Tyco BIFFI OLGAS-M 35-2000-100-OP Installation Instructions And Maintenance Manual

Type
Installation Instructions And Maintenance Manual

This manual is also suitable for

EHAS (OLGAS-M 35-2000-100-OP)
ELECTRO-HYDRAULIC ACTUATOR
with
INTEGRAL ELECTRONIC POSITION CONTROL
INSTALLATION INSTRUCTIONS AND
MAINTENANCE HANDBOOK
MDE 142E
CUSTOMER
Tyco Hong Kong
ORDER
0235155/BB3606
VALVE MAKER
Vanessa srl
VALVE SIZE
32”/150
ACTUATOR MAKER
Biffi italia
ACKNOWLEDGE
02/3063/GKF
END USER
ANSHAN STEEL WORK
ENGINEERING
tba
!@ç$ flow control
BIFFI ITALIA s.r.l. - Loc. Caselle S. Pietro - 29017 Fiorenzuola d’Arda -Piacenza - ITALY -
Tel. (0523) 944411 - Fax (0523) 941885 - e_mail: [email protected]
MDE142E0 2/60 06/04/04
INDEX
1. FOREWARD 6
2. ACTUATOR FUNCTIONAL DESCRIPTION 7
3. SYSTEM OPERATING PRINCIPLE 10
4. CONTROL SYSTEM FUNCTIONING 11
4.1. Control function 11
4.1.1. Position regulator and speed control 11
4.2. General function 12
4.2.1. Selection between turn clockwise to close or anti-clockwise to close 12
4.2.2. Stroke limit electronic setting 12
4.2.3. Open loop operation 12
4.2.4. Direct / Reverse action 12
4.2.5. Position failure (Jammed) 12
4.2.6. Opening high speed operation 12
4.2.7. ESD operation 12
4.2.8. Internal temperature monitoring 12
4.2.9. Accumulator nitrogen leakage 12
4.2.10. Motor/pump control 13
4.2.11. Language selection 13
4.2.12. Maintenance instruction 13
5. REMOTE CONNECTIONS 14
5.1. Analogue input / output 14
5.1.1. Position signal request (input) 14
5.1.2. Process valve position signal (output) 14
5.1.3. Oil level transmitter (output) 14
5.1.4. Oil pressure transmitter (output) 14
5.1.5. Oil temperature transmitter (output) 14
5.2. Digital input / output 14
5.2.1. ESD control (input) 14
5.2.2. Monitor relay (output) 14
5.2.3. Auxiliary relays (output) 14
6. LOCAL OPERATOR INTERFACE 15
6.1. Local operator interface features 16
6.2. Variables, alarms and warnings visualisation 18
6.3. Configuration options 19
6.3.1. Actuator set-up 19
6.3.2. Name plate 19
6.3.3. Valve data 19
6.3.4. Maintenance 19
6.4. Entering the view mode 20
6.5. Entering the set-up mode 20
6.6. Exit from view and set-up mode 20
7. SET-UP MENU 22
8. VIEW MENU 24
9. SET-UP ROUTINES 26
9.1. Stroke limits 26
9.2. Purge 26
9.3. Positioner 27
9.4. ESD Control 27
9.5. Local control 28
9.6. OUTPUT Relays 28
9.6.1. Monitor relay 28
9.6.2. Auxiliary output relays 28
9.7. Fail safe 29
MDE142E0 3/60 06/04/04
9.8. Output 4-20 mA 30
9.9. Interlock 30
9.10. Miscellaneous 30
9.10.1. Time and date 30
9.10.2. Factory setting 31
9.10.3. Pump 31
9.10.4. Valve jammed (time) 31
9.10.5. Vem calib. 32
9.11. VALVE DATA ROUTINES 33
9.11.1. Tag name 33
9.11.2. Serial number 33
9.12. MAINTENANCE ROUTINES 33
9.12.1. Set password 33
9.12.2. Clear alarm log 33
9.12.3. Clear recent data log 34
9.12.4. Set maintenance date 34
9.13. Example of set-up routine (Local Control) 35
10.VIEW ROUTINES 36
10.1. Actuator set-up routines 36
10.2. Name plate routines 36
10.3. Valve data routines 36
10.4. Maintenance routines 37
10.5. Example of view routine 38
11.FACTORY TEST CONFIGURATION 39
11.1. Actuator set-up menu 39
11.2. Name plate menu 40
11.3. Valve data menu 40
11.4. Maintenance menu 40
12.EHAS SYSTEM DATA 41
12.1. Working condition 41
12.2. System performances 41
12.3. Electrical and hydraulic features 41
12.4. Hydraulic oil characteristics 41
12.5. Valve torque requirement 41
12.6. Actuator performances 41
13.INSTALLATION INSTRUCTIONS 42
13.1. Assembling the actuator on the valve 42
13.2. Setting of the mechanical stroke limits 43
13.3. Instruction for start up 43
13.3.1. Hydraulic controls 43
13.3.2. Electric connections 43
13.3.3. Start up 45
13.3.4. Purge operation 45
14.MAINTENANCE 46
14.1. Standard maintenance 46
14.2. Special maintenance 46
15.TROUBLE-SHOOTING 46
15.1. The display is off when the actuator is powered 46
15.2. The electronic control logic works but there is an alarm 47
16.MAIN COMPONENT PART LIST TABLE 49
16.1. Control cabinet 50
16.2. Hydraulic cylinder /quick exhaust valve 51
16.3. Actuator spring cartridge) 52
MDE142E0 4/60 06/04/04
16.4. Actuator scotch yoke mechanism 53
16.5. Position transmitter and limit switch assembly 54
16.6. Hydraulic Control Unit (HCU) 55
16.7. Motor Control Unit (MCU) 56
17.OPERATING DIAGRAM 57
17.1. Hydraulic operating diagram SLASDOO2 57
17.2. Wiring diagram SE 89B-173A/B 58
MDE142E0 5/60 06/04/04
NOTES:
.................................................................................................................................................................
.................................................................................................................................................................
.................................................................................................................................................................
.................................................................................................................................................................
.................................................................................................................................................................
.................................................................................................................................................................
.................................................................................................................................................................
.................................................................................................................................................................
.................................................................................................................................................................
.................................................................................................................................................................
.................................................................................................................................................................
…………………………………………………………………………………………………………..
…………………………………………………………………………………………………………..
…………………………………………………………………………………………………………..
…………………………………………………………………………………………………………..
…………………………………………………………………………………………………………..
…………………………………………………………………………………………………………..
…………………………………………………………………………………………………………..
…………………………………………………………………………………………………………..
REVISION LIST
0 18/10/2002 Issue document R.Z A.A.
Rev. Date Description Prepared Approved
MDE142E0 6/60 06/04/04
1. FOREWARD
The EHAS are Electro-Hydraulic Linear Actuator series fitted with a new electronic units used to control
the position of modulating linear valves in accordance with an external signal called ‘’position
request’’.(REQ)
The actuators system is consisting of an electro-hydraulic power unit (HPU) which generates the
hydraulic pressure to fill an hydraulic accumulator (HA) in order to control, by means a microprocessor
unit (MCU) and a solenoid valve control unit (HCU), the position of an hydraulic cylinder (HLA)
connected by a suitable pedestal to a modulating valves (MV).
The units are provided with display and non intrusive push-buttons/selector to allow local actuator
control, configuration and diagnosis operations. A powerful, memory resident, diagnostic function
monitor the correct operation of the actuator and generates an alarm when failure occurs.
HPU
Hydraulic Power Unit
HCU
solenoid valve control unit
MCU
Microprocessor Control Unit
OLGAS
Hydraulic Spring return
Actuator
MV
Modulating Valve
PT
Position Transmitter
Valve position request (REQ)
Electric supply
Valve position (FB)
EHAS
push-buttondisplay
Hydraulic HA Accumulator
MDE142E0 7/60 06/04/04
2. ACTUATOR FUNCTIONAL DESCRIPTION
The EHAS actuators are equipped with the following main components:
1. Oil pressure transmitter
2. Oil temperature transmitter
3. Oil level transmitter
4. High pressure filter with clogging indicator junction box
5. Oil reservoir
6. Hydraulic accumulator
7. Quick opening piloted valve
8. Transmitter terminal block enclosure
9. HCU Hydraulic solenoid valves Control Unit
10. Hydraulic power unit electric motor
11. MCU local interface operator with pushbutton/selector and display
12. Hydraulic power unit pump
13. Hydraulic suction filter
14. Actuator position transmitter/limit switches enclosure
15. MCU Microprocessor Control Unit with terminal block enclosure
16. Hydraulic power unit cabinet
MDE142E0 8/60 06/04/04
The actuator functional description is referred to the simplified schematic reported here under:
The electric motor (956) drives the pump (542) which send the pressurised oil, through the filter (361), to
the hydraulic accumulator (34). When the pressure value reaches the set point value of the logic valve
(395A), the discharge valve (998B) opens and the oil flow back the reservoir (555), at very low pressure
value.
When the pressure value, due to the actuator movement, slow down at the logic valve lower set point, the
discharge valve closes and the oil is send again to the hydraulic accumulator.
The movement and the direction of the motion occurs by controlling the oil pressure value of the cylinder
chamber of the OLGAS ACTUATOR.
The speed of operation is controlled by the MCU (954) in function of the difference (ERROR) between
the actuator position signal EPT (41), called feed-back (FB) and the position request signal (REQ) as
described on par.4.2.1.
MDE142E0 9/60 06/04/04
a) Opening operation
When the request signal requires to move the valve in opening direction (see Direct/Reverse action on
par. 4.2.2) the MCU energise the solenoid valve (401B), which opens and reduces the cylinder chamber
pressure value until the spring force start to move towards opening direction.
b) Closing operation
When the request signal requires to move the valve in closing direction (see Direct/Reverse action on par.
4.2.2) the (MCU) energise the solenoid valve (401A) which opens allowing the oil flows from the
accumulator to the cylinder chamber, the pressure value in this chamber increases and the piston force
compress the spring and moves the actuator towards closing direction.
c) Stop in position
When, during the movement, the position of the actuator approaches the requested position, the MCU
adjust the pressure in the cylinder chambers to minimise the speed of operation.
As soon as the position of the actuator reaches the range of permitted error (DEAD BAND), the MCU de-
engines all solenoid valves causing the actuator to stop.
d) Opening high speed operation
When the 4-20 mA signal (REQ) change from low to higher value with a variation speed higher than 32
mA/sec, the MCU energise the solenoid valve (399) which allows that the pilot valve (998B) opens
discharging quickly the cylinder chamber pressure. In this condition the actuator speed reaches a speed of
180°/sec (equal to 0,5 sec from fully close to fully open position).
e) ESD operation
When a dry contact in the control room is opens (ESD) the MCU ignore the 4-20 mA signal (REQ) and
moves the actuator to the open position with a speed of 13-15°/sec (equal to 6-7 sec from fully close to
fully open position).
MDE142E0 10/60 06/04/04
3. SYSTEM OPERATING PRINCIPLE
The MCU drives the HCU solenoid valves and positions the valve in accordance with an external signal
called ‘’position request (REQ)’’. The function is performed by the continuous comparison of the ‘’valve
position (FB)’’ and (REQ) signals: if they are different the solenoid valves are driven so as to move the
actuator to the position indicated by the position request signal.
The following figure represents the block diagram of the positioning system.
The modulating operation is performed as follows:
-if the (REQ) signal decreases in comparison with the ‘’present valve position’’ signal, the position
regulator generates the voltage (see paragraph 4.2.1) that, through a power module, will power the
coil of the proportional solenoid valve, in close direction, to decrease the position and close the valve.
- if the (REQ) signal increases in comparison with the ‘’present valve position’’ signal, the position
regulator generates the voltage that, through a power module, will power the coil of the proportional
solenoid valve, in open direction, to increase the position and open the valve.
if the “ position request variation ” is greater than 32 mA/sec., the high speed solenoid valve is
energised to open the valve in a short time.
When a dry contact in the control room is opens (ESD) the MCU cut-off the 4-20 mA signal (REQ)
and moves the actuator to the open position with an established speed (equal to 6-7 sec from fully
close to fully open position).
When the (ESD) contact is restored, the control returns to the (REQ).
If the (REQ) signal do not change for 15 minutes the MCU stop the motor. The motor will restart as
soon as the (REQ) signal change or when the accumulator pressure slow down to the minimum and
the pressure switch (PS) change over its contact.
a pressure switch monitors the hydraulic pressure and generates an alarm if the pressure do not
increases within an established time
in case of loss of 3ph 380 V power supply the actuator remains in service until the hydraulic pressure
is available
in case of UPS supply failure the actuator remains in stay-put.
High speed
control
HPU control
ESD CONTROL
open
close
Valve
position
signal (FB)
POSITION LOOP
PS
PT
Position Transmitter
HCU
Proportional solenoid
valves
OLGAS
Spring return Hydraulic
Actuator
MCU
Microprocessor
Electronic Control
Position request (REQ)
Power supply 3ph 380 V
PIPELINE
MODULATING
VALVE
POSITION RE-TRANSMISSION
AUTOMATIC NOT AVAILABLE
OR WARNING
HPU
Hydraulic Power Unit
EHAS BLOCK DIAGRAM
High speed
solenoid valve
END of TRAVEL CONTACTS
Supply from UPS 230 V
MDE142E0 11/60 06/04/04
4. CONTROL SYSTEM FUNCTIONING
4.1. Control function
The functioning of the control system can be described by referring to the block diagrams represented on the
following pages.
Every block represents a function relevant to pressure and position control of the actuator. The function of each
block is detailed as follows:
4.1.1. Position regulator and speed control
The new requested valve position value, is compared (actuator position loop) with the present valve position
(FB). The difference between the two values (position error) is processed by the position regulator which sends
an opening request signal to the proportional valve positioner. The request signal value is used to generate a
variable voltage to open accordingly the proportional valves in order to move the valve process to the correct new
position at variable speed operation.
The voltage generated by the proportional valve positioner and
applied to the coils, is proportional to the position error, it means
that the spool position and then the oil flow and actuator speed,
change in function of the applied voltage. The greater is the position
error, the greater is the actuator speed and vice-versa.
The opening value of the proportional valves are verified
(proportional valve position loop) with the real value continuously
through the position transmitter (PPT).
The regulator utilises a P (proportional) algorithm and its Control
band is adjustable independently for both directions of operation.
Furthermore two speed gains (k and k2) allows to establish the
suitable speed operation. Dead band, and Max speed, can also be
adjusted. The sign of the position error represents the direction
where the valve should move and it is used to select the coil of
solenoid valve that should be powered.
When the position error is greater than the pre-set position control band, the coils of the solenoid valves are
powered by the maximum voltage. When the position error is below the pre-set position control band value, the
coils of the solenoid valves are powered by a voltage proportional to the position error. When the position error is
smaller than the pre-set dead band value, the voltage applied to the coils of the solenoid valves is zero and the
actuator remains in the present position.
proportional
control band (P) (%)
dead band
position error %
0 %
max. speed
Actuator
speed
Speed / position error relation
k2
k
OPEN LOOP
CONTROLS
Internal
POSITION
REQUEST
(REQ)
ACTUATOR
FUNCTIONS
CONTROL
LOOP
CONTRO
L
POWER
SUPPLY
OUTPUT
RELAYS
DISPLAY
and LED’s
SOLID STATE
POWER
SWITCHES
POSITION
REGULATOR
VALVE
POSITION
(FB)
+
-
3-ph MAIN
POWER
SUPPLY
HCU
Proportional
solenoid valve
Motor control
PS
Pressure
Switch
PT
Position
Transmitter
POSITION LOOP
Motor
thermostat
MCU
BLOCK DIAGRAM
Output
contacts
LOCAL
OPERATOR
INTERFAC
E
LOC/OFF/REM
OPEN
CLOSE
LOCAL
SETTING
OUTPUT
4-20mA
Position re-
transmission
RS232
serial port
INPUT
4-20mA
Position
request
input
ESD
input
OPTO-
COUPLED
INPUT
High speed
solenoid
valve
UPS supply
230 V
SOLENOID VALVE LOOP
PPT
Proportional
valve trans.
MDE142E0 12/60 06/04/04
4.2. General function
4.2.1. Selection between turn clockwise to close or anti-clockwise to close
Via local operator interface it is possible to select between the following: “actuator turn CLOCKWISE or stem OUT
for linear actuator, (CW/OUT) to close” or “actuator turn counter clockwise or stem IN for linear actuator
(CCW/IN) to close”.
4.2.2. Stroke limit electronic setting
The stroke limits of the hydraulic linear actuator are performed by means of the local interface operator (see relevant
paragraph). This operation must be done after the mechanical setting.
4.2.3. Open loop operation
A local 3 position selector switch (Local/Off/Remote), of the local operator interface, permits the opening of the
position control loop and the direct control of the actuator through local Open/Close/Stop commands (MANUAL
mode). The STOP command is always available , both in LOCAL and ins REMOTE
4.2.4. Direct / Reverse action
The configurable Direct/Reverse action parameter, allows to choose the action of the position regulator in function
of the position request signal.
If direct action was configured, the 4 mA position request signal corresponds to closing request and the 20 mA
corresponds to opening request.
Vice versa if reverse action was configured, the 4 mA signal requires opening and the 20 mA requires closing.
The Direct / Reverse parameter does not affect the 4-20 mA position re-transmission signal. In fact, 4 mA
corresponds always to closed position and 20 mA to open position.
4.2.5. Position failure (Jammed)
If the error of position (difference between ‘’present position’’ and ‘’internal position request’’) is greater than
4 %, but the position value does not change within a configurable time, an automatic cut-off of the control circuit
occurs and an alarm is set. The time can be configured at a value from 1 to 250 sec. The control is active when the
MCU works in REMOTE (AUTO).
4.2.6. Opening high speed operation
When the 4-20 mA signal (REQ) change from low to higher value with a variation speed higher than 32 mA/sec (for
minimum 3,2 mA) , the MCU energise a third solenoid valve which allows that the pilot valve opens, discharging
quickly the cylinder chamber pressure. In this condition the actuator speed reaches a speed of 180°/sec. As soon as
the actuator position reaches 90% opening, the high speed solenoid valve is de-energised, the operating speed slow
down and the movement is controlled by the positioner solenoid valve until the new requested position.
4.2.7. ESD operation
When a dry contact, in the control room, opens (see option D1 of the SE89B-173A terminals C4-C1) the actuator, is
configured to override any existing command and drives the valve to the fully open in 6-7 sec
4.2.8. Internal temperature monitoring
The system are designed to work from -30° C to 60 °C.
If the internal temperature is greater than 80°C or lower then -35°C, a warning is set.
If the internal temperature is greater than 90°C or lower then -40°C, an alarm is set. .
4.2.9. Accumulator nitrogen leakage
The actuator is provided with a pressure switch that contact opens when the hydraulic pressure drop down to an
adjustable pressure threshold. The pressure threshold should be set at least 5 bars below the minimum pressure fixed
by the “adjustable relief valve” (see par. 5.3).
The pressure switch contact is read by the MCU that switches on the hydraulic pump electrical motor. When the
pressure is increased of about 10 bars the pressure switch contact closes.
The MCU measures the time between the opening and the closing of the pressure switch contact .
If the time is 50% lower than the variable “N2 REF TIME ” a “ LOW N2 “ warning, is send to advise that the
Nitrogen leakage ( N2 ) is occurred.
The measure is performed only if the local selector is in REMOTE, the hydraulic pump motor is “on” and the
position request signal (REQ)remains constant.
MDE142E0 13/60 06/04/04
The measure is not done during the first cycle after the power-up, or if the position request signal changes during the
measuring time.
The above warning condition is signalled only by the red LED (alarm/warning) located on the local operator
interface.
4.2.10. Motor/pump control
The motor of the hydraulic pump is controlled by the MCU. The following operating mode can be configured via
local operator interface:
1) OFF: electrical motor always off
2) ON: electrical motor always on
3) AUTO: - in LOCAL the electrical motor is always running
- in OFF the power of the electrical motor is switched off in 30 sec. It is switched on when the local selector is
moved to LOCAL or REMOTE
- in REMOTE the electrical motor switches off, if the variation of the position request signal is less than 0.5%
for 15 min. It is switched on if the position request signal changes or if the pressure switch contact opens
If the pressure switch is still open after 10 min. from the start of the motor pump, an alarm is generated
(HYDRAULIC PUMP)
4.2.11. Language selection
To visualise the messages of the display the operator can choose between two available languages (Italian and
English).
4.2.12. Maintenance instruction
A large amount of data is stored in the MCU memory and it is available for future analysis or to assist the operator
in the maintenance program. The maintenance menu includes the set password routine, to read the maintenance date
operation, to clear recent data log and to set the next maintenance date.
MDE142E0 14/60 06/04/04
5. REMOTE CONNECTIONS
The EHAS system are provided of digital and analogue input / output, available from the terminal board, suitable for
the remote control as described in the following:
5.1. Analogue input / output
5.1.1. Position signal request (input)
The position request signal must be 4-20 mA, coming from an external generator or process controller. Impedance
250 . The input is provided of a galvanic insulation. The connection must be done by a screened cable.
Note: when the position request signal increases with a variation higher than 32 mA/sec the MCU controls the
opening high speed operation as described on par.2.
5.1.2. Process valve position signal (output)
The process valve position signal, internally generate by the MCU, is available also in case of electric supply failure,
but with the external 24 Vdc, 400 mA supply active.
The output signal is 4-20 mA, internally provided with galvanic insulation. The connection must be done by a
screened cable.
5.1.3. Oil level transmitter (output)
One oil level transmitter allow to check continuously at a distance the level of the hydraulic oil in the reservoir. The
transmitter has a chain of red sensors with 10 mm apart, connected wit an electronic reading device which gives a
linear and continuous 4-20 mA output signal. The connection must be done by a screened cable.
5.1.4. Oil pressure transmitter (output)
One oil pressure transmitter allow to check continuously at a distance the pressure value of the hydraulic accumulator.
The transmitter, piezoresistive type has a range of 250 barg and an output signal of 4-20 mA.The connection must be
done by a screened cable.
5.1.5. Oil temperature transmitter (output)
One oil temperature transmitter allow to check continuously at a distance the temperature of the hydraulic oil the The
transmitter is connected with an RTD sensor PT100 type, has a range of 0 to 100° C, and an output signal of 4-20 mA.
The connection must be done by a screened cable.
5.2. Digital input / output
5.2.1. ESD control (input)
An ESD (Emergency Shut Down) signal can be connected to the actuator to override any existing command (see ESD
SETUP) and to drive the actuator / process valve in a predetermined position (move to open, move to close, move to
% and stay in place), at a programmable speed operation.
The ESD command is opto-coupled. The circuits associated to the input can be supplied by an external 20-125Vdc or
20-120Vac (50/60Hz).
The signal level are the following:
Ø minimum ON signal >20Vdc/Vac
Ø maximum ON signal < 125Vdc or 120Vac
Ø maximum OFF signal < 3Vdc/Vac
Ø current drawn from ESD controls < 15mA.
5.2.2. Monitor relay (output)
A voltage free change over contacts of the monitor relay are available. It indicates that there is a problem or condition,
into the DHAP system, which prevents the automatic control of the process.
The conditions that cause the switch over of the relay are listed in the relevant paragraph.
Contact rating: max voltage 250Vac/30Vdc; max. current 5A
min voltage 5Vdc; min current 5mA.
5.2.3. Auxiliary relays (output)
The voltage free contacts of 5 latching relays are available. The status (make or break) and the conditions that cause
the switching of the relay can be viewed and configured by using the “VIEW and SET-UP” features. The status of the
latching relays is immediately updated as the associated conditions to change occur. Moreover, the status of the above
contacts are cyclically updated
MDE142E0 15/60 06/04/04
Contact rating: max voltage 250Vac/30Vdc; max. current 5A
min voltage 5Vdc; min current 5mA.
6. LOCAL OPERATOR INTERFACE
The following functions are available by the MCU local operator interface:
Ø actuator control
Ø system configuration
Ø system status visualisation
The below figure describes the function of each component of the local operator interface.
MDE142E0 16/60 06/04/04
6.1. Local operator interface features
Numeric display to indicate the present
process valve position
in % of the opening
Three LED’s to indicate the actuator status
according to the following logic:
green ON/ red OFF: the actuator is stopped
in open position
green OFF/ red ON: the actuator is stopped
in closed position
green OFF/ red flashing: the actuator is
running in closing direction
green flashing/ red OFF: the actuator is
running in opening direction
green ON/ red ON: the actuator is stopped
in intermediate position
yellow ON: alarm
yellow flashing: warning
Local controls: OPEN/YES, CLOSE/NO, and
STOP push buttons.
The STOP push-button resets any existing
command and it is active both in local and in
remote.
If the 3-position selector is in LOCAL, the
OPEN / YES, and CLOSE /NO push buttons
work as
OPEN and CLOSE commands.
If the 3-position selector is in REMOTE or in
OFF, the OPEN / YES and CLOSE / NO
push-
buttons work as YES and NO to answer at the
prompt (next? OK? view?, change? exit?) of the
alphanumeric display.
In OFF, the OPEN / YES and CLOSE / NO push
buttons allow to move in the menu, to view and
change actuator configuration or to scroll the list
of variables, status, and alarms.
In REMOTE, the above push buttons allow
scrolling the list of variables, status, and alarms,
but viewing or changing actuator configuration
cannot be made.
Alphanumeric display: during normal operation the
alphanumeric display shows the present status (NORMAL,
ESD ON, ALARM, WARNING), the 3-position selector status
(LOCAL, OFF, REMOTE), the position request signal (R
xx,x%) and the actuator action (OPEN, OPENING, CLOSED,
CLOSING, STOP). If the local selector is in OFF or
REMOTE, pressing the YES push-button it is possible to
scroll the below list of variables and alarms:
main voltage supply
temperature inside the actuator enclosure
time
date
alarm list
warning list
The warning condition occurs when a variable reaches a
critical value and/or a maintenance action is required, but the
actuator control functions are still available. The alarm
condition occurs when a variable is out of the acceptable range
and the actuator control functions are not available
The alarm and warning lists contain the present alarms and
warnings
. When the fault condition disappears, also the
corresponding alarm or warning disappears from the list. A
reset routine is provided to clear the type of alarm / warning
that are memorised (jammed valve, etc.).
3-position selector to set the following operation modes:
LOCAL: for local control only
OFF: no control is active but the actuator is still
connected to the mains
REMOTE: for regulating service only
CLOSE
STOP
OPEN
MDE142E0 17/60 06/04/04
The following drawing shows the use of the OPEN / YES, CLOSE / NO and STOP push buttons in function of the
local selector position.
Press
YES and STOP
simultaneously
to enter VIEW and
SETUP menus
only OPEN,
CLOSE and STOP
controls available
ALPHANUMERIC
DISPLAY
Press
YES
to answer at the
prompt ( cont?)
Place the
3-position selector in
LOCAL or press YES
and NO simultaneously to
exit from VIEW and
SETUP MENUS
to
VIEW
and
SETUP
MENUS
VIEW and SETUP MENUS
NORMAL LOCAL
R 37,5 %
37.5 %
NORMAL OFF
R 37,5 %
next ?
37.5 %
NORMAL REMOTE
R 37,5 %
next
?
37.5 %
=
OPEN / YES push-button
= CLOSE / NO push-button
= STOP push-button
LOCAL OFF REMOTE
VARIABLE,
ALARM
and
WARNING
LISTS
Press
NO
to return to
NORMAL OFF / REMOTE
Actuator control
MDE142E0 18/60 06/04/04
6.2. Variables, alarms and warnings visualisation
The following drawing shows the use of the OPEN/YES, CLOSE/NO and selector to visualise the VARIABLE,
LIST OF AVAILABLE ALARMS LIST OF AVAILABLE WARNINGS
CONFIGURATION (configuration error) THERMOSTAT (motor over temperature)
INT.TEMPERATURE (internal temperature out of the limits) INT.TEMPERATURE (internal temperature near limits)
MAIN VOLTAGE (supply voltage out of the limits) MAIN VOLTAGE (supply voltage near limits)
HARDWARE (hardware error) PUMP STARTS (pump starts > 1,000,000)
POSITION SENSOR (feed-back failure) MAINTENANCE REQ (maintenance request)
JAMMED IN CL (jammed valve in closing) N2 REF TIME (accumulator Nitrogen pressure value too low)
JAMMED IN OP (jammed valve in opening) COMP. LEAKAGE (leakage on hydraulic components)
REQUEST SIGNAL (set-point failure) STROKE LIMITS (uncorrected stroke limits)
VEM1 SENSOR (VEM1 Hall sensor failure)
VEM2 SENSOR (VEM2 Hall sensor failure)
LOW PRESSURE (hydraulic pressure supply failure)
PUMP FAILURE (hydraulic pump failure)
NOTE: the alarm indication could be reset only after having removed the condition that causes the malfunctioning
(see relevant instructions on the table of the TROUBLE-SHOOTING paragraph.
YES
ALARM # 1
next?
................….
...............….
……………
……………
ALARM # n next ?
RESET ALARM OK?
YES
WARNING # 1
next?
.................…….
................……..
WARNING # n next?
RESET WARNING OK?
YES
NO
3-POSITION SELECTOR
Press YES or NO to answer at
the prompt (OK?, view?, next?)
Variable and alarm list
NORMAL LOCAL
R 37,5 %
37.5 %
NORMAL OFF
R 37,5 % next
37.5 %
NORMAL REMOTE
R 37,5 % next
37.5 %
= pulsante OPEN / YES
= pulsante CLOSE / NO
POSITION ERROR
%
next?
VEM1/VEM2 POSITION. % / % next?
SUPPLY VOLTAGE. V-Hz next ?
INT. TEMPERATURE xx °C next ?
TIME hour/min/sec next ?
DATE day/month/year next ?
ALARMS none next ?
WARNINGS none next ?
YES
YES
NO
YES
NO
LOCAL OFF REMOTE
YES
YES
YES
NO
=
OPEN / YES push-button
= CLOSE / NO push-button
= STOP push-button
MDE142E0 19/60 06/04/04
6.3. Configuration options
The DHAP system can be totally configured from the local interface by means of a series of menus that can be
selected from the alphanumeric display. The operator is guided through the different displays by answering YES or
NO at the appropriate prompt (change? OK?, view?, next?, etc.) present in the right corner of the lower row of the
alphanumeric display.
To access to menus: set the local selector in OFF and then simultaneously press OPEN/YES and STOP. The
alphanumeric display will now show the present language. Press YES if the language is OK, press NO to scroll the
list of available languages and then press YES to select.
After having chosen the language, the next step is the selection among view and set-up mode. Use view mode to
seethe actuator configuration, and use set-up mode to change the present configuration. Unauthorised entry to
the set-up mode is prevented by a 4 alphanumeric character password. The actuator is supplied by BIFFI with the
default password “ 0 0 0 0 “.
Once the correct password has been entered, the actuator parameters can be configured. There is also the opportunity
to change the present password to a new value by the “set password" routine in the maintenance menu. After having
entered the new password, the old one ceases to be valid, so it is important to record the password in a secure location
for future retrieval.
The configuration functions (view and set-up mode) are grouped in 4 main menus: Actuator set-up, Name plate
and Maintenance.
6.3.1. Actuator set-up
It includes the routines that allow the actuator to be configured according to the requested control mode and to the
valve that it is mounted on.
List of routines:
q stroke limits q ESD control q fail safe q miscellaneous
q purge q local controls q output 4-20mA q
q positioner q output relays q interlock q
6.3.2. Name plate
It includes a series of data to identify the actuator characteristic, service, and utilisation mode. The data are entered by
the actuator manufacturer and can only be viewed.
List of routines:
q serial number
q actuator type
q nominal thrust/torque
q supply voltage
q motor data
q test date
q wiring diagram
q Oil type
q HW / SW version
6.3.3. Valve data
It includes a series of data relevant to the valve. The valve manufacturer and end user should enter the data.
List of routines:
q tag name q serial number
6.3.4. Maintenance
It includes a large amount of information relevant to diagnostic and historic data to help the operator in case of failure
or in maintenance operations. Maintenance menu includes also the set password routine.
List of routines:
q set password
q clear alarm log
q clear operation log
q maintenance date
The parameters appear on the alphanumeric display in the same order both in view and set-up mode. At the end of
each routine the program automatically returns to the beginning of the routine, and the operator can choose to re-enter
by YES or to move to a next routine by NO.
MDE142E0 20/60 06/04/04
6.4. Entering the view mode
Before commissioning the actuator on the valve, the existing configuration should be checked. The parameters are
configured in factory, according to a standard setting or alternatively to customer requirements. In view mode, no
password is requested, but no change of parameters can be made.
Ensure the electrical main power is applied.
Move the 3-position selector to OFF and then press at the same time OPEN/YES and STOP.
The display shows the present language. Press YES to confirm or press NO to scroll the list of available languages.
Press YES to select the new language.
Press NO to scroll the list of available menus (ACTUATOR SET-UP, NAME PLATE, VALVE DATA,
MAINTENANCE) and then press YES to select the desired menu.
Press NO to scroll the list of available routines and press YES to select the routine where the parameter to be
changed is located.
Press NO to scroll the list of parameters and press YES to view the value.
6.5. Entering the set-up mode
To change the existing settings or to set the stroke limits it is necessary to enter the correct password before being able
to make changes.
Ensure the electrical main power (or the external auxiliary supply) is applied.
Move the 3-position selector to OFF and then press simultaneously OPEN/YES and STOP.
The display shows the present language. Press YES to confirm or press NO to scroll the list of available languages.
Press YES to select and to confirm the chosen language.
Press NO when the message is “VIEW MODE OK? ”. Press YES to answer at “ENTER PASSWORD OK?"
Enter password. Enter one digit at a time. Press YES if digit is correct, press NO to scroll the list of available
characters and then press YES when the character is correct. Enter 4 digits. After having entered the last digit, the
microprocessor checks the password. If it is correct the messages “PASSWORD CORRECT” and then “SET-UP
MODE OK?” appear. Press YES.
Press NO to scroll the list of available menus (ACTUATOR SET-UP, VALVE DATA, MAINTENANCE) and
press YES to select the desired menu
Press YES to scroll the list of available routines and press YES to select the routine where the parameter to be
changed is located.
Press YES and NO to answer at the prompt on the display and to change the parameter.
If password is not correct the message “PASSWORD WRONG” appears and set-up mode will not available.
All settings are automatically saved to a non-volatile memory and retained also if the electrical power is removed
from the actuator.
All systems are configured, before being shipped, with a standard default setting unless alternatives have been
requested with the order. In case of difficulty encountered during commissioning, the default setting can be re-
installed by the appropriate function present in the routine ”miscellaneous” of the actuator set-up menu. The actuator
returns to its original type configuration and commissioning can begin again, adjusting the original configuration
with the factory test settings (see par.14).
6.6. Exit from view and set-up mode
The following conditions cause to exit from view and set-up mode:
move the 3-position selector to LOCAL or REMOTE
answer YES when the display asks “EXIT OK? ”
press simultaneously YES and NO
automatic exit after 5 minutes without any parameter change or view
remove the electrical power from the unit
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Tyco BIFFI OLGAS-M 35-2000-100-OP Installation Instructions And Maintenance Manual

Type
Installation Instructions And Maintenance Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI