Daikin IM 1316 Outside Airflow Sensor Kit precisely measures and transmits outside airflow in cubic feet per minute (CFM) for use with Daikin unit controllers. It features a compact airflow sensor probe with a direct-mount design for easy installation and maintenance. The sensor enclosure protects the components from harsh environments, and the included conduit bushing provides a secure connection to the controller. With its accurate and reliable performance, the Daikin IM 1316 is an ideal solution for monitoring and controlling outside airflow in various applications.

Daikin IM 1316 Outside Airflow Sensor Kit precisely measures and transmits outside airflow in cubic feet per minute (CFM) for use with Daikin unit controllers. It features a compact airflow sensor probe with a direct-mount design for easy installation and maintenance. The sensor enclosure protects the components from harsh environments, and the included conduit bushing provides a secure connection to the controller. With its accurate and reliable performance, the Daikin IM 1316 is an ideal solution for monitoring and controlling outside airflow in various applications.

CFM Monitor/Transmitter
Airflow Collection Tubes
and Enclosure
Installation and Maintenance Manual IM 1316
Group: WSHP
Part Number: 910338145
Date: January 2021
Outside Airow Sensor Kit
Outside Airow Sensor Kit
Included Parts:
Outside Airflow Monitor/Transmitter
(2) Sensor Probes
(4) Probe Brackets
(1) Top and (1) Bottom Panel
(1) Left-Side Panel and (1) Right-Side Panel
Conduit Bushing
5-pin Male Molex plug with (1 each) 12” Red, Black, Green
wires (not shown)
• 3" long black wire (not shown)
(38) 3/8" #10 self-tapping screws
(6) Cable Ties (not shown)
(6) Wire Ties (not shown)
Figure 1: Kit Parts Assembly
Probe Brackets
(Hand Bend Before
Installation)
Sensor Probe (2)
Outside Airflow
Monitor/Transmitte
r
Conduit
Bushing
Bottom Enclosure Panel
Top Enclosure Panel
Left-Side
Enclosure Panel
" #10 Enclosure
Panel Screws (38)
Right-Side
Enclosure Panel
Installation
All wiring must comply with the National Electric Code
(NEC) and local codes. Do NOT run any of this device’s
wiring in the same conduit as other AC power wiring.
Tests show that uctuating and inaccurate signal levels
are possible when AC power wiring is present in the
same conduit as the signal lines. If you are experiencing
any of these difculties, please contact your Daikin
representative.
1. Remove all components from the packaging and
conrm all pieces have been received.
2. Assemble the sensor enclosure as show in Figure 1.
Note: Useeld-suppliedscrewstoattachsensorprobe
bracketstosensorprobes
3. Attach sensor assembly to lter inlet frame as shown
in Figure 2.
Figure 2: Attach Assembled Outside Airflow Kit to Filter
Inlet Frame
Bend Out Upper and
Lower Flanges
⅜" #10 Enclosure Mounting Screws
4. Attach sensor wires from Monitor/Transmitter to
sensor probe tubes as shown in Figure 3.
Figure 3: Attach and Route Wires from Sensor Probes
Brackets to Monitor/Transmitter
Route Sensor Wires
Through Knockout
Bushing and Connect to
Monitor/Transmitter
Factory Provided Screws (4)
to Attach Sensor Probe Brackets
IM 1316 Outside Air Sensor 2 www.DaikinApplied.com
5. Route wiring harness from mating CFM/IHS molex plug to the monitor/transmitter, (Figure 4).
Figure 4: Route Male Plug Wire Harness Wires to Monitor/Transmitter
A
Cable Ties Locations
Monitor/Transmitter
Molex Cable Wires
Detail A
Male
Molex Plug
(to CFM / IHS)
6. Connect the wires from the wire harness to the monitor/transmitter terminals as follows: Refer to Figure 5
Green wire (CFM11-GN) to the POWER 24VAC IN : L1 connection
Black wire (CFM12-BK) to the POWER 24VAC IN : L2 connection
Red wire (CFM13-RD) to the OUTPUT : 1 connection
Install the 3" black wire (CFMJP) between the POWER 24VAC IN: L2 and OUTPUT: COM connections
Figure 5: Connect Wire Harness Wires to Monitor/Transmitter Terminals
CAUTION HOT
GTx116 Main
ON
OFF
RETNECSE
PGM
CONTRAST
24VAC IN
L2 L1
OUTPUT
COM
POWER
REPLACE WITH
1.5 AMP
FAST ACTING ONLY
EBTRON INC.
400-1810 REV. J
U11
U10U9
J6
U4
D4
U1
C1
VR1
J4
L1
Z1
D2
D1
C5
HS2
HS1
VR2
C6
C4
C3
C2
R5
R4
R3
LCD1
R2
J1
F1 J2
J3
SW1
R1
EG1
R26
R25
R24
R23R22
R21
R20
R19
R18
R17
R16
R15
R14
R13
R12
R10
R11
U8U7
U3
U6
U24U23
U22U21
U20U19
U18U17
U16U15
U14U13
U12
R6
R59
R58
R57
R56R55R54R53R52R51R50R49
74R84R
54R64R
R44
R43
R42
R41
93R04R73R83R
R36
R35
R34
R33
R32
R31
92R03R
R28
R27
U5
U2
C9
C8
C12
C11
C7
C22
C21
C20
C19
C18
C17
C16
C15
C13
C10
C14
R9
R8
R72R71R70
R7
R69R68R67R66R65
36R46R
16R26R
R60
+
+
MH1
D3
C23
J7
J8
XTAL1
TP1
TP9TP8TP7TP6TP5TP4TP3TP2 TP17TP16TP14TP13TP12TP11 51PT01PT
SW5
SW4SW2 SW3
D1
D4 D3
C4
C3
C6
U2
MH1
U1
U3
R1
C5
C2
MH3
C1
EBTRON, INC.
400-1850 REV. E
GTL116 LOut
SERVICE
WINK
YEL
GRN
MH2
C15
C16
U6
C8
R7 R8
D6
SW1
R4
R10R9
R6
D7
D5
C7
J1
XFMR1
SG1 SG2
D2
1
10
1
+
+
1
U4
C11C10
C9
C14
C12
C13
XTAL1
U5
J2
R3R2
R5
1
64
33
32
1
1
10
1 2
TX LED Green
RX LED Green
Service LED Yellow
Service Button
Wink LED Green
Transmitter Status LED
Activity LED Red
LCD Display
Male Molex Plug
(to CFM / IHS)
Power
Switch
Monitor/Transmitter
CFMJP
CFM13-RD
CFM12-BK
CFM11-GN
www.DaikinApplied.com 3 IM 1316 Outside Air Sensor
Outside Airow Monitor/Transmitter
Conguration
1. Set the power switch to ON.
2. Set transmitter SW1 to VDC
3. Set transmitter to display in ACFM by selecting
SETUP > ANALOG OUT > *AO1 UM=AFPM
Change to AO1 UM = ACFM
Figure 6: Monitor/Transmitter Board
CAUTION HOT
GTx116 Main
ON
OFF
RETNECSE
PGM
CONTRAST
24VAC IN
L2 L1
OUTPUT
COM
POWER
REPLACE WITH
1.5 AMP
FAST ACTING ONLY
EBTRON INC.
400-1810 REV. J
U11
U10U9
J6
U4
D4
U1
C1
VR1
J4
L1
Z1
D2
D1
C5
HS2
HS1
VR2
C6
C4
C3
C2
R5
R4
R3
LCD1
R2
J1
F1 J2
J3
SW1
R1
EG1
R26
R25
R24
R23R22
R21
R20
R19
R18
R17
R16
R15
R14
R13
R12
R10
R11
U8U7
U3
U6
U24U23
U22U21
U20U19
U18U17
U16U15
U14U13
U12
R6
R59
R58
R57
R56R55R54R53R52R51R50R49
74R84R
54R64R
R44
R43
R42
R41
93R04R73R83R
R36
R35
R34
R33
R32
R31
92R03R
R28
R27
U5
U2
C9
C8
C12
C11
C7
C22
C21
C20
C19
C18
C17
C16
C15
C13
C10
C14
R9
R8
R72R71R70
R7
R69R68R67R66R65
36R46R
16R26R
R60
+
+
MH1
D3
C23
J7
J8
XTAL1
TP1
TP9TP8TP7TP6TP5TP4TP3TP2 TP17TP16TP14TP13TP12TP11 51PT01PT
SW5
SW4SW2 SW3
D1
D4 D3
C4
C3
C6
U2
MH1
U1
U3
R1
C5
C2
MH3
C1
EBTRON, INC.
400-1850 REV. E
GTL116 LOut
SERVICE
WINK
YEL
GRN
MH2
C15
C16
U6
C8
R7 R8
D6
SW1
R4
R10R9
R6
D7
D5
C7
J1
XFMR1
SG1 SG2
D2
1
10
1
+
+
1
U4
C11C10
C9
C14
C12
C13
XTAL1
U5
J2
R3R2
R5
1
64
33
32
1
1
10
1 2
TX LED-GRN
RX LED-GRN
Service LED-YEL
Service Button
Wink LED-GRN
Transmitter
Status LED
Activity LED Red
LCD Display
Power
Switch
Monitor/Transmitter
Programming
To enable use of this sensor the following congura-
tion point must be changed. Changes can be made
through the local user interface or through the Service
Tools software for Microtech® Unit Controllers program
on a connected PC. For information on how to use the
ServiceTools software, refer to OM 732. The local user
interface menu path is shown below.
To enable Outdoor Air Flow measuring go to
Service > Serv-AnaIn > Serv-AnaIn-Cong >
CFgAnIn16 and change the value from None to
OAFLOW. Then go to SET > Set-SensorInstall >
OAFlowSens and conrm that it is set to ‘Inst’.
If using the ServiceTools software, change the unit con-
guration as follows:
To enable Space Temperature sensing, go to the
‘Conguration’ menu and under the ‘Inputs’ drop
down change ‘Analog Input 16’ to ‘Outside Air
Flow’. Conrm that under the ‘Sensor Installation’
drop down, ‘Outside Air Flow’ is ‘Installed’.
Click the Save button after making changes so they
take effect. ServiceTools prompts you to save if you are
switching to another screen without saving.
IM 1316 ©2021 Daikin Applied (01/21) | (800) 432–1342 | www.DaikinApplied.com
Daikin Applied Training and Development
Now that you have made an investment in modern, efcient Daikin equipment, its care should be a high priority. For training information on all
Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Applied
representative for warranty details. Refer to Form 933-430285Y. To nd your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To nd your local parts ofce, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To nd your local service ofce, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.
DaikinApplied.com.
Products manufactured in an ISO Certied Facility.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Daikin IM 1316 User manual

Type
User manual

Daikin IM 1316 Outside Airflow Sensor Kit precisely measures and transmits outside airflow in cubic feet per minute (CFM) for use with Daikin unit controllers. It features a compact airflow sensor probe with a direct-mount design for easy installation and maintenance. The sensor enclosure protects the components from harsh environments, and the included conduit bushing provides a secure connection to the controller. With its accurate and reliable performance, the Daikin IM 1316 is an ideal solution for monitoring and controlling outside airflow in various applications.