardoftheProtoNode.
o OnshortcablingrunstheEOLswitchdoesnottoneedtobeturnedON.
IftheProtoNodeisplacedatoneoftheendsofthetrunk,settheblueEOLjumpertotheONposition
straddlingthepinsclosesttotheoutsideoftheboardoftheProtoNode.
AlwaysleavethesingleRedJumperintheAposition(defaultfactorysetting).
ModbusRS485EOL
Switch
LeaveinA
Position
Figure11:ModbusRS485EndOfLineTerminationSwitchontheProtoNodeN34(left)
and
ProtoNodeN35
(
r
i
g
ht)
INS70085LochinvarProtoNodeStartupGuide Page17 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
3.2.2 Lochinv ars Armor, SYNC/Armor X2, Knight/Knight XL, Crest, Copper‐Fin II and FTXL
Low Voltage Modbus RTU Connect
ion Wiring to the ProtoNode:
OntheLochinvar’sModbusterminalstrip,connectPinA(RS485+)toB+(RS485+)ontheProtoNode’s6
PinPhoenixconnector.
OntheLochinvar’sModbusterminalstrip,connectPinB(RS485)toA‐ (RS485)ontheProtoNode’s6
pinPhoenixconnector.
The
ShieldPintheterminalstripwhichisGroundonthedoesnotneedtobegroundedtotheProtoNode.
Figure12:LowVoltageModbusRTUConnectionWiringtotheProtoNode
INS70085LochinvarProtoNodeStartupGuide Page18 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
BMS
RS485
Wiring
ProtoNode
Pin
#
Pin
Assignment
RS485+
Pin
1
RS485 +
RS485‐
Pin
2
RS485
Pin
3
RS485 GND
+
3.3 BACnet MS/TP or Metasys N2 (FPC‐ N34): Wiring Field Port to RS‐ 485 Network
Connect the BACnet MS/TP or Metasys N2 RS485 network wires to the 3pin RS485 connector on
ProtoNodeFPCN34asshownbelowinError!Referencesourcenotfound..
o TheRS485GND(Pin3)isnottypicallyconnected.
SeeSection4forinformationonconnectingtoBACnet/IPnetwork.
IftheProtoNodeisthelastdeviceontheBACnetMS/TPorMetasysN2trunk,thentheEndOf‐
LineTerminationSwitchneedstobeenabled(Figure14).
o ThedefaultsettingfromthefactoryisOFF(switchposition=rightside).
o ToenabletheEOLTermination,turntheEOLswitchON(switchposition=leftside).
G
Figure13:ConnectionfromProtoNodetoRS485FieldNetwork
EndofLineSwitch
Figure14:RS485EOL
Swi
tc
h
INS70085LochinvarProtoNodeStartupGuide Page19 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
3.4 LonWorks (FPC‐ N35): Wiring Field Por t to LonWo rks Network
ConnectProtoNodetothefieldnetworkwiththeLonWorksterminalusingatwistedpairnonshielded
cable.LonWorkshasnopolarity.
Figure15:LonWorksTermi
nal
INS70085LochinvarProtoNodeStartupGuide Page20 o
f
48
ProtoCessor1991TarobCourtMilpitas, California 95035 USA Web:
www.ProtoCessor.com
Email:
Support@ProtoCessor.com
3.5 Connectin g P ower to ProtoNode
Applypowerto ProtoNodeasshowbelowin Figure17. Ensurethatthepowersupplyusedcomplieswith
thespecificationsprovidedinAppendixD.1.
ProtoNodeacceptseither930VDCor1224VAConpins4and5.
PowerRequirementforProtoNodeat9Vthrou gh30VDCor1224VAC
CurrentDrawType
ProtoNodeFamily 12VDC/VAC 24VDC/VAC 30VDC
FPCN34(Typical) 170mA 100mA 80mA
FPCN34(Maximum) 240mA 140mA 100mA
FPCN35(Typical) 210mA 100mA 90mA
FPCN35(Maximum) 250mA 130mA 100mA
Note:Thesevaluesare‘nominal’ andasafetymarginshouldbeaddedtothepowersupplyofthehostsystem.A
safetymarginof25%isrecommended.
Figure16: RequiredcurrentdrawfortheProtoNode
Powerto
ProtoNode
ProtoNode
Pin
#
Pin
Assignment
PowerIn(+) Pin
4
V
+
PowerIn() Pin
5
V
FrameGround Pin
6
FRAME GND
Figure17:PowerC
onn
ec
tions
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48