Siemens LMV51.140C1, LMV 5 Series, LMV51.040C1, LMV52.240B1, LMV52.440B1 Technical Instructions

  • Hello! I am an AI chatbot trained to assist you with the Siemens LMV51.140C1 Technical Instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Combustion Controls
Global Siemens Headquarters
Siemens AG
Berliner Ring 23
76437 Rastatt
Germany
SCC, Inc.
1250 Lunt Avenue
Elk Grove Village, IL 60007
USA
Telephone: 1-224-366-8445
www.scccombustion.com
Printed in USA
© Siemens Industry, Inc. • (05/2015)
LMV5...
Linkageless Burner
Management System
Technical Instructions November 21, 2016
IntentionallyLeftBlank
Section 1 Overview
Section 2 Wiring
Section 3 Parameters
Section 4 Commissioning
Section 5 VSD
Section 6 O
2
Trim
Section 7 Troubleshooting
Section 8 Modbus
Section 9 ACS450
Section 10 Revision History
Appendix A Application Guide
Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
GP 2 FUEL TRAIN
ERROR CODES
Section 1 Overview
Section 2 Wiring
Section 3 Parameters
Section 4 Commissioning
Section 5 VSD
Section 6 O
2
Trim
Section 7 Troubleshooting
Section 8 Modbus
Section 9 ACS450
Section 10 Revision History
Appendix A Application Guide
Appendix B* Complimentary
Products Guide
*Can be found at www.scccombustion.com.
GP 2 FUEL TRAIN
ERROR CODES
LMV Series Technical Instructions
Document No. LV5-1000
SCC Inc. Page 1 Section 1
1-1: Introduction
The LMV5 Burner / Boiler Management System (BMS) is ideally suited for use with steam
boilers, hot water boilers, thermal fluid heaters, and industrial burners. The LMV5 is extremely
flexible, and encompasses the following features:
Flame safeguard (independent processor)
Fuel-air ratio control
Load control / full PID control for pressure or temperature
Integrated O
2
trim
Variable Frequen
cy Drive (VFD) control
Fuel usage monitoring
Efficiency monitoring
Simultaneous operation of up to 5 rotary actuators (up to 6 connected)
Dual setpoints
Modbus communication
Remote setpoint or remote firing rate from building automation or external controller
Flue gas recirculation hold functions (LMV52)
Thermal shock protection
Valve proving / valve leak testing
Dual flame scanner options
Figure 1-1.1: The Main Components of an LMV5 System
HOME
Technical Instructions LMV Series
Document No. LV5-1000
Section 1 Page 2 SCC Inc.
1-2: LMV5 System Builder
The LMV5 Linkageless Burner Management System is comprised of many components in
addition to the LMV5 itself. Use the following pages to choose the components needed for
your specific application. See pages 20-22 for an LMV5 system order sheet. For additional
technical information about any of the products listed, refer to Appendix B.
Control Panel Components
Base Unit – Qty (1) Required
Choose one of the following LMV5 options. See page 24 for mounting information.
LMV51.040C1
Dual fuel burner control with electronic fuel-air ratio
control of up to 3 actuators (4 connected). Requires
an external PID controller
LMV51.140C1
Same features as LMV51.040C1. Includes a PID load
controller capable of temperature and / or pressure
control and a programmable analog output
LMV52.240B1
Same features as LMV51.140C1 for up to 5 actuators
(6 connected). Includes a closed loop VFD control,
integrated O
2
trim, fuel meter reading (gas and oil),
and temperature / time based FGR hold
LMV52.440B1
Same features as LMV52.240B1 as well as enhanced
O
2
trim control designed for low NO
x
mesh-style
pre-mix burners and high percentage FGR (>25%)
applications
Transformer – Qty (1) or (2) Required
At least one transformer is required per LMV5. A second transformer may be necessary
depending on the size and number of actuators present in the system (see Section 2 – Wiring).
Refer to page 26 of this section for mounting information.
AGG5.210
120 VAC to 12 VAC transformer (three secondaries)
HOME
LMV Series Technical Instructions
Document No. LV5-10
00
SCC Inc. Page 3 Section 1
Control Panel Components (continued)
Display – Qty (1) Required
Each LMV5 must be equipped wit
h one AZL52.40B1 display. See page 25 for mounting
information and panel cutout dimensions.
AZL52.40B1
Display with Modbus port, PC
port, backlight, six
languages available
Display Cable – Qty (1) Required
Each LMV5 must be equipped wit
h a cable to connect the AZL52 display to the LMV5.
AGG5.635
Pre-made 9 foot cable for conn
ecting the AZL52
display to the LMV5
Base Plug Set – Qty (1) Required
The terminal plug sets for the LMV5 are s
old separately. Each LMV5 needs one base plug set.
Additional plug sets are available (see “Control Panel Spare Parts”).
AGG5.720
Plug set containing all terminals for a typical LMV5
system. Will accommodate a system with O
2
trim,
three actuators, one transformer, and no fuel meters
AGG5.7COMPLETE
Plug set containing all te
rminals necessary for a
maximum LMV5 system. Will accommodate a
system with a VFD, O
2
trim, six actuators, two
transformers, and two fuel meters
Strain Relief – Qty (1) Required
A strain relief is required to ground the CANbus shield to th
e LMV5.
AGG5.110
Strain relief and actuator CANbus grounding
HOME
Technical Instructions LMV Series
Document No. LV5-100
0
Section 1 Page 4 SCC Inc.
Control Panel Components (continued)
Touchscreens – Optional
Touchscreen kits are available to provide a
human machine interface for the LMV5. Kits come
with a touchscreen and a plate kit with all necessary inputs and outputs. Standard
communication is via Modbus TCP/IP. Other communication types are available. For more
technical information about touchscreens, refer to Document No. TS-1000.
TS…
Touchscreen kits with 6” or 10” touchscreen,
power
supply, interconnect terminals, and optional PLC
LMV5 Mounting Brackets – Qty (2) Recommended But
Not Required
Recommended brackets for mounting the L
MV5 in an electrical enclosure to offset the base
unit from the subpanel, allowing easy access to plugs. Two brackets are needed per LMV5.
BR-LMV5
Brackets for mounting an LMV5 in an el
ectrical
enclosure
Control Panel Spare Parts – Not Re
quired
The LMV5 has three replaceable fuses:
one main power fuse and two secondary CANbus fuses.
Each LMV5 comes with spares for each fuse. Additional spare fuses are available if necessary.
FUSE6.3A-SLOW
5 pack of LMV5 primary fuses - 6.3A, 250V,
5x20mm, slow blow, for 120 VAC power
FUSE4.0A-SLOW
5 pack of LMV5 secondary CANbus fuses –
4.0A,
250V, 5x20mm, slow blow, for 12 VAC power
HOME
LMV Series Technical Instructions
Document No. LV5-10
00
SCC Inc. Page 5 Section 1
Control Panel Components (continued)
Replacement green connectors are available if
necessary. 4-pin connectors are for terminals
X52, X71, and X72. 5-pin connectors are for terminals X60, X61, X62, X70, and on each actuator
and O
2
module. 6-pin connectors are for terminals X50, X51, and X73.
1840382(5)
5 pack of spare 4-pin green connectors
1840395(5)
5 pack of spare 5-pin green connect
ors
1840405(3)
3 pack of spare 6-pin green connect
ors
An extra set of transformer terminals
is required if using a second transformer.
AGG5.2PLUGS
Extra set of terminals for a second
transformer (PRI,
SEK1, SEK2)
An optional spark quencher is available t
o reduce voltage spikes typically caused by closing a
normally open vent valve.
XEB0471
Spark quencher for reducing voltage spikes
An optional converter is available to
allow communication between RS-485 devices and the
LMV5 which utilizes the RS-232 communication protocol.
TS-5X-KT
RS232 to RS485 DIN rail converter kit
HOME
Technical Instructions LMV Series
Document No. LV5-100
0
Section 1 Page 6 SCC Inc.
Air Damper Assembly
Actuator – Qty (1) Required
Choose one of the following actuato
rs for the air damper. For more information, refer to
Document No. N7814 (SQM4… actuators) or Document No. N7818 (SQM9… actuators). SQM9…
actuators are rated NEMA 4. Any SQM4… actuator can be made NEMA 4 by adding the correct
NEMA 4 kit. See the “Actuator Accessories” section for more information.
SQM45.295B9 27 in-lb torque, 10mm “D” shaft, 10-120 seconds
SQM48.497B9 177 in-lb torque, 14mm keyed sha
ft, 30-120 seconds
SQM48.697B9 310 in-lb torque, 14mm keyed sha
ft, 60-120 seconds
SQM91.391A9 600 in-lb torque, 25mm keyed sha
ft, 30-120 seconds
Coupling – Qty (1) Required (Provided With S
ome Mounting Brackets – See Below)
Zero-lash, flexible couplings are available f
or each actuator. For more information, refer to
Document No. CPBK-1000.
CCM10DCA… Flexible couplings for SQM45… actuators
CFM14KCB… Flexible couplings for SQM48… actuators
CJM25KCA… Flexible couplings for SQM91… actuators
HOME
LMV Series Technical Instructions
Document No. LV5-10
00
SCC Inc. Page 7 Section 1
Air Damper Assembly (continued)
Mounting Bracket Kits - Optional
Modular bracket kits are available to assist i
n mounting any SQM… actuator to a variety of
valves or air dampers. A coupling is necessary when using a modular bracket kit. For more
information, refer to Document No. CPBK-2000.
BR-AS…
Modular bracket kits for mounting SQM… ac
tuators
to a variety of valves or dampers
When retrofitting a Cleaver Brooks boiler,
the following kits are available for the rotary air
damper. No additional couplings are needed with these retrofit kits. Refer to Document No.
CPBK-4000 for technical information or Document No. CPBK-4100 for installation instructions.
BR-48CBAIR
Bracket for mounting an SQM48… actuator to a
Cleaver Brooks rotary air damper
BR-3345CBAIR
Bracket for mounting an SQM45… actuator
to a
Cleaver Brooks rotary air damper
When using a Lucoma air damper, the f
ollowing actuator mounting kits are available. No
additional couplings are needed with these mounting kits. Refer to Document No. CPBK-3000
for technical information or Document No. CPBK-3100 for installation instructions.
BR-SQM48-LUC
Bracket for mounting an SQM48… actuator
to an
8x8 through 28x28 Lucoma air damper
BR-SQM3345-
LUC
Bracket for mounting an SQM45… actua
tor to an
8x8 through 28x28 Lucoma air damper
HOME
Technical Instructions LMV Series
Document No. LV5-1000
Section 1 Page 8 SCC Inc.
Gas Firing Rate Control Valve
Valve Actuator Assemblies – Qty (1) Required if Firing Gas
Pre-built valve actuator assemblies are available that mount an SQM45… actuator to a VKG…
gas butterfly valve. A variety of VKG… valves are available from 1/2” to 4”. For more
information about VKG… valves, refer to Document No. CVLV-2000. For more information
about valve actuator assemblies using VKG… valves, refer to Document No. VA-1000.
VA45.2-NF-050
SQM45 to
1/2” full port firing rate valve
VA45.2-NF-075
SQM45 to 3/4” full port firing rate valve
VA45.2-NF-100
SQM45 to 1” full port firing rate valve
VA45.2-NM-100
SQM45 to 1” medium port firing rate valve
VA45.2-NF-125
SQM45 to 1-1/4” full port firing rate valve
VA45.2-NM-125
SQM45 to 1-1/4” medium port firing rate valve
VA45.2-NF-150
SQM45 to 1-1/2” full port firing rate valve
VA45.2-NM-150
SQM45 to 1-1/2” medium port firing rate valve
VA45.2-NR-150
SQM45 to 1-1/2” reduced port firing rate valve
VA45.2-NF-200
SQM45 to 2” full port firing rate valve
VA45.2-NM-200
SQM45 to 2” medium port firing rate valve
VA45.2-NR-200
SQM45 to 2” reduced port firing rate valve
VA45.2-NF-250
SQM45 to 2-1/2” full port firing rate valve
VA45.2-NM-250
SQM45 to 2-1/2” medium port firing rate valve
VA45.2-NR-250
SQM45 to 2-1/2” reduced port firing rate valve
VA45.2-NF-300
SQM45 to 3” full port firing rate valve
VA45.2-NM-300
SQM45 to 3” medium port firing rate valve
VA45.2-NR-300
SQM45 to 3” reduced port firing rate valve
VA45.2-NF-400
SQM45 to 4” full port firing rate valve
VA45.2-NM-400
SQM45 to 4” medium port firing rate valve
VA45.2-NR-400
SQM45 to 4” reduced port firing rate valve
HOME
LMV Series Technical Instructions
Document No. LV5-10
00
SCC Inc. Page 9 Section 1
Gas Firing Rate Control Valve (continued)
Pre-built valve actuator assemblies are availa
ble that mount an SQM45… or SQM48… actuator
to a VKF… gas butterfly valve. A variety of VKF… valves are available from 1-1/2” to 8”. The
most common assemblies are listed below. For more information about VKF… valves, refer to
Document No. CVLV-1000. For more information about valve actuator assemblies using VKF…
valves, refer to Document No. VA-3000.
VA45.2-3.0VKF
SQM45 to 3” VKF butterfly valve
VA45.2-4.0VKF
SQM45 to 4” VKF butterfly valve
VA45.2-6.0VKF
SQM45 to 6” VKF butterfly valve
Oil Firing Rate Control Valve
Valve Actuator Assemblies – Qty (1) Required if
Firing Oil (Not Using a Cleaver Brooks Oil Valve)
Pre-built valve actuator assemblies are availa
ble to mount an SQM45… or SQM48… actuator to
a Hauck S, AS, B, F, G, or K series oil valve. For more information about valve actuator
assemblies using Hauck oil valves, refer to Document No. VA-4000.
VA…
Valve actuator assemblies mounting an SQM4
5… or
SQM48… actuator to a Hauck oil valve
Cleaver Brooks Oil Valve Retrofit Kit - Optional
When retrofitting a Cleaver Brooks boiler,
the following kits are available for the oil metering
valve. Refer to Document No. CPBK-5000 for technical information or Document No. CPBK-
5100 for installation instructions.
BR-48CBOIL
Bracket for mounting an SQM48… actuator to a
Cleaver Brooks oil metering valve
BR-45CBOIL
Bracket for mounting an SQM45… actuator
to a
Cleaver Brooks oil metering valve
HOME
Technical Instructions LMV Series
Document No. LV5-1000
Section 1 Page 10 SCC Inc.
FGR Control Valve
Valve Actuator Assemblies – Qty (1) Required if Using FGR
Pre-built FGR valve actuator assemblies are available to mount an SQM45… or SQM48…
actuator to a high-temperature VKF… butterfly valve. The most commonly used assemblies are
listed below. For a list of all assembly options, see Document No. VA-3000. For more
information on VKF valves, refer to Document No. CVLV-1000. Contact SCC if an FGR valve
actuator assembly larger than 8” is required.
VA48.4-3.0VKF-HT
SQM48 to 3” high-temp VKF valve assembly
VA48.4-4.0VKF-HT
SQM48 to 4” high-temp VKF valve assembly
VA48.4-6.0VKF-HT
SQM48 to 6” high-temp VKF valve assembly
VA48.4-8.0VKF-HT
SQM48 to 8” high-temp VKF valve assembly
Actuator Accessories
CANbus Cable – Qty (1) Required
Special cable is used to connect the actuators and O
2
module to the LMV5. This cable may be
purchased in 100’ or 500’ rolls.
AGG5.643(100) 100’ roll of CA
Nbus cable
AGG5.643 500’ roll of CANbus cable
Electrical Cable Cord Grips and Conduit Adapters – Qty (2) Required Per Actuator
SQM45…, SQM48…, and SQM91… actuators come with two M16 threaded electrical
connections. Various adapters are available to convert these connections to an English thread.
One short and one long adapter are recommended per actuator to offset conduit connections.
ADP-
M16XE500(5)
5-pack of short M16 to 1/2” NPSM metal conduit
adapters, compatible with liquid tight or EMT fittings
ADP-M16XE500-
LONG(5)
5 pack of long M16 to 1/2” NPSM metal conduit
adapters, compatible with liquid tight or EMT fittings
7466201040
M16 to 1/2” NPSM nylon conduit adapter,
compatible with liquid tight or EMT conduit fittings
7466200470
M16 nylon cord grip
HOME
LMV Series Technical Instructions
Document No. LV5-10
00
SCC Inc. Page 11 Section 1
Actuator Accessories (continued)
NEMA 4 Kits – Optional
A kit can be added to any SQM4… act
uator in order to provide NEMA 4 protection.
BR-N4-SQM45 NEMA 4 kit for an SQM45… actuator
BR-N4-SQM48 NEMA 4 kit for an SQM48… actuator
Explosion Proof Housing – Optional
An explosion proof housing is available
for the SQM48.697B9 actuator.
LMV5-XPR-
SQM48
Explosion proof housing for an SQM
48.697B9
actuator
Flame Scanners
Infrared Flame Scanners – Qty (1) Required Unl
ess Using a QRA75.A17 Flame Scanner
Two infrared flame scanners are available: o
ne side viewing and one forward viewing. For
technical information about QRI… flame scanners, refer to Document No. N7719.
QRI2A2.B180B
Self-check infrared flame scanner, forward viewin
g
QRI2B2.B180B
Self-check infrared flame scanner, side viewing
Ultraviolet Flame Scanners – Qty (1) Required Unl
ess Using a QRI… Flame Scanner
One ultraviolet flame scanner is available for
use with the LMV5. For technical information
about the QRA75… flame scanner, refer to Document No. N7712.
QRA75.A17
Self-check ultraviolet flame scanner, side viewing,
supplied with mounting clamp
HOME
Technical Instructions LMV Series
Document No. LV5-100
0
Section 1 Page 12 SCC Inc.
Flame Scanner Accessories
QRA75 Wiring Cable – Qty (1) Required per QRA75.A17 Flame Scan
ner
A pre-made 12 foot cable is requir
ed when using the QRA75 flame scanner. For more
information, refer to Document No. N7712.
AGM23U
Pre-made 12 foot cable for use
with the QRA75…
flame scanner, supplied with 1/2” NPSM conduit
adapter.
QRI… Accessories - Optional
Mounting accessories are available for bot
h the forward viewing and side viewing QRI… flame
scanners. For more information, refer to Document No. N7719.
AGG2.110
Kit for mounting forward viewing scanner
QRI2A2.B180B on a flame tube. Comes with clamp,
mounting sleeve, thermal barrier with 3/4” NPSM
connection, and heat insulation glass
AGG2.120
Pg9 thread to 1/2” NPSM con
duit connection
adapter for use with any QRI… flame scanner
AGG90.U
Right angle adapter for mounting
side viewing
scanner QRI2B2.B180B on a flame tube. Comes
with 3/4” NPSM female thread connection
LMV5-XPR-QRI
Explosion proof housing for any QRI… flame
scanner
HOME
LMV Series Technical Instructions
Document No. LV5-10
00
SCC Inc. Page 13 Section 1
Flame Scanner Accessories (continued)
QRA75… Accessories - Optional
Mounting accessories are available for the
QRA75… flame scanner. For more information, refer
to Document No. N7712.
AGG16.U
Right angle adapter for mounting
a QRA75 flame
scanner. Comes with a 1” NPSM female thread
connection
THERMAL-1X75
Thermal barrier for use with t
he QRA75 flame
scanner along with accessory AGG16.U. Adapts a 1”
NPSM thread to a female 3/4” NPT connection
AGG02
Heat insulating glass with spring washer
and O-ring,
for applications where the temperature at the
scanner will exceed 176 °F, to be mounted inside
thermal barrier THERMAL-1X75
AGG03
Magnifying lens with spring washer
and O-ring for
increased sensitivity, to be mounted inside thermal
barrier THERMAL-1X75
HOME
Technical Instructions LMV Series
Document No. LV5-100
0
Section 1 Page 14 SCC Inc.
Sensors
Pressure Sensors – Qty (1) Required for St
eam Boilers
A wide range of pressure sensors is available
for steam boilers. All sensors have a 1/4” NPT
process connection and a 1/2” NPT conduit connection. Sensors are available with either a 4-
20 mA or 0-10 Vdc output signal. All available 4-20 mA sensors are listed below. To order a 0-
10 Vdc sensor, change the underlined digit to a 1. The 0-100 PSI sensor is only available with a
4-20 mA signal. For more information on 7MF pressure sensors, refer to Document No. SEN-
2000.
7MF1565-4BB00-5EA1
0-15 PSI range, 4-20 mA signal
7MF1565-4BE00-5EA1
0-30 PSI range, 4-20 mA signal
7MF1565-4BF00-5EA1
0-60 PSI range, 4-20 mA signal
7MF1565-4BG00-5EA1
0-100 PSI range, 4-20 mA signal
7MF1565-4CA00-5EA1
0-150 PSI range, 4-20 mA signal
7MF1565-4CB00-5EA1
0-200 PSI range, 4-20 mA signal
7MF1565-4CD00-5EA1
0-300 PSI range, 4-20 mA signal
7MF1565-4CE00-5EA1
0-500 PSI range, 4-20 mA signal
7MF1565-4CF00-5EA1
0-750 PSI range, 4-20 mA signal
HOME
LMV Series Technical Instructions
Document No. LV5-10
00
SCC Inc. Page 15 Section 1
Sensors (continued)
Temperature Sensors – Qty (1) Required for
Hot Water Boilers, Optional for Other Applications
One temperature sensor is needed
to measure water temperature on hot water boilers.
Additionally, one may be needed for low fire hold on a steam boiler, hot standby on a steam
boiler, or ambient and stack temperatures for efficiency calculations or FGR hold features. The
most commonly used temperature sensors are listed below. For a list of all temperature sensor
options as well as technical instructions for all available temperature sensors, refer to
Document No. SEN-1000.
QAE2020.001
100 Ohm, 3-wire, platinum RTD used t
o measure
water temperature on hot water boilers
Range: -4 to 374 °F
QAE2012.001
1000 Ohm, 2-wire, platin
um RTD used to measure
water temperature for low fire hold or hot standby
on steam boilers. Also recommended to measure
ambient air temperature for LMV52.4 applications
Range: -4 to 374 °F
QAE2012.9002
1000 Ohm, 2-wire, pla
tinum RTD used to measure
water temperature on hot oil heaters and steam
boilers operating over 150 PSI
Range: -50 to 900 °F
QAC22
1000 Ohm, 2-wire, nickel RTD used to
measure
ambient air temperature (required for efficiency
calculations)
Range: -58 to 158 °F
QAM-P210
1000 Ohm, 2-wire, platinum RTD use
d to measure
flue gas temperature (required for efficiency
calculations and FGR low temperature hold features)
Range: -50 to 900 °F
HOME
Technical Instructions LMV Series
Document No. LV5-100
0
Section 1 Page 16 SCC Inc.
Variable Frequency Drive (VFD) Components
Variable Frequency Drives (VFDs) - Optional
Pre-programmed Variable Frequency Drives
(VFDs) are available for use with an LMV52.
Braking resistors and line / load reactors are available as accessories.
DR…
Pre-programmed VFDs with LMV52 programmi
ng
and wiring instructions
Speed Sensor Mounting Kit – Qty (1) Req
uired per VFD
Because the LMV52 requires speed fee
dback when using a VFD, one of the following speed
sensor kits is required if a VFD is present.
AGG5.305
Speed sensor and associated mounting kit with
connections available for mounting directly to ½” or
¾” conduit. Includes speed sensor, 6 foot cable, 3-
finger speed wheel, O-ring for a watertight seal, and
necessary mounting hardware
Range: 300-6300 RPM
AGG5.310
Speed sensor and associated mounting kit.
Includes
speed sensor, 6 foot cable, 3-finger speed wheel,
and necessary mounting hardware
Range: 300-6300 RPM
Explosion Proof Housing – Optional
An explosion proof housing is available
for speed sensor kit AGG5.310.
LMV5-XPR-SS
Explosion proof housing for speed sensor kit
AGG5.310