SCE SCE-N12TMV Installation Information

Type
Installation Information
5cf.pdf
1
5cf top mount fans
Technical data for:
SCE-N12TM5CF120V SCE-N12TM5CF230V SCE-N12TM5CF460V3
Model number: 6085A3000SG 6085A4000SG 6085A9000SG
Operating temperature range: 14°F - + 131°F 14°F - + 131°F 14°F - + 131°F
Air volume ow: 570 cfm 570 cfm 520 cfm
Static pressure: 750 Pa 750 Pa 550 Pa
Mounting: Top mounted Top mounted Top mounted
Dimension H x W x D: 5.8 x 18 x 18 inch 5.8 x 18 x 18 inch 5.8 x 18 x 18 inch
Weight: 14.1 lbs 14.1 lbs 14.1 lbs
Cut out dimensions: 11.46 x 11.46 inch 11.46 x 11.46 inch 11.46 x 11.46 inch
Voltage / Frequency: 120 V ~ 60 Hz 230 V ~ 50/60 Hz 400/460 V - 50/60 Hz 3~
Rated current: 1.9 A Max 1.1 A Max 0.33 A
Power consumption: 225 W Max 234 W Max 230 W
Degree of separation: 85% - DIN 24185 85% - DIN 24185 85% - DIN 24185
Filter class: G3 G3 G3
Noise level: 76 dB(A) 76 dB(A) 76 dB(A)
Connection: 4 - Push pin connectors 4 - Push pin connectors 4 - Push pin connectors
Minimum tightening torque: 45 in-lb 45 in-lb 45 in-lb
Minimum exhaust lter intake: 2 x SCE-N12FGA1010(LG)
(model number 400040000) 2 x SCE-N12FGA1010(LG)
(model number 400040000) 2 x SCE-N12FGA1010(LG)
(model number 400040000)
Description
Color: RAL 7035
Material: Mild steel, powder coated
Ingress protection: NEMA 12
Approvals: CE, cURus UL Recognized Type 12
Min enclosure depth: ≥ 14
5cf.pdf
2
Optional M6 screws
(screw mount only)
(screw mount only)
(screw mount only)
304
304
[11.97]
[11.97]
[11.46]
[11.46]
291
291
+1
+1
Mounting
Aperture
Cabinet roof
thickness
1.5 - 3.2 mm
[0.059 - 0.126]
[.315]
Ø8
800
400
600
200
700
300
500
100
Static Pressure (Pa)
0
0
115V -F 230V -F 460V - F
Air Flow [cfm]
50 100 300200 400 550150 350 500250 450 600
Cutout dimensions Performance graph
Wire diagram
M
L1 L2 L3 PE L N PE
3 1
M
Electrical connection to the top mount fan filters
The feed voltage and frequency must be according to
the rated values stated on the name plates. The electrical
connection must be carried out according to the local
norms and safety regulations which govern the use of
electrical material.
Electrical connections and repairs must be carried out by
qualified personnel only.
5cf.pdf
3
breakdown
Replace old filters
Power connector
Air inlet
Holes for screw
mounting (x4)
Cable relief
Mounting provisions for
Fan control thermostat
or alarm thermostat (x2)
Air outlet
1
2
3
4
5
6
1. Remove screws on top.
2. Remove top.
3. Take old out filters.
4. Put new filters in.
5. Place top back on.
6. Replace screws.
For the duration of the
replacement the unit must
be disconnect from the
electrical supply.
!
5cf.pdf
4
Clip mounting:
To secure top mounted
fan, push firmly on all four
corners until click of the
mounting clips can no
longer be heard.
Screw mounting:
Minimum tightening
torque: 45 in-lb
Air Direction
Standard flow allows cool air to come in
through two SCE Nema 12 filters installed
in lower part of enclosure, on both sides or
door, and then push out the rising warmer air
through the top mounted fan.
*Minimum qty 2 required for Type 12 applications
SCE-N12FGA1010
10” Nema 12 filters
SCE-N12FGA1010LG