  • Hello! I am an AI chatbot trained to assist you with the Autonics PSAN-01CA Series User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or
substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways,
aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
 Failuretofollowthisinstructionmayresultinre,personalinjury,oreconomicloss.
2. Install on a device panel or to a pressure port directrly to use.
 Failuretofollowthisinstructionmayresultinre.
3. Do not connect, repair, or inspect the unit while connected to a power source.
 Failuretofollowthisinstructionmayresultinre.
4. Check 'Connections' before wiring.
 Failuretofollowthisinstructionmayresultinre.
5. Do not disassemble or modify the unit.
 Failuretofollowthisinstructionmayresultinre.
DIGITALPRESSURESENSOR(Pneumatictype)
PSAN SERIES
Safety Considerations
Warning
Caution
Output Operation Mode
Parameter Setting
Preset Setting
Input/Output Circuit and Diagram
Installation
Error
Functions
I N S T R U C T I O N M A N U A L
ThankyouverymuchforselectingAutonicsproducts.
For your safety, please read the following before using.
Pleasekeeptheseinstructionsandreviewthembeforeusingthisunit.
Thefollowingisanexplanationofthesymbolsusedintheoperationmanual.
Caution:Injuryordangermayoccurunderspecialconditions.
Pleaseobservethecautionsthatfollow;
Warning Seriousinjurymayresultifinstructionsarenotfollowed.
Caution Productmaybedamaged,orinjurymayresultifinstructionsarenotfollowed.
Specications Setting
Major Products
Display Description Countermeasures
ERR1
Whenexternalpressureisinputwhileadjustingzeropoint.
Tryagainafterremovingexternalpressure.
ERR2 Whenoverloadisappliedoncontroloutput Removeoverload.
ERR3 WhensettingconditionisnotmetinAutosensitivity
settingmode.
Checksettingconditionsandsetproper
settingvalues.
LLLL WhenappliedpressureexceedsLow-limitofdisplay
pressurerange. Applypressurewithindisplaypressure
range.
HHHH WhenappliedpressureexceedsHigh-limitofdisplay
pressurerange.
-HH-,-LL-,
-HL-
Autoshiftcorrectionerror. Setthecorrectedsettingvaluewithin
settingpressurerange.
Hysteresis mode[ HYS.M]
Itisabletosetcertainvalueforpressuredetection
level[ST1,ST2]andhysteresis[HYS1,HYS2].
Hysteresis mode
Hysteresis-Window comparison output mode
Zero point adjustment
1.Pleasepress + keysforover1sec.atthe
sametimeputtinganappliedpressureinstateofthe
atmosphericpressure.
2.Whenthezeropointadjustmentiscompleted,itwill
display)0 andreturntoRUNmodeautomatically.
Ifexecutingzeropointadjustmentonexternal
pressurebeingatpressureport[ERR1] flashes 5
times.Pleaseexecuteitintheatmosphericpressure
afterremovingexternalpressure.
Pleaseexecutezeropointadjustmentregularly.
1:PSAN- H- DisplayedonlywhenD-IN is
set to SHFT.Autoshiftreferencepressurecanbeset
withindisplayerrorrange.
(Low_Range≤SH.IN ≤High_Range)
Low_Range=Min.displaypressure-Min.preset
setting value
•High_Range=Max.displaypressure-Max.preset
setting value
Ifpressing + keysforover1sec.incaseofHigh
peak/Lowpeak/Autoshiftreferencepressurevalue,
settingvaluewillbeeraseandreturntonextoperation.
[ RUN]flashestwice,thenreturntoRUNmode.
Peak Hold / Auto Shift Check/Change
Hysteresis-window comparison output mode[ HY-W]
Itisavailabletosethysteresismode[ST1, HYS1]
andwindowcomparisonoutputmodewhenboth
hysteresismodeandwindowcomparisonoutput
mode[LOW, HIGH]arenecessary.
Detectionhysteresisisfixedtomin.displayrange.
Forced output control mode[ fOUT]
UsedtodisplaypressurewithforciblyholdingcomparingoutputOFFregardlessofsettingvalue.
Inparametersetting,ifoutputoperationmodesetting[OUtN]ischangedto[fOUT],forcedoutputcontrol
modeisoperated.
OUT1,2canbeON/OFFmanuallybypressing , keyWhiletheforcedoutputcontrolmodeisapplied.
Analog output type (Voltage output PSAN-□□□□V-, Current output PSAN-□□□□A-)
Hold / Auto Shift input type (PSAN-□□□□H-□)
1.Pressureportisdividedasbasicandoptionspecification.
Therefore,besurethattousecommerciallyavailableone
touchfitting.(Standard:Rc1/8",Option:NPT1/8",R1/8")
2.Pleaseconnectitbyusingspanner(12mm)atthe
metalpartinordernottooverloadonthebodywhen
connectingonetouchfitting.
3.TwodifferentfixingbracketsareprovidedforPSAN
model.Selectproperonewithconsideringyour
applicationenvironments.
4.Atfirst,pleaseunscrewhexagonwrenchboltand
assemblethebracketonthisunitbyfixinghexagon
thewrenchbolt.In this case, tightening torque of
hexagon wrench should be max. 3N.m. It may cause
mechanical problems.
5.Panelbracket(PSO-B02)andfrontprotection
cover(PSO-P01)areoptionaltosell.
Pleaseseethefigureforinstallation.
●NPNopencollectoroutputtype ●PNPopencollectoroutputtype
●NPNopencollectoroutputtype ●PNPopencollectoroutputtype
Window comparison output mode[ WIN]
Itisabletosettherangeforhigh[HI-1,HI-2]/
low[LO-1, LO-2]limitofpressuredetectionlevelwhen
itisrequiredtodetectpressureatacertainrange.
Detectionhysteresisisfixedtomin.displayrange.
Automatic sensitivity setting mode
Automatic sensitivity setting mode[ AUTO]
Thisfunctionistosetpressuredetectionlevel
totheproperpositionautomatically.Itissetby
appliedpressurefromtwopositions[ST1,ST2].
Detectionhysteresisisfixedtomin.displayrange.
Thepressuredetectionlevel[SET] is shown in
thefollowingcalculation.
Pressure unit change
PSAN-V01C(P)andPSAN-C01C(P)has7kindsofpressureunit,PSAN-01C(P)andPSAN-1C(P)has5kinds
ofpressureunit.Pleaseselecttheproperunitforapplication.
PSAN-V01C(P),PSAN-C01C(P):kPa,kgf/cm2,bar,psi,mmHg,inHg,mmH2O
PSAN-01C(P),PSAN-1C(P):MPa,kPa,kgf/cm2,bar,psi
WhenusingmmH2Ounit,pleasemultiplydisplayvalueby100.
Output mode change
Thereare5kindsofcontroloutputmodeinordertorealizethevariouspressuredetection.
Hysteresismode[HYsM]:Whenneededtochangehysteresisfordetectingpressure.
Windowcomparisonoutputmode[WIN]:Whenneededtodetectpressureincertainarea.
Hysteresis-Windowcomparisonoutputmode[HY-W]:Whenbothhysteresismodeandwindowcomparison
outputmodearerequired.
Automaticsensitivitysettingmode[AUTO]:Whenneededtosetdetectionsensitivityautomaticallyatproper
position.
Forcedoutputcontrolmode[fOUT]:Whenneededtodisplaypressurewithremainingcomparisonoutput
OFFregardlessofsettingvalue.
Control output change
TypeofcontroloutputforOut1andOut2canbeabletosetNormallyOpenandNormallyClosed.
NotethatNormallyOpenandNormallyClosedprovideoppositeoutput.
Response time change(chattering prevention)
Itcanpreventchatteringofcontroloutputbychangingresponsetime.
Itisabletoset5kindsofresponsetime(2.5ms,5ms,100ms,500ms,1000ms)andiftheresponsetimeis
gettinglonger,thedetectionwillbemorestablebyincreasingthenumberofdigitalfilter.
Analog output scale setting and Hold/Auto Shift setting
Analogvoltageoutputscalesetting:Thescalefunctionforanalogoutputvoltage(1-5VDC)isnotfixedtothe
ratedpressurerange.ItcanbechangedforUser'sapplication.Analogoutputis1-5VDCwithinthepressure
rangefromthepressurepoint[A-1V]for1VDCtothepressurepoint[A-5V]for5VDC.
Analogcurrentoutputscalesetting:ThescaleforanalogoutputCurrent(DC4-20mA)isnotfixedtotherated
pressurerange.ItcanbechangedforUser'sapplication.Analogoutputis4-20mAwithinthepressurerange
fromthepressurepoint[A-04]for4mAtothepressurepoint[A-20]for20mA.
Hold/AutoShiftinputsetting
- Holdfunction:AfunctiontoholdPVandControloutputwhilesignalisinput.
- AutoShiftfunction:Afunctiontocompensatethesettingvalueforchangedvalueofreferencepressureas
thresholdlevelifreferencepressureofthedevicechanges.
Key lock
Thekeylockfunctionpreventskeyoperationssothatconditionssetineachmode.[preset/parametermodeare
notinadvertentlychanged.Thereare2kindsofkeylockfunctionsavailable.
LOC1:Allkeysarelocked;thereforeitisnotavailabletochangeparametersettings,presetvalue,zero
adjustment,High/LowpeakcheckandSH.IN datainitialization.(Locksettingchangeisavailable)
LOC2:Partiallylockedstatus;thereforeitisnotavailabletochangeparametersettingsonly(Locksetting
changeisavailable).Othersettingsarestillavailable.
OFF:Allofthesettingisavailable,allkeysareunlocked.
Zero point adjustment
Thezeropointadjustmentfunctionforciblysetsthepressurevalueto"Zero"whenthepressureportisopened
toatmosphericpressure.Whenthezeroadjustmentisapplied,analogoutput[VoltageorCurrent]ischanged
bythisfunction.(Press + keysover1sec.inRUNmode.)
High Peak / Low Peak Hold Function
Thisfunctionistodiagnosismalfunctionofthesystemcausedbyparasiticpressureortocheckthrough
memorizingthemax./min.pressureoccurredfromthesystem.
1:(P)isPNPoutputtype, ofmodelnameisaspressureport.
Rc1/8:PT1/8"model(standard),NPT1/8:NPT1/8"model(option),
R1/8:PT1/8"model(Option)
2:Inhysteresisoutputmode,detectiondifferenceisvariable.
3:Itisallowedtoselectoneanalogoutputtypeonly.
4:Resolution(1000/2000)ofmin.Displayintervalisautomatically
selecteddependonpressureunits.
5:Thisweightiswithpackagingandtheweightinparenthesesis
onlyunitweight.
F.S.:Ratedpressure.
Theremaybe±1digiterrorinhysteresis
bypressureunitcalculationerror.
ForusingmmH2Ounit,multiplydisplay
valueby100.
Environmentresistanceisratedatno
freezingorcondensation.
(ST1+ST2)
2
SET
=
Ifthekeylockisset(lock1orlock2),unlockthekeylockbeforesettingparameters.
Press , keytochangesettingvalues.
Press keytosavesettingvalueineachparameterandmovetonextparameters.
Whenpressing keyfor3secinthemiddleofparametersetting,currentsettingvaluewillbesaved
and[RUN]willflashtwice,thenreturnedtoRUNmode.
[ RUN]flashestwicewhenreturningtoRUNmode.
Press , keytochangesettingvalues.
Press keytosavesettingvalueineachparameterandmovetonextparameters.
Ifthereisnoadditionalkeyoperationwithin60sec.while
setting,itisreturnedtoRunmode(Exceptforforceoutput
mode).Previoussetvaluesareremained.
Incaseofchangingoutputoperationmode,nopreset
valueswillbeinitialized.Instead,previousoutputoperation
settingswillbecomethepresetvalues.
Whenchangingpressuredisplayunit,resolutionandHold/
AutoShiftinputfunction,presetvalueswillbeinitializedas
shownthetablebelow.(Whenchangingpressuredisplay
unit,presetvaluewillbeautomaticallyswitchedtochanged
pressureunit.)
Ifthereisnoadditionalkeyoperationwithin60sec.whilesetting,currentsettingvalueisnotvalidand
previoussettingvaluewillberemained.
< Preset Default >
Whenusingtheforcedoutputfunction,Hold/Autoshift
functionisnotavailabletouseinHold/Autoshiftmode.
(unit:kPa)
Min.displaypressure
≤[ST1]≤Max.display
pressure-1%ofrated
pressure
[ ST1]+1%ofrated
pressure≤[ST2]≤
Max.displaypressure
[ SET]
= ([ ST1]+[ ST2])/2
Press , key for
manualadjustment
[ ERR3] Error flashes 3 times in case setting
conditionsarenotmet,resettingisonstandby.
PSAN series has 5 kinds of output operation mode, please use proper output operation mode in
accordance with detection.
Over current
protection
circuit
Over current
protection
circuit
(Brown)+V
(Blue)0V
(Black)OUT1
(White)OUT2
12-24VDC
Load
Load
:Forvoltageoutputtypeonly.
1kΩ
Main circuit
(Orange)
Analogoutput
voltage/current
Pressuretype Gaugepressure
Negativepressure Standardpressure Compoundpressure
Model1
Voltageoutput PSAN-V01C(P)V- PSAN-01C(P)V- PSAN-1C(P)V- PSAN-C01C(P)V-
Currentoutput PSAN-V01C(P)A- PSAN-01C(P)A- PSAN-1C(P)A- PSAN-C01C(P)A-
Hold/Autoshiftinput PSAN-V01C(P)H- PSAN-01C(P)H- PSAN-1C(P)H- PSAN-C01C(P)H-
Ratedpressurerange 0.0to-101.3kPa 0.0to100.0kPa 0to1,000kPa
-101.3kPato100.0kPa
Displaypressurerange 5.0to-101.3kPa -5.0to110.0kPa -101.3to1,100kPa
-101.3kPato110.0kPa
Min.displayunit 0.1kPa 0.1kPa 1kPa 0.1kPa
Max.pressurerange 2timesofrated
pressure
2timesofrated
pressure
1.5timesofrated
pressure
2timesofrated
pressure
Applieduid Air,Non-corrosivegas
Powersupply 12-24VDC±10%(rippleP-P:Max.10%)
Currentconsumption Max.50mA(AnalogCurrentOutputtypeMax75mA)
Controloutput
NPNorPNPopencollectoroutput
•Loadvoltage:Max.30VDC•Loadcurrent:Max.100mA
•Residualvoltage-NPN:Max.1VDC,PNP:Max.2VDC
Hysteresis2Min.displayrange
Repeaterror ±0.2%F.S.±Min.displayrange
Responsetime Selectable2.5ms,5ms,100ms,500ms,1000ms
Shortcircuitprotection
Built-in
Analog
output3
Voltageoutput
•Outputvoltage:1-5VDC±2%F.S.•Linear:Max.±1%F.S.•Outputimpedance:1kΩ
•Zeropoint:Max.1VDC±2%F.S.•Span:Max.4VDC±2%F.S.•Responsetime:50ms
•Resolution:Automaticallychangedto1/1000or1/2000bypressureunit
Currentoutput
•Outputcurrent:DC4-20mA±2%•Linear:Max.±1%F.S.
•Zero-point:Max.DC4mA±2%F.S.•Span:Max.DC16mA±2%F.S.•Responsetime:70ms
•Resolution:Automaticallychangedto1/1000or1/2000bypressureunit
Displaymethod 7segmentLEDDisplay
Min.Displayinterval4
Resolution
Pressure unit
1000 2000 1000 2000 1000 2000 1000 2000
MPa
- -
0.001
-
0.001
- - -
kPa 0.1
-
0.1
-
1
- -
0.1
kgf/cm20.001
-
0.001
-
0.01
- -
0.001
bar 0.001
-
0.001
-
0.01
- -
0.001
psi
-
0.01 - 0.01 - 0.1
-
0.02
mmHg
-
0.4
-
0.8
inHg
-
0.02
-
0.03
mmHO0.1
- -
0.1
Displayaccuracy 0to50:Max.±0.5%F.S.,-10to0℃:Max.±1%F.S.
Dielectric strength 1000VAC50/60Hzfor1minute
Insulation resistance Over50MΩ(at500VDCmegger)
Vibration
1.5mmamplitudeatfrequencyof10to55Hz(for1min.)ineachofX,Y,Zdirectionfor2hours
Environ-
ment
Ambienttemp. -10to50,storage:-20to60
Ambienthumi. 30to80%RH,storage:30to80%RH
Protection IP40(IECspecification)
Material Frontcase:PC,Rearcase:PC,Pressureport:NickelPlatedBrass
Cable Connectorcable(Ø4mm,5-wire,Length:2m)
(AWG24,Corediameter:0.08mm,Numberofcores:40,Insulatoroutdiameter:Ø1mm)
Approval
Weight
5
Approx.165g(approx.80g)
ST2
HYS2
ST1
HYS1
Pressure
Time
Time
Time
Time
Time
ST2/HYS2
ST1/HYS1
ST1/HYS1
ST2/HYS2
OUT1N.O.
OUT2N.O.
OUT1N.C.
OUT2N.C.
RUN mode
RUN mode
Flashing
in turn
fOUT
Currentpressure
8#1
RUN modeRUN mode Forced output control mode
operation status
OUT1
OUT2
Time
Time
ON
OFF
ON
OFF
Press key
over3sec.
Press key
over3sec.
Press
keysover1sec.
Press key
Parameter
setting
Pressure
unit setting
Output
operation
modesetting
Output
typesetting
Response
time setting
Key lock
setting
Analogoutputscaleand
Hold/AutoShiftinputsetting
Peakhold Highpeak
value check
Lowpeak
value check
Autoshiftinputsetting
(IncaseofHold/Autoshiftinputtypemodel)
Zero-point
adjustment Zero-pointadjustment
Preset value
setting
Detectionlevel1setting(out1)
Detectionlevel2setting(out2)
Forcedoutput
controlmode
setting
Theforcedoutputcontrolmodeisappliedwithpressign keyafterselectingforcedoutputcontrol
mode[fOUT]inoutputoperationmode[OUtM]parameter.Formoredetailedinformation,
referto'●Forcedoutputcontrolmode'' Outputoperationmode'
RUNmode
1: Min.displayrange
Pressure
Time
Time
Time
Time
Time
LO-1/HI-1
LO-1/HI-1
LO-2/HI-2
LO-2/HI-2
OUT1N.O.
OUT2N.O.
OUT1N.C.
OUT2N.C.
1
1
1
1
HI-2
HI-1
LO-2
LO-1
Time
1:Min.displayrange
Pressure
Time
Time
Time
Time
LOW/HIGH
ST1/HYS1
ST1/HYS1
LOW/HIGH
OUT1N.O.
OUT2N.O.
OUT1N.C.
OUT2N.C.
1
1
ST1
HYS1
LOW
HIGH
Time
1:Min.displayrange
Pressure
Time
Time
Time
Time
SET=(ST1+ST2)/2
ST1/ST2
SET
SET
ST1/ST2
OUT1N.O.
OUT2N.O.
OUT1N.C.
OUT2N.C.
1
1
1
ST2
SET
ST1
flashing
in turn
flashing
in turn
flashing
in turn
flashing
in turn
flashing
in turn flashing
in turn
flashing
in turn
flashing
in turn flashing
in turn
flashing
in turn
flashing
in turn
IncaseofusingmmH2Ounit,
multiply100bydisplayvalue.
Incaseofstandardpressure
typemodel,[MPA],[KPA],[KGF],
[ BAR],[PSI]parametersare
displayedonly.
Parameter OUT1output OUT2output
1O2O
NormallyOpen NormallyOpen
1O2C
NormallyOpen NormallyClosed
1C2O
NormallyClosed NormallyOpen
1C2C
NormallyClosed NormallyClosed
Unit: ms
Analog voltage output
(PSAN-□□□□V-)
Analog current output
(PSAN-□□□□A-)
Hold/Shift input
(PSAN-□□□□H-)
SelectHold(Referto" Function")
1:Setrange:Min.ratedpressure≤[A-1V,A-04]≤90%ofratedpressure
2: Set range : [ A-1V,A-04]+10%ofratedpressure≤[A-SV,A-20]≤Max.ratedpressure
See setting Function key lock function for more
details.
Press key
over3sec.
Press key
over3sec.
11
22
RUN mode
Pressure unit
Outputoperation
mode
Output
Responsetime
1VScale
5VScale
4mA Scale
20mAScale
Externalinputfunction
Controloutputfor
Auto shift function
Key lock
(MPa) (KPa) (kgf/cm
2
)(bar)
(psi)
(mmH
2
O) (inHg) (mmHg)
MPA
H2O
KPA
INHG
KGF
MMHG
BAR
PSI
UNIT
OUtM
@5
1O2O
%0
1O2C
100
1C2O
500
1C2C
Hysteresis
mode
Window
comparison
outputmode
Auto sensitivity
settingmode Forcedoutput
controlmode
Hysteresis-Window
comparisonoutput
mode
HYsM WIN HY-W AUTO fOUT
1000
NoNC
SPD
A-04 HOLD
OUT1
ALL
D-IN
ShOTA-20
A-1V )0 )0 SHFT
OUT210)0A-5V 10)0
OFFLOCK LOC1 LOC2
flashing
in turn
flashing
in turn
flashing
in turn
flashing
in turn
Set range :
Min.displaypressure
[ ST1]≤Max.display
pressure
Set range :
Min.displaypressure
≤[HYS1] [ ST1]
Set range :
Min.displaypressure
[ ST2]≤Max.display
pressure
Set range :
Min.displaypressure
≤[HYS2] [ ST2]
Hysteresislevel1
Pressuredetection
level 2
Pressuredetection
level 1
Hysteresislevel2
ST1 2)0
HYS1 1)0
ST2 4)0
HYS2 3)0
RUN mode
flashing
in turn
flashing
in turn
flashing
in turn
Pressuredetection
level 1
Pressuredetection
level 2
Auto setting value
ST1 1)0
ST2 2)0
STT 1%0
RUN mode
Window comparison output mode
Set range :
Min.displaypressure
≤[LO-1]≤Max.display
pressure-(3×Min.display
interval)
Set range :
[ LO-1]+(3×Min.display
interval)≤[HI-1]
≤Max.displaypressure
Set range
Min.displaypressure≤
[ LO-2]≤Max.display
pressure-(3×Min.display
interval)
Set range
[ LO-2]+(3×Min.display
interval)≤[HI-2]
≤Max.displaypressure
flashing
in turn
flashing
in turn
flashing
in turn
flashing
in turn
Low-limitvalueof
Pressuredetectionlevel1
Low-limitvalueof
Pressuredetectionlevel2
High-limitvalueof
Pressuredetectionlevel1
High-limitvalueof
Pressuredetectionlevel2
LO-1 1)0
HI-1 2)0
LO-2 3)0
HI-2 4)0
RUN mode
Set range
Min.displaypressure
[ ST1]≤Max.display
pressure
Set range
Min.displaypressure
≤[HYS1] [ ST1]
Set range
Min.displaypressure
≤[LOW]≤Max.display
pressure-(3×Min.display
interval)
Set range
[ LOW]+(3×Min.display
interval)≤[HIGH]
≤Max.displaypressure
flashing
in turn
flashing
in turn
flashing
in turn
flashing
in turn
ST1 1)0
HYS1 2)0
LOW 3)0
HIGH 4)0
RUN mode
Pressuredetection
level 1
Hysteresislevel1
Low-limitvalueof
Pressuredetectionlevel2
High-limitvalueof
Pressuredetectionlevel2
Output
mode
Negative
pressure
0.0to-101.3
Standard
pressure
0.0to100.0
Standard
pressure
0to1,000
Compound
pressure
-101.3to100.0
HYS.M
ST1
:-50.0
ST1
:50.0
ST1
:500
ST1
:50.0
HYS1
:0.0
HYS1
:0.0
HYS1
:0
HYS1
:-50.0
ST2
:-50.0
ST2
:50.0
ST2
:500
ST2
:50.0
HYS2
:0.0
HYS2
:0.0
HYS2
:0
HYS2
:-50.0
WIN
LO-1
:0.0
LO-1
:0.0
LO-1
:0
LO-1
:-50.0
HI-1
:-50.0
HI-1
:50.0
HI-1
:500
HI-1
:50.0
LO-2
:0.0
LO-2
:0.0
LO-2
:0
LO-2
:-50.0
HI-2
:-50.0
HI-2
:50.0
HI-2
:500
HI-2
:50.0
HY-W
ST1
:-50.0
ST1
:50.0
ST1
:500
ST1
:50.0
HYS1
:0.0
HYS1
:0.0
HYS1
:0
HYS1
:-50.0
LOW
:0.0
LOW
:0.0
LOW
:500
LOW
:-50.0
HIGH
:-50.0
HIGH
:50.0
HIGH
:0
HIGH
:50.0
AUTO
ST1
:0.0
ST1
:0.0
ST1
:0
ST1
:-50.0
ST2
:-50.0
ST2
:50.0
ST2
:500
ST2
:50.0
SET
:-25.0
SET
:25.0
SET
:250
SET
:0.0
●Accessory
●Sold separately
● Panel cut-out
. Pressure unit label
(unit:mm)
. Bracket A
. Connector cable(PSO-C01, 2m)
. Panel bracket(PSO-B02/B03)
. M5 Gender(PSO-Z01)
. Front cover(PSO-P01)
Dimensions
The tightening torque of
one touch fitting should be
max. 10N.m. It may cause
machanical problems.
Caution
12mm
Spanner
Protection
cover
(PSO-P01)
Mountingpanel
(panelthickness0.8to3.5mm)
Panelbracket
(PSO-B02)
Body
(PSAN)
flashing
in turn
flashing
in turn
flashing
in turn
HighPeakvalue
Low Peak value
Referencepressure
for Auto Shift
hPEK 10)6
lPEK -@7
ShIN 5)0
RUN mode
1
Press key over3sec.
Springwasher
Hexagonwrench
bolt(M3×6)
BracketA
BracketB
A
20
20
12
2-M3Tap
30.7
22.8 7.9
A
30
30
30.7
22.8 7.9 8
PT1/8"
Inside
M5Tap
64.2
14
20
30
5
3-Ø3.2
Ø4.2
20
6
12.7
20
45
15
13
. Bracket B
45
22
3-Ø3.2
14
6
5
20
20
35
30
25
4.2
6
Ø4.2
PT1/8"model
(standard)
8
NPT1/8"model
(panelthickness:0.8to3.5mm)
36+0.5
0
36+0.5
0
10 1
5.7
40
42
40
40
40
30 320
25.8
28.2
Unit Descriptions
1. Range of rating pressure:ItispossibletochangethepressureunitinPressure
sensor.Pleaseusedifferentunitaslabelforyourapplication.
2. 4digit LED display(Red):Usedtoindicatemeasuredpressurevalue,setting
valueanderrormessage.
3. Output1 indicator(Red):Output1isON,LEDwillbeON.
4. Output2 indicator(Green):Output2isON,LEDwillbeON.
5. key:UsedtoenterintoPreset/ParametersettingmodeandtosaveSetting
mode.
6. , key:Usedtosetparameterandpreset,peakvaluecheckmode,function
settingoroutputoperationmode.
+ key:Usedforzeropointadjustmentfunctionbypressing + keys
over1sec.simultaneouslyinRUNmode.
1
2
4
6
3
5
Load
Load
(Brown)+V
(Black)OUT1
(White)OUT2
12-24VDC
:Forvoltageoutputtypeonly.
1kΩ
Main circuit
(Blue)0V
(Orange)
Analogoutput
voltage/current
Over current
protection
circuit
Over current
protection
circuit
Load
Load
(Brown)+V
(Blue)0V
(Black)OUT1
(White)OUT2
(Orange)Hold/
Autoshiftinput
12-24VDC
Main circuit
Over current
protection
circuit
Over current
protection
circuit
Load
Load
(Brown)+V
(Blue)0V
(Black)OUT1
(White)OUT2
(Orange)Hold/
Autoshiftinput
12-24VDC
Main circuit
Over current
protection
circuit
Over current
protection
circuit
1. Use the unit within the rated specications.
 Failuretofollowthisinstructionmayresultinreorproductdamage.
2. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failuretofollowthisinstructionmayresultinre.
3. This product is designed to detect the pressure of noncorrosive gas. Do not use for corrosive gas.
 Failuretofollowthisinstructionmayresultinproductdamage.
4. Do not use the unit in the place where ammable/explosive/corrosive gas, humidity, direct sunlight,
radiant heat, vibration, impact, or salinity may be present.
Failuretofollowthisinstructionmayresultinreorexplosion.
5. Keep metal chip, dust, and wire residue from owing into the unit.
Failuretofollowthisinstructionmayresultinreorproductdamage.
The above specications are subject to change and some models may be discontinued without notice.
Be sure to follow cautions written in the instruction manual and the technical descriptions
(catalog, homepage).
Ifshort-circuitthecontroloutputterminalorsupplycurrentovertheratedspecification,normalcontrol
signalisnotoutputduetotheoutputshortovercurrentprotectioncircuit
6.Donotpullthecablewithatensilestrengthof30Norover.
Cautions during Use
1.Followinstructionsin'CautionsduringUse'.
 Otherwise,Itmaycauseunexpectedaccidents.
2.12-24VDCpowersupplyshouldbeinsulatedandlimitedvoltage/currentorClass2,SELVpowersupplydevice.
3.Usetheproduct,3secaftersupplyingpower.
4.Whenusingswitchingmodepowersupply,frameground(F.G.)terminalofpowersupplyshouldbegrounded.
5.Wireasshortaspossibleandkeepawayfromhighvoltagelinesorpowerlines,topreventinductivenoise.
6.Thisunitmaybeusedinthefollowingenvironments.
Indoors(intheenvironmentconditionratedin'Specications')
Altitudemax.2,000m
Pollutiondegree3
Installation category II
Photoelectric Sensors TemperatureControllers
FiberOpticSensors Temperature/HumidityTransducers
Door Sensors SSRs/PowerControllers
DoorSideSensors Counters
Area Sensors Timers
Proximity Sensors Panel Meters
Pressure Sensors Tachometer/Pulse(Rate)Meters
RotaryEncoders DisplayUnits
Connector/Sockets Sensor Controllers
SwitchingModePowerSupplies
ControlSwitches/Lamps/Buzzers
I/OTerminalBlocks&Cables
StepperMotors/Drivers/MotionControllers
Graphic/LogicPanels
FieldNetworkDevices
LaserMarkingSystem(Fiber,CO,Nd:YAG)
LaserWelding/CuttingSystem
http://www.autonics.com
HEADQUARTERS:
18,Bansong-ro513beon-gil,Haeundae-gu,Busan,
SouthKorea,48002
TEL:82-51-519-3232
DR W171185A A
DR W17118 5A A
/