OPTI-UPS SS45K33 User manual

Type
User manual
- 1-
AVR
IndustrialGradeHighEfficiencyA.CVoltageRegulator
USER’SMANUAL
OPTIUPSInternationalCorporationreservestherighttomakeengineeringchangesonallitsproducts.Suchrefinements
mayaffectinformationgivenintheinstructions.Therefore,USEONLYTHEINSTRUCTIONSTHATAREPACKEDWITHTHE
PRODUCT.
WARNING:Highvoltagesarepresentinsidethisunitduringoperation.Donotoperatethisunitunless
allcoversareinplace.
Installationandservicingshouldonlybedonebyqualifiedpersonnel.
- 2-
CONTENTS
1‐TheProtectionandMaintenanceofAVR
3
2‐Safetywarnings
4
3‐Descriptionofthesymbolsusedinthismanual
5
4‐Introduction
6
5‐FunctionsIntroduction
7
6‐PreliminarywarningstousetheAVR
7~8
7‐Operatingprocedures
8~9
8‐TheOperationProceduresofMaintenanceByPassSwitch
10
9‐Maintenance&Cleaning
10~11
10‐TroubleshootingGuide
11
11‐Storage
11
12‐Technicalspecifications
12
13‐Machineschematicview/outline
12~19

- 3-
1‐TheProtectionandMaintenanceofAVR
1.PleasecleanandmaintaintheAVRperiodicallytokeepfromdustforlastingmachinelife.
2.Pleaseusesoftclothforwiping,andpleasedon’tusesandpaperasdetergent.
3.Pleasecheckeverykindofconnectionwireseverymonthperiodicallytopreventtheloosingor
abrasion.
4.Pleaseplacetheunitonaflatorevensurface.
5.Thisunitshouldbesituatedwithwellventilation,pleaseallowatleast30cmclearancefromtherear
front,leftandrightside,andtheseventilationopeningsofrightandleftfront,andrearlineshould
neverbeblocked.
6.Pleaseavoidthedirectsunshine,rainormoistureplace.
7.Keepingtheunitawayfromfireandhightemperaturetoavoidoverheat.
8.Pleasedon’tplaceanyobjectonthetop.
9.Avoidingtheinstallingplacethatcontainsthecorrosiongas.
10.Operatingtemperatureisbetween0~40
.
30cm
- 4-
2‐Safetywarnings
Fortheuser’sownsafety,thesafetyofdataandthisproduct
readthefollowingsafetyinstructionscarefullybeforeusing
theunit!
‐Thissystemhasbeendesignedtoprovideallthenecessarysafetyconditionsneeded
toprotectelectronicofficeequipmentincludinginformationsystems.Incaseofanyquestions,
refertoyourauthorizedtechnicalservicerepresentative.
‐Inordertoavoidanydamagetotheequipment,itisadvisedtotransportitinits
ownpacking.
‐Intheeventofsuddentemperaturechangessuchasfromcoldtothenormalworkingtemperature,
mistcanforminsidetheAVR.ItisabsolutelyessentialthattheAVRbedrybeforeswitchingiton.
Duetothisreasonwaitforatleast2hoursbeforeoperatingit.
‐Oncedry,makesureyouobservealltheconditionsintheenvironmentsectionofthetechnical
specificationstable,beforeintroducingitintothecircuit.
‐WheninstallingtheAVRitisnecessarytouseaconnectioncableofsuitablediameter.Thepointto
benotedhereisthattheneutral
andtheearthingconnectionsshouldbedoneintheproperway.
‐Placeallthecablesinaproperplacesothattheyarenotsteppedonorgetcaughtintopeoplesfeet.
BeforeconnectingtheAVRtothecircuitmakesureyoucarefullyreadalltheinstructionsand
warningsinthe“MontageandOperatingProceduressectionofthismanual.
‐Don’tdropanyforeignmaterials(likeclips,nailsetc...)intotheequipment.
‐Inemergencies(damagetothecabin,frontpanel,ormainsconnections,splashingofliquiddropping
ofanyforeignmaterialsintotheequipment)switchofftheAVR,pullouttheplugandinformthe
authorized
servicecenter.
‐TheAVRcanonlyberepairedbytheauthorizedtechnicalservicepersonnel.Anyattempttoopen
andtorepairbytheuseronhisowncouldprovetobedangerous.
‐DonotconnectanyconsumerloadstotheAVR,whichexceeditspowerrange.
‐Readtheinstructions
carefullyinthe“TheOperationProceduresofMaintenanceByPassSwitch”&
“Cleaning”sectionwhencleaningtheAVR.
‐Leaveatleastadistanceof45cmbetweentheAVRandthewallsinordertomaintainadequate
airflow.
- 5-
3‐Descriptionofthesymbolsusedinthismanual
Thefollowingsymbolshavebeenusedinthismanual.
Thissymbolgivesinformationregardingpointsimportantforuser’sownhealthand
safety,AVRoperationandthesafetyofyourdata.
Thissymbolgivesinformation,warnings,andothersuggestions.
Thissymbolshowstheoperationsthatneedtobeexecuted.
- 6-
4‐Introduction
Inputpowerisappliedacrossthemotordrivenvariabletransformerwhichhasa“centertap”that
dividesthevariabletransformerintobuckingandboostingvoltageareas.Thebuckboosttransformeris
afixedratioisolationtransformercapableofhighamperesatlowvoltage.Theratioofthebuckboost
transformerisdeterminedbytheamountofvoltageneededtobuckorboosttheinputlinevoltageto
maintainthespecifiedoutputlevel.Thebuckboosttransformersecondaryiswiredinserieswiththe
loadandtheprimaryisconnectedacrossthevariabletransformer’s“centertap”andbrush
terminals.Dependingonwhichsideofthe“centertap”thevariabletransformerbrushispositioned,
thevariable/buckboosttransformersystemwilladdto(boost)orsubtractfrom(buck)theinputline
voltage.Thefurtherthevariabletransformerbrushisfromthe“centertap”themorebuckingor
boostingofvoltagewilloccur.Thekeytotheprovenreliabilityandlongtroublefreeservicelifeofa
VoltageRegulatorisinthecombinationofamotordrivenvariabletransformerwithbuckboost
transformertechnology.

InputOutput



Figure1.Singlephaseregulatorblockdiagram
Asshowninfigure1,theonlyactivecomponentinthemainpowerpathofthevoltageregulatoris
thesecondaryofthebuckboosttransformer.Thisgivestheregulatortheadvantageofbeingableto
withstandsubstantialcurrentoverloads.Thevariabletransformerbrushes,whicharethemost
vulnerablecomponentinany
variabletransformersystem,arecompletelyisolatedfromoverload
conditionsbythebuckboosttransformer.Duetotransformerinefficiencyaboverateddesign,the
amountofcurrentthatthebuckboosttransformercaninduceacrosstoitsprimarywindingandinto
thevariabletransformercircuitisdramaticallydecreasedasregulatoroverload
currentincreases.
Thecontrollermonitorstheregulator’soutputvoltageandthenusesthesefeedbacksignalsto
determinedrivecommandsforthevariabletransformermotorinterfacecircuit.Thecontrolleris
designedtoadjustthemotorizedvariabletransformertoprovidea+/1~2%orbetteroutputvoltage
regulationovertheentireinputvoltagerange.
5‐FunctionsIntroduction
M Controller
Buck-Boost transformer Variable transformer
- 7-
MCCB1:Moldcastcircuitbreaker
Mainpowerswitch
MCCB2:Moldcastcircuitbreaker
Maintenancebypassswitch.
PleaserememberthatMCCB2isusedonlyforservicetechnician.
Nonmaintenancepersonnelmustnotopenittouse,otherwise,AVRcouldbebreakdownbecauseof
improperoperating.
Onpushswitch(redbutton):
Controllingtheoutput(On)action.
Offpushswitch(greenbutton):
Controllingtheoutput(Off)action.

Off(0):AVRnoaction,sotheoutputhasnovoltagestabilityfunction.
On(1):AVRaction,sotheoutputvoltageissteady.
Voltageandcurrentindicator:(Thereisnovoltage&currentmeterindicationbelow50KVA).
Voltagemeter(V)indicatestheoutputvoltage.
Voltageselectorindicatesperphase(UVW)withNtheoutputvoltage.
6‐PreliminarywarningstousetheAVR
AutomaticVoltageRegulator(AVR)areusedtoprotectthesensitiveloadsfromtheunstablemainsand
toprovideproperoperatingoftheload.
Relatedpointsforhumanhealtharementionedin“SafetyWarnings”partofthismanual.
Inthispart,thesepointswillrepeatedtogiveinformationabouttheconnectionsofAVRandtheload.
WheninstallingtheAVRtousecablewithimproperdiametercanbedangerousforuser
healthandsafetyoftheunit.
Earthcableshouldbechosenconcerningthecurrentcapacity,whichiswrittenonthelabelon
thefrontpaneloftheAVR.Allunitsearthconnections,whichareconnectedtoAVR,should
bedonewiththisearthcable.Withoutearth,connectionorunprovedearthconnectedunits
aredangerousforuserhealthandhavehighriskofelectroniccircuitboardfaults.

Theoperationenvironmentandcableconnectionplaysveryimportantroletothe
functionofAVR.ItwillcauseverydirectandcriticaleffecttotheAVR’sMTBF.Therefore
- 8-
itisessentialtofollowtheinstructionsofinstallationandcableconnection.
Requirementofoperationenvironment
TheoperationenvironmentplaysavitalroleforanAVR,boththefunctionandtheenduranceofAVR
willallbeeasilyaffecte diftheenvironmentdoesnotmeetitsrequirementlistedbelow
1.Ambienttemperature0~40.
2.Keepofftheoilandthesalt.
3.Keepoffdust,fluffandmetaldust.
4.Avoidinstallingonavibratorymachine.
5.IfAVRisinstalledinsideamachineorapanelcabinet,theventilationisveryimportant,thebestis
toaddcoolingfan.
6.DonotplaceanythingontopoftheAVR.
CableConnection
1. The installation standard varies with the different models, different capacities as well as the
different voltage, please refer to the appropriate installation standard provided in this manual to
installyourAVRandputattentiontotherightcablesusedforinstallation.
2. PleaseuseaseparateACinputBreakerforAVRandacloserdistancetotheACpower
isrecommended.
3. Be sure to check the right polarity while connecting cables to terminals, no matter the AVR is a
singlephaseorthreephase.
4. TheutmostimportancetoinstallathreephaseAVRistomarksureoftherightphaseorder.
5. Forsafelyconsideration,itisstrictlyforbiddentoinstallwithACpower“On”status.
6. Cableassemblingmustbecompletelyinaccordancewiththeelectricianrules.
7‐Operatingprocedures
CheckiftheAVRhasbeensubjectedtoanydamagebeforeunpackingit.
Ifyounoticeanydamagethencontacttotransportfirm.
CheckifallthesparepartshavebeensuppliedwiththeAVR.
Checkingtheinputpoweriscorrectornot,thenclosingallswitches(includingevery
load).
Deliveredpackincludes:
- 9-
AutomaticVoltageRegulator
UserManual
Bythehelpofrollingwheels,carrytheunittoasuitablelocationtoinstallit.
PlugtheinputpowercableofAVRtoproperlyearthedmains.
Checktheconnectionsbeforechangingthepositionoftheinput,output,andbypassswitchesto
suitablepositions.
ProperoperationproceduremakesAVR function moresmoothand preventfromvarious unnecessary
troubles.
Beforeswitchon(initialstart)
InordertoperfecttheAVRnormalfunction,pleasecheckthefollowingsinadvance:
makesureMCCB(1)MCCB(2)Moldcastcircuitbreakerisin“O ffstatus.
makesurealloftheload’sMoldcastcircuitbreakerarein“Offstatus.
makesureallthecablesarefixedtightintheterminalanddonotcomeloose.
checkwithamultimeterfortherightACvoltagetosuitforAVR.
Afteralltheabovearewellconfirmed,pleasetak ethefollowingstepstoswitchOnandOff:
1. toswitchon:
SwitchMCCB(1)Moldcastcircuitbreakerupto“On”position.
Pushingtheredbutton“On”onfrontpanel
 If the red buttonindicatoris lighted,meaning the O/P voltage metershowing the rightoutput
voltagevalue.
UsingTureRMSvoltagemetertomeasuretheO/PN,UVWontheterminalboard.Iftheoutput
voltageiscorrect,AVRisactivatedsuccessfully.
pleasenottooverloadyourAVR
2. toswitchoff:
CloseMoldcastcircuitbreaker“O ffofeveryload.
Pushingthegreenbutton“Off”onfrontpanel,althoughthereisnooutputvoltage,theAVRis
stillinaction.
SwitchMCCB(1)Moldcastcircuitbreakerto“Off”position.

8.TheOperationProceduresofMaintenanceByPassSwitch

- 10-
MaintenanceBypass:
CloseMoldcastcircuitbreaker“O ffofeveryload.
Pushingthegreenbutton“Off”onfrontpanel,althoughthereisnooutputvoltage,theAVRis
stillinaction.
SwitchMCCB(1)Moldcastcircuitbreakerto“Off”position.
SwitchMCCB(2)Moldcastcircuitbreakerupto“On”position.
UsingTureRMSvoltagemetertomeasuretheO/PN,UVWontheterminalboard,iftheoutput
voltageiscorrect,AVRisbypasssuccessfully.
9‐Maintenance&Cleaning
DothecleaningduringtheinputMoldcastcircuitbreakerMCCB(1)andmaintenance
bypassMCCB(2)switchisin“Off”positionforhumanhealth.
Donotusedetergentsoranycleaningmaterialthatmaydamagethecabinetsurfaces.
DonotletanyliquidgetintotheAVR.
Ensurethattheairholesareopen.
TheAVRbodycanbewipedwithacleananddrycloth.
ChecktheareasurroundingtheAVR.Ensuretheareaisnotcluttered,allowingfree
accesstotheunit.
Ensuretheairintakes(ventsonthefrontdoors)andexhaustopening(onrearoftheAVR
cabinetsections)arenotblocked.
Toensuremaximumlifeoftheequipment,thefollowingshouldbepartofanannualmaintenance
program.WarningDeenergizeunitbef or eperformingmaintenance.Voltagesarepresentinsidethisunit
whichcancauseinjury.Therefore,onlypersonnelqualifiedtoserviceelectricalequipmentshould
performmaintenanceonthisunit.
Vacuum the voltageregulatorinsideandouttoremoveaccumulateddirt,whichcouldleadto
overheatingorinsulationfailure.
Tightenallelectricalconnections,particularlyallpowerwiringto ,andin,theunit.
Inspectallvariabletransformerbrushesandcommutatorsforsignsofwearorpitting.Replaceas
required.Donotat tempttocleanacommutatorwithanabrasivesuchassandpaperorafile.Thiswill
ruinthesoftpreciousmetalplatingonthecommutatorandwillshortenthelifeoftheunit.Itis
normalforcommutatorstobecomeblackduetocarbonbrushtracking.Ifacommutatoristobe
cleaned,usedenaturedalcoholandasoftcloth.
- 11-
Inspectthevariabletransformerdrivebelts,sprockets,gears,cams,etc.forsignsofslippageorwear
andadjustasrequired.
Checkthevariabletransformerradiator(s)(thediecastpartthatholdsthebrushassembly)forsignsof
slippage,andseeifallbrushesdrivenbythesamemotorarealignedwitheachother.Thealignment
oftheradiatorandbrushesdependsonthesetscrewsthatholdthevariabletransformer centertube(s)
totheshaftandthesetscrewsthatholdtheradiatortothecentertube.Adjustandtightenasneeded.
LubricationoftheAVRisnotrequiredsinceithasbeenlubricatedatthefactoryforitslifetime.
10‐TroubleshootingGuide
IfanyerrorsoffaultsareobservedontheAVR,makesureyoucheckthefollowing
pointsbeforeinformingtheauthorizedtechnicalservice:
Doesthedistributionpanelhavemainsconnection?
Havetheprotectionfusesblownoff?
InformingtheauthorizedserviceabouttheAVR:
Informationfoundontheproductlabel(model,no)
Describetheproblemindetail.
11.Storage
Theunithastobestoredinadryplacebetween0~90.
- 12-
12.Technicalspecifications
InputCharacteristics
Capacity:
VoltageRange: 
Phases: 
FrequencyRange: 
Terminationterminalblock
45KVA
380Y/220Volt,+15%to‐15%at50Hzforregulation.
Threephases4wire,Wyeconnection(R,S,T,N,G)
4753Hzfor50Hzmodels+/3Hz
terminalboard
OutputCharacteristics
Voltage:
Phases:
VoltageRange:
FrequencyRange:
LoadRegulation:
HarmonicDistortion:
Efficiency:
Overload:
Waveform:
InsulationResistance:
Technology:
BypassSwitch
Cooling:
Termination
380Y/220Volt
Threephases4wire,Wyeconnection(U,V,W,N,G)
Regulatedto±1~2%ofnominalvoltagewithaninputvoltagerangeof+15
to–15%
50Hz,forevery1%
changeininputfrequencytheoutputvoltagewillchangeby
1%inthesamedirection.
5%,noloadtofullload
non
97%atfullload.
For1minutes100%,for30minutes125%,for60minutes100%.
Sinewave
5megaohmsfromwindingtocoremeasuredat500Vdc
Thistechniqueusesthecombinationof
amotordrivenvariabletransformerwith
buckboosttransformertechnology.
inputpowerdirectlytoload,bypassingthevoltageregulator.
fanassisted
terminalboard
Environmental
AudibleNoise:
AmbientTemperature:
OperatingAltitude:
OperatingHumidity:
HeatRejection:
Lessthan65dBAat1.5metre
to40°COperating,
10°to90
°CStorage
3,000metrewithoutderating
90%relative(noncondensing)
Atfullload,10%ofVAratingx3.41.
13‐Machineschematicview/outline
[Front view]
[Right side view]
[Isometric view]
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
E E
F F
Page 1
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
E E
F F
Fan
Page 2
Push botton
Buck-boost transformer
Control board
MOV
VS
AS
Voltage multimeter
Current Multimeter
Variable transformer
Current transformer
Input/Output teminal board
Bypass MCCB
Main MCCB
3-Phase monitoring & protection relay
Magnetic contact
Industrial castors
Power relay
Fuse holes
Lifting lugs
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
E E
F F
R S T N G U V W N G
INPUT OUTPUT
Page 3
Main MCCB On
Main MCCB Off
Bypass MCCB Off
Bypass MCCB On
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
E E
F F
M
a
i
n
M
C
C
B
B
y
p
a
s
s
M
C
C
B
Page 4
ON
OFF
ON
OFF
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
E E
F F
F1 F2 F3
Fuse
Page 5
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
E E
F F
AVR controll board
U PFASE
V PHASE W PHASE
Output voltage adjust
Page 6
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
E E
F F
MOV
Page 7
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
A A
B B
C C
D D
E E
F F
RUN
OVER
UNDER
Page 8
RUN:Status of normal running
OVER:Status of over high voltage limit
UNDER:Status of under low voltage limit
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

OPTI-UPS SS45K33 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI