Daikin IM 1314 is a high duct pressure limit switch designed to protect your HVAC system from excessive duct pressure. It features automatic enablement and factory programming for a normally open configuration. The unit can be reconfigured for a normally closed state through the local user interface or ServiceTools software. Additionally, the device can be used with a field-provided duct pressure tap to monitor downstream static pressure and initiate an immediate shutdown if the connected switch closes, indicating a high duct pressure fault.

Daikin IM 1314 is a high duct pressure limit switch designed to protect your HVAC system from excessive duct pressure. It features automatic enablement and factory programming for a normally open configuration. The unit can be reconfigured for a normally closed state through the local user interface or ServiceTools software. Additionally, the device can be used with a field-provided duct pressure tap to monitor downstream static pressure and initiate an immediate shutdown if the connected switch closes, indicating a high duct pressure fault.

Installation and Maintenance Manual IM 1314
Group: WSHP
Part Number: 910339000
Date: January 2021
High Duct Pressure Limit Switch
High Duct Pressure Limit Switch
Included Parts:
High Duct Limit Pressure Switch
(2) 120” Black Wires with connectors
Installation
• Locatetheeldprovidedductpressuretap
downstreamstaticpressure.
• Mountsensoronthesupplyductnearthelocation
selectedfortheductpressure.SeeFigure 2
• Connecttheeldprovidedtubebetweenthetapand
thehighpressure(H)portonthesensor.
• Runthewiresprovidedfromthesensorlocationto
theunit.
• RefertoFigure3andFigure4onpage3and
connecttherstwirefromtheNormallyOpenterminal
onthesensortopin13ontheunitterminalstrip.
ConnectthesecondwirefromtheCommonterminal
onthesensortopin26ontheunitterminalstrip.
Figure 1: Mounting Holes Locations
Figure 2: Sensing Tube Location
IM1314HighDuctPressureLimitSwitch 2 www.DaikinApplied.com
Figure 3: Unit Terminal Connections
A
Detail A
Figure 4: Unit Terminals to Switch Terminals
Terminal“NormallyOpen” Common
www.DaikinApplied.com 3 IM1314HighDuctPressureLimitSwitch
Programming:
ThisHighDuctPressureLimitisautomaticallyenabled
andthefactoryprogrammedforaNormallyOpencon-
guration.IftheconnectedswitchclosestheHighDuct
Limitfaultoccursandtheunitwillinitiateanimmediate
shutdown.TheinputcanbereconguredforaNormally
Closedstate.Changescanbemadethroughthelocal
userinterfaceorthroughtheServiceToolssoftwarefor
Microtech®UnitControllersprogramonaconnected
PC.ForinformationonhowtousetheServiceTools
software,refertoOM732.Thelocaluserinterfacemenu
pathisshownbelow.
• TochangethepolarityoftheDuctHighLimitSwitch
input,gotoService>Serv-BinIn>Serv-BinIn-Cong
>CfgRevBI4andchangethevaluefromReverseto
Direct.
IfusingtheServiceToolssoftwarechangetheunit
congurationasfollows:
• TochangethepolarityoftheDuctHighLimitSwitch
input,gotothe‘Conguration’menuandunderthe
‘Inputs’dropdownchange‘DI4Polarity’to‘Direct’.
ClicktheSavebuttonaftermakingchangessothey
takeeect.ServiceToolspromptsyoutosaveifyouare
switchingtoanotherscreenwithoutsaving.
IM 1314 ©2021 Daikin Applied (01/21) | (800) 432–1342 | www.DaikinApplied.com
Daikin Applied Training and Development
Now that you have made an investment in modern, ecient Daikin equipment, its care should be a high priority. For training information on all
Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Applied
representative for warranty details. Refer to Form 933-430285Y. To nd your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To nd your local parts oce, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To nd your local service oce, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.
DaikinApplied.com.
Products manufactured in an ISO Certied Facility.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Daikin IM 1314 User manual

Type
User manual

Daikin IM 1314 is a high duct pressure limit switch designed to protect your HVAC system from excessive duct pressure. It features automatic enablement and factory programming for a normally open configuration. The unit can be reconfigured for a normally closed state through the local user interface or ServiceTools software. Additionally, the device can be used with a field-provided duct pressure tap to monitor downstream static pressure and initiate an immediate shutdown if the connected switch closes, indicating a high duct pressure fault.