Leviton 78W47-C Installation guide

Type
Installation guide

Leviton 78W47-C:

This Wetguard connector is intended to be used with Wetguard inlets only. It has a NEMA and NON-NEMA IP66 Suitability and is rated to NEMA Type 4, 4X & 12 when mated with Leviton Wetguard Inlets. The device can be used in both grounded and non-grounded circuits; it's also UL Listed for replacement use only.

The 78W47-C connector is easy to install, and the instructions provided in the manual are clear and concise; they include diagrams and specific torque values for tightening screws. It's important to note that the device should be installed by a qualified electrician to ensure proper functionality and safety.

Leviton 78W47-C:

This Wetguard connector is intended to be used with Wetguard inlets only. It has a NEMA and NON-NEMA IP66 Suitability and is rated to NEMA Type 4, 4X & 12 when mated with Leviton Wetguard Inlets. The device can be used in both grounded and non-grounded circuits; it's also UL Listed for replacement use only.

The 78W47-C connector is easy to install, and the instructions provided in the manual are clear and concise; they include diagrams and specific torque values for tightening screws. It's important to note that the device should be installed by a qualified electrician to ensure proper functionality and safety.

Wetguard
®
Connectors
(For use with Wetguard
®
Inlets only)
NEMA & NON-NEMA
IP66 Suitability. Rated to NEMA Type 4, 4X & 12
when mated with Leviton Wetguard
®
Inlets
PK-93740-10-00-0A
WARNINGS AND CAUTIONS:
• Tobeinstalledand/orusedinaccordancewithappropriateelectricalcodesandregulations.
• Ifyouarenotsureaboutanypartoftheseinstructions,consultanelectrician.
• Usethisdevicewithstranded copper wire only.
• Non-grounded devices are for connection to non-grounded circuits only.
• Non-NEMAdevicesareULListedforreplacementuseonly.
WIRING INSTRUCTIONS
ENGLISH
TO INSTALL
NOTE:WIRESIZEANDTYPEMUSTCOMPLYWITHAPPROPRIATELOCALELECTRICALCODES.INUSAREFERTONECTABLESARTICLE400.
WARNING:TOAVOIDFIRE,SHOCKORDEATH;UNPLUG CORD OR TURN OFF POWER
ATCIRCUITBREAKERORFUSEANDTESTTHATPOWERISOFFBEFOREWIRING!
1.Selectsizeandtypeofroundcordasperyourrequirements.
2.ReferringtoFig. 1,removenut(1)fromrubberhousing(3).Separatewiringmodule(4)from
rubberhousingbypushingthemodulefrombackofhousingwithascrewdriver(orcord).
3.Selectpropersizeofstrainreliefwasher(10)andrubberbushing(9)peryourcordsizeasper
appropriate table below,orusethebackoftherubberbushingasagage.The washers and
bushings must be broken apart from each other before use (see Fig. 1).
4.Feedwiringcordthroughnut(1),strainreliefwasher(10),rubberbushing(9)andintothreaded
insertofhousing(3)asshowninFig. 1. DO NOT REVERSE ORIENTATION OF STRAIN
RELIEF WASHER AND RUBBER BUSHING.
5.Stripcordjacketandconductorsasperappropriatewire stripping gage, or as per strip gage
moldedonthebackofwiringcover.
6. Connect wires:Carefullybackoutallterminalwiringscrewsuntiledgeofbackwireclampis
notvisibleinwirewell.Twistthestrandsofeachstrippedconductortightlytogether,andinsert
intoproperwirewell.Tightenwiringscrewrmlyto12-14in.-Ibs.Torque.CHECK FOR STRAY
WIRE STRANDS. Repeat for all conductors. NOTE:Whereapplicableitisrecommendedto
connectGROUNDwirerst.
CAUTION: Wiring clamps MUST contact on conductor only, NOT on insulation.
DO NOT USE SOLID WIRE. DO NOT TIN CONDUCTORS.
7.Reattachthewiredmodule(4)tothehousing(3)byaligningkeyguide(8)onthemoduletothe
keyonthehousing,andtightentheassemblyscrewsrmlyto10-14in.-Ibs.torque.
8.Pushuprubberbushing(9)andstrainreliefwasher(10)overcordsothatthenutcanengage
the threaded insert.
IMPORTANT:Rubberhousingmustbeheldrmlywhentighteningnut.
NOTE 1: Usebackofrubberbushingsasagageforcablesizeorappropriate table below.
Alwaysusematchedbushingandstrainreliefwashers.
NOTE 2:
Polarity of wiring for NEMA devicesisidentiedbymarkingsondeviceand/orscrew
colorasshownbelow.ForPolarityofwiringforNON-NEMAdevicesrefertodevice(s)tobe
replacedforspecicwiringpattern.
1
2
3
4
A
B
C
D
5
6
7
9
10
8
Fig. 1 - Locking Connector (3 wire shown)
1 - Nut
2 - Cord
3 - Rubber Housing
4 - Wiring Module
5 - Threaded Insert
6 - Assembly Screws
7 - Terminal Screws
8 - Key Guide on Wiring Module
(to be aligned with Key on Housing)
9 - Rubber Bushing (select as per Strain Relief Washer)
10 - Strain Relief Washer
MARKING ON NEMA DEVICE
G, GRND, GREEN, or EQ GR
W, or WHITE
X,Y,Z or BLANK
CONDUCTOR COLOR
Bare, Green, or Green/Yellow wire
White or Gray wire
Black, Red, Blue or any other than White, Green, Gray, Green/Yellow or Bare wire
NEMA SCREW COLOR
(Grounding) -- GREEN
(Neutral) -- SILVER
(Hot) -- BRASS or BLACK
Wire Stripping Gage – 20A & 30A (3-5 wire) LockingWire Stripping Gage – 15A & 20A (2-3 wire) Straight Blade,
15A (2-3 wire) Locking, 20A (2 wire) Locking
Insulation
5/8"(1.6 cm)
All Conductors
1"(2.5 cm)
All Conductors except 5 wire Ground
Cord Jacket
5 Wire Ground Only
1-1/2"(3.8 cm)
15/16"
(2.38 cm)
9/16"
(1.43 cm)
Cord Jacket
Insulation
©2011LevitonMfg.Co.,Inc.
15A & 20A (2-3 wire) Straight Blade, 15A (2-3 wire) Locking, 20A (2 wire) Locking
20A (3 - 5 wire) Locking
18/3 S, ST, SO, SOW
16/3 S, ST, SO, SOW
14/3 SJ, SJT, SJTO, SJTOW
14/2 SJ
16/4 SO, SOO, ST, STO, SJ, SJO, SJT
14/3 SO, SOO, ST, STO, SJ, SJO, SJT
12/4 SO, SOO, ST, STO, SJ, SJO, SJT
14/4 SO, SOO, ST, STO, SJ, SJO, SJT
12/3 SO, SOO, ST, STO, SJ, SJO, SJT
12/3 SO, SOW
12/4 SO, SOO, ST, STO
10/2 SO, SOW
12/5 SO, SOO, ST, STO
10/3 SOW
10/3 SO, SOO, ST, STO
14/3 S, ST, SO, SOW
10/5 SO, SOO, ST, STO
12/3 SO, SOO, ST, STO
14/4 SO, SOO, ST, STO
Bushing/Washer Gage (AWG) Type Range
A 18/2 S, ST, SVT, SO, SOW .234 - .437
A
16/3 SO, SOO, ST, STO, SJ, SJO, SJT .375-.500
C 12/2 SO, SOW .562-.687
C 14/5 SO, SOO, ST, STO .625-.750
B 14/2 S, ST, SO, SOW .437-.562
D 10/4 SO, SOO, ST, STO .750-.875
B 14/3 SO, SOO, ST, STO .500-.625
BUSHING AND STRAIN RELIEF CORD SIZING
30A (3 - 5 wire) Locking
12/4 SJ, SJO, SJT, SO, SOO, ST, STO
12/5 SJ, SJO, SJT, SO, SOO, ST, STO
10/3 SJ, SJO, SJT, SO, SOO, ST, STO
10/4 SJ, SJO, SJT, SO, SOO, ST, STO
8/3 SO, SOO, ST, STO
10/5 SO, SOO, ST, STO
Bushing/Washer Gage (AWG) Type Range
A 12/3 SJ, SJO, SJT, SO, SOO, ST, STO .625-.750
C 8/4 SO, SOO, ST, STO .875-1.000
D 8/5 SO, SOO, ST, STO 1.000-1.125
B 10/4 SO, SOO, ST, STO .750-.875
BUSHING AND STRAIN RELIEF CORD SIZING
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) www.leviton.com
LIMITED LIFETIME WARRANTY AND EXCLUSIONS
Levitonwarrantstotheoriginalconsumerpurchaserand notforthebenet ofanyoneelsethat thisproductat thetime ofitssale byLevitonisfreeof defectsinmaterials andworkmanshipundernormal
and proper use during the lifetime of the product.Leviton’s only obligation is to correct such defects byrepair or replacement, at its option, if the product is returnedprepaid, with proof of purchase
date, and a description of the problem to Leviton Manufacturing Co., Inc., Att: Quality Assurance Department, 201 North Service Road, Melville, N.Y. 11747.This warranty excludesand there
is disclaimed liability forlabor forremoval of this product or reinstallation.This warranty is void if this product is installed improperly or in an improper environment,overloaded, misused, opened,
abused, or altered in any manner, or is not used under normaloperating conditions or not in accordance with any labels or instructions. There are no other or implied warrantiesof any kind, including
merchantabilityandtness foraparticular purpose.Levitonisnot liableforincidental,indirect,special,or consequentialdamages,includingwithoutlimitation, damageto,orlossof useof,anyequipment,
lost sales or prots or delay or failureto perform this warrantyobligation.The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tortor otherwise.
PK-93740-10-00-0A
TheseproductsarecoveredbyPatents:US5,863,221;US6,017,243;CA2,243,838;
CA2,266,253;MX225,136andMX215,544.
  • Page 1 1
  • Page 2 2

Leviton 78W47-C Installation guide

Type
Installation guide

Leviton 78W47-C:

This Wetguard connector is intended to be used with Wetguard inlets only. It has a NEMA and NON-NEMA IP66 Suitability and is rated to NEMA Type 4, 4X & 12 when mated with Leviton Wetguard Inlets. The device can be used in both grounded and non-grounded circuits; it's also UL Listed for replacement use only.

The 78W47-C connector is easy to install, and the instructions provided in the manual are clear and concise; they include diagrams and specific torque values for tightening screws. It's important to note that the device should be installed by a qualified electrician to ensure proper functionality and safety.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI