SCE SCE-N12TM3CF460V3 Installation Information

Type
Installation Information
3cf.pdf
1
3cf top mount fans
Technical data for:
SCE-N12TM3CF120V SCE-N12TM3CF230V SCE-N12TM3CF460V3
Model number: 6095A3000SG 6095A4000SG 6095A9000SG
Operating temperature range: 14°F - + 131°F 14°F - + 131°F 14°F - + 131°F
Air volume ow: 370 cfm 370 cfm 370 cfm
Static pressure: 470 Pa 360 Pa 570 Pa
Mounting: Top mounted Top mounted Top mounted
Dimension H x W x D: 5.8 x 18 x 18 inch 5.8 x 18 x 18 inch 5.8 x 18 x 18 inch
Weight: 14.1 lbs 14.1 lbs 14.1 lbs
Cut out dimensions: 11.46 x 11.46 inch 11.46 x 11.46 inch 11.46 x 11.46 inch
Voltage / Frequency: 120 V ~ 60 Hz 230 V ~ 50/60 Hz 400/460 V - 50/60 Hz 3~
Rated current: 0.88 A Max 0.50 A Max 0.32 A
Power consumption: 108 W Max 116 W Max 145 W
Degree of separation: 85% - DIN 24185 85% - DIN 24185 85% - DIN 24185
Filter class: G3 G3 G3
Noise level: 70 dB(A) 70 dB(A) 70 dB(A)
Connection: 4 - Push pin connectors 4 - Push pin connectors 4 - Push pin connectors
Minimum tightening torque: 45 in-lb 45 in-lb 45 in-lb
Minimum exhaust lter intake: 2 x SCE-N12FGA1010(LG)
(model number 400040000) 2 x SCE-N12FGA1010(LG)
(model number 400040000) 2 x SCE-N12FGA1010(LG)
(model number 400040000)
Description
Color: RAL 7035
Material: Mild steel, powder coated
Ingress protection: NEMA 12
Approvals: CE, cURus UL Recognized Type 12
Min enclosure depth: ≥ 14
3cf.pdf
2
800
400
600
200
700
300
500
100
Static Pressure (Pa)
Air Flow [cfm]
50
0
0100 300200 400 550150 350 500250 450 600
115V -F
230V -F
460V - F
Cutout dimensions Performance graph
Wire diagram
M
L1 L2 L3 PE L N PE
3 1
M
Electrical connection to the top mount fan filters
The feed voltage and frequency must be according to the rated values
stated on the name plates. The electrical connection must be carried
out according to the local norms and safety regulations which govern
the use of electrical material.
Electrical connections and repairs must be carried out by qualified
personnel only.
Optional M6 screws
(screw mount only)
(screw mount only)
(screw mount only)
304
304
[11.97]
[11.97]
[11.46]
[11.46]
291
291
+1
+1
Mounting
Aperture
Cabinet roof
thickness
1.5 - 3.2 mm
[0.059 - 0.126]
[.315]
Ø8
3cf.pdf
3
breakdown
Replace old filters
Power connector
Air inlet
Holes for screw
mounting (x4)
Cable relief
Mounting provisions for
Fan control thermostat
or alarm thermostat (x2)
Air outlet
1
2
3
4
5
6
1. Remove screws on top.
2. Remove top.
3. Take old out filters.
4. Put new filters in.
5. Place top back on.
6. Replace screws.
For the duration of the
replacement the unit must
be disconnect from the
electrical supply.
!
3cf.pdf
4
Clip mounting:
To secure top mounted
fan, push firmly on all four
corners until click of the
mounting clips can no
longer be heard.
Screw mounting:
Minimum tightening
torque: 45 in-lb
Air Direction
SCE-N12FGA1010
10” Nema 12 filters
SCE-N12FGA1010LG
Standard flow allows cool air to come in
through two SCE Nema 12 filters installed
in lower part of enclosure, on both sides or
door, and then push out the rising warmer air
through the top mounted fan.
*Minimum qty 2 required for Type 12 applications