Cooper Lighting Ethernet Interface Module, EIM Installation guide

Type
Installation guide
INS #
Installation Instructions
Model# EIM
Ethernet Interface Module
Module d’interface Ethernet
Del software de interfaz de Ethernet
General Information
The Ethernet Interface Module (EIM) is a device that
makes communications from a PC to a Greengate
panel or network of panels possible over an Internet
connection. The PC can be local within the building
complex or located at a remote location.
The Ethernet Interface Module (EIM) converts data
packets sent over the TCP/IP connection to RS-232
communications. One Ethernet Interface Module (EIM)
is needed per Lighting Control Network unless using the
VisionTouch software. If VisionTouch software is being
used, it is recommended that an Ethernet Interface
Module be dedicated to VisionTouch use. Please contact
technical support for further details. If panels are not
networked, one Ethernet Interface Module (EIM) will be
needed per panel. The Ethernet Interface Module (EIM)
Device Package comes with the following:
Ethernet Interface Module (EIM) device
AC Power Adapter
Cable Package (Contains a crossover cable for
configuration, one phone style serial cable and adapter
head for connection to the lighting panel.)
Status LEDs
RS232 Port
RJ54 Ethernet Port
Power
Input
Reset Button
Typical Layouts
The Ethernet Interface Module may be used to allow
access only from within the internal building LAN or
may also be set up by a qualified network administrator
for external access through the internet. The following
pictures depict these types of configurations.
ROUTER
Lighting Control Panel Connected
to Lighting Control Network
TCP/IP Internet Connection from a Remote Location
Ethernet
Interface
Module
(EIM)
Ethernet Interface Module
Private IP Address: 10.0.0.1
EIM Port Assigned: 10001
Lighting Software set
up to talk to lighting
control panels using
Firewall IP Address
64.30.7.31 and
Firewall
Port 10001.
Firewall Public IP Address: 64.30.7.31
Firewall Port for EIM: 10001 - This
should be the same port number as
the port assigned in the EIM
Firewall Port 10001 is assigned to
direct all traffic coming to this port to
private IP Address 10.0.0.1
Remote Computer
with Lighting Software
INTERNET
FIREWALL
HUB/SWITCH
TCP/IP Intranet Connection from a Local Location
Lighting Control Panel Connected
to Lighting Control Network
Ethernet Interface
Module (EIM)
HUB/
SWITCH
Local Computer with
Lighting Software
Ethernet Interface Module Private IP
Address: 10.0.0.1
EIM Port Assigned: 10001
Lighting Software
set up to talk to
lighting control
panels using EIM IP
Address 10.0.0.1
and EIM Port 10001
NOTE: In this scenario, it is not necessary
to access the external, public internet. The
Ethernet Interface Module may be
accessed directly.
2
Customer Obligations
Ethernet Interface Module
Customer Obligations
The Ethernet Interface Module (EIM) must be configured by
a qualified network administrator. The customer must also
provide an IP address for each Ethernet Interface Module
(EIM) Device being used and be able to support TCP/IP
communications protocol. It may be necessary for the site’s
network administrator to perform firewall programming to
allow for remote access to the device depending on system
setup and desired computer access.
Ethernet Interface Module Configuration
In order for the Ethernet Interface Module (EIM) to work
properly with your application, it will be necessary for the
network administrator to set up the Ethernet Interface
Module (EIM) device(s). Please follow the steps outlined in
this instruction in order for the unit to communicate properly
with the lighting control system. Greengate recommends
using the built-in configuration web server pages in the unit
as the method of configuration.
The instructions that follow describe the setup of the device
using the web server pages.
The following instructions describe what methodology is
used to configure the unit. Regardless of what the important
settings that must be configured, include the following:
1. IP Address must be statically assigned
2. Subnet mask must be set
3. Default Gateway Address must be assigned
4. The IP Port must be configured with a port number.
Port # 10001 is usually an unused port that may be
assigned.
5. The serial settings must be configured properly per the
instructions for communication to the lighting control
network.
Failure to configure the above settings will result in the
failure of the device to communicate with the lighting
control system.
Making the Initial Connection
Before you begin the device configuration, it will be
necessary to configure your Network Interface Card
connection to be on the same subnet as the EIM’s
default IP Address. The default address of the EIM is
192.168.127.254 before configuration. To change your
computer’s TCP/IP settings (Windows XP Steps Shown):
1. Disconnect your LAN Ethernet connection cable from
your computer.
2. Access the Windows Control Panel.
3. Select the Network Connections option.
4. Under the LAN and high-speed internet option, find the
Local Area Connection for your network interface card.
(you may have several listed – if you are not connected
to your building LAN, it will more than likely be the
connection that states “Network cable unplugged”)
5. Right click on the connection and choose Properties
from the pop-up window.
6. In the General tab, scroll down the list of items and
highlight the option for Internet Protocol (TCP/IP).
7. Click on the Properties button.
8. Make note of the current settings so that you can
reconfigure them after configuration is complete.
9. Select the Use the following IP address radial button.
10. Type in an IP Address of 192.168.127.1.
11. Type in the subnet mask 255.255.255.0.
12. Leave all other fields blank.
13. Click on the OK button.
14. Click on the Close button. It may take several seconds
for the new IP settings to take effect.
15. Connect the crossover cable provided from your
computer’s Ethernet port to the EIM’s Ethernet port.
16. Open your internet browser.
1 7. Make certain that cookies are enabled. (please refer
to your internet browser help file for information on
enabling cookies for your browser version).
18. In the browser address window, type in the default EIM
address 192.168.127.254 and press the Enter key.
19. You will be brought to the web console configuration
tool for the EIM.
3
Configuration Settings in the EIM
Ethernet Interface Module
Configuration Settings in the EIM
1. In the menu tree on the left side of the screen, select
the Network Settings folder.
2. In the Network Settings screen, define the following
items:
IP Address
Netmask
Gateway IP Address
IP Configuration – make certain this is set to Static
3. Select the Submit button.
4. In the Network Settings OK screen, select the Home
button.
5. In the menu tree on the left side of the screen, expand
the Serial Settings folder.
6. Select the Port 1 folder within the Serial Settings folder.
7. In the Serial Settings screen, set the following
parameters:
Baud rate: 9600
Data bits: 8
Stop bits: 1
Parity: Even
Flow Control: None
FIFO: Enable
8. Select the Submit button.
9. In the Serial Settings OK screen, select the Home
button.
4
Connecting the EIM to the Lighting Panel
Ethernet Interface Module
10. In the menu tree on the left side of the screen, expand
the Operating Settings folder.
1. Select the Port 1 folder within the Operating Settings
folder.
2. In the Operating Settings screen, set the following
parameters:
Operation Mode: TCP Server Mode
TCP alive check time: 1 minute
Inactivity time: 0
Max Connection: 4
Local TCP port: 10001 recommended (or other port
specified by the IT administrator)
Other fields not identified should be left at default
settings shown
3. Select the Submit button.
4. In the Operating Settings OK screen, select the Save/
Restart button.
11. Once the Save/Restart OK screen appears, close the
web browser. Configuration is complete.
Remember to reset your computers network TCP/IP
settings to their original settings. If you need to reconnect
through the web server pages, you will need to make
certain that your computer is configured to communicate
on the same subnet as the EIM device. Instead of typing in
the default address in the browser address, you will need to
use the unit’s assigned IP Address.
Connecting the EIM to the Lighting Panel
After configuration is complete, it will be necessary to
connect the device to the lighting control panel using the
following steps:
1. Connect the supplied phone style communications
cable to the female 9 pin adapter head provided.
2. Connect the 9 pin adapter head to the Ethernet
Interface Modules serial port.
3. Connect the other end of the phone style
communications cable to the RJ11 style COM port on
the Lighting Control Panel. (on some controllers there
are two RJ11 style connectors. Please connect the
cable to connector labeled RS-232.)
4. Connect one end of the Ethernet cable to the Ethernet
Interface Module RJ45 port and the other end of the
cable to the Ethernet network.
12. Plug in the power adapter supplied with the device.
ADJ
LCD
RSC POWERRSC LINK
ICD LINK
VCC
GND
TCK
TDO
TDI
TMS
JTAG
TEST
16
32
15
31
14
30
13
29
12
28
11
27
10
26
9
25
8
24
7
23
6
22
5
21
4
20
3
19
2
18
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
1CH
17CH
ON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSO
ON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSO
PWR
NET+NET
REM
GND+24
REM
LOCAL
PCI-NET
DIGITA
PCI-NETPCI-NET
RS-232
NET
POWER
LSC
TERM
CAN-TX CAN-RX
RESET
50-022180-02
C
PCI 2005
STATUSNET
54-022180-
ANALOG COMAN1AN2AN3AN4
ANALOGS
CW
TP1
TB2
J10
J9
C43
TB1
LED2
LED6
LED3
SR1
IND1
C29
J8
J4
J5
J2
LED4 LED5
J6
J3
LED1
J7
J1
D6D5D4D3
TB3
HUB
Building LAN
Lighting Control Software
The Ethernet Interface Module (EIM)
can be connected to any controller in the network.
AC Adapter
RS-232 Phone Style
Cable with Adapter
Cable Head
RS-485 Network
to Other Lighting
Control Panels
Ethernet Interface
Module (EIM)
5
Diagnostic LEDs
Ethernet Interface Module
Diagnostic LEDs
There are three LEDs located on the top of the EIM unit.
They can be useful in diagnosing proper operation as well
as troubleshooting if necessary. The EIM will indicate a valid
connection to the Ethernet in the following ways:
The Ethernet LED maintains a solid green color when
connected to a 100 Mbps Ethernet network
The Ethernet LED maintains a solid orange color when
connected to a 10 Mbps Ethernet network
The Ethernet LED will flash when Ethernet packets are
being transmitted or received
LED Name LED Color LED Function
Ready
Red
Green
OFF
Steady ON: Power is on and the EIM
is booting.
Blinking: Indicates an IP Conflict
Steady ON: Power is on and the EIM
is functioning normally
Power is OFF or power error
condition exists.
Link
Orange
Green
OFF
10 Mbps Ethernet Connection
100 Mbps Ethernet Connection
Ethernet cable is disconnected or has
a short.
Tx/Rx
Orange
Green
OFF
Serial port is receiving data
Serial port is transmitting data
No data is being transmitted or
received through the serial port.
Reset Button
There is an onboard reset button located between the
power connection and Ethernet connection on the EIM.
Press the Reset button continuously for 5 seconds to
load factory defaults: Use a pointed object, such as a
straightened paper clip or toothpick, to press the reset
button.
This will cause the Ready LED to blink ON and OFF. The
factory defaults will be loaded once the Ready LED stops
blinking (after about 5 seconds). At this point, you should
release the reset button.
It is possible to limit the reset function for the first 60
seconds from initial power-up by accessing the Basic
Settings screen in the webserver configuration mode and
selecting the “Yes” option for Reset Button Protect.
9
Raccordement du MIE au panneau de commande de l’éclairage
Module d’interface Ethernet
35. À l’écran de confirmation des paramètres de
fonctionnement, sélectionnez le bouton Enregistrer/
redémarrer.
36. Fermez le navigateur Web lorsque l’écran Enregistrer/
redémarrer avec le bouton apparaît. La configuration est
maintenant terminée.
N’oubliez pas de restaurer les paramètres réseau TCP/IP à
leur configuration d’origine. S’il est nécessaire de rétablir la
connexion à partir des pages du serveur Web, assurez-vous
que l’ordinateur est configuré pour communiquer par le
même sous-réseau que l’appareil de MIE. Au lieu d’entrer
l’adresse par défaut du navigateur, il faudra utiliser l’adresse
IP attribuée à l’appareil.
Raccordement du MIE au panneau de com-
mande de l’éclairage
Une fois la configuration terminée, il est nécessaire de
raccorder l’appareil au panneau de commande de l’éclairage
et suivant les étapes suivantes:
1. Branchez le câble série de style téléphonique dans
l’adaptateur femelle à 9 broches fourni.
2. Branchez la tête de l’adaptateur à 9 broches au port
série du module d’interface au Ethernet.
3. Branchez l’autre extrémité du câble de communication
de style téléphonique au port de communications de
style RJ11 du panneau de commande de l’éclairage.
(Certains régulateurs possèdent deux ports de style
RJ11. Il faut brancher le câble au connecteur portant
l’étiquette RS-232.)
4. Branchez une extrémité du câble Ethernet au port RJ45
du module d’interface Ethernet et l’autre extrémité du
câble au réseau Ethernet.
5. Branchez le bloc d’alimentation fourni avec l’appareil.
ADJ
LCD
RSC POWERRSC LINK
ICD LINK
VCC
GND
TCK
TDO
TDI
TMS
JTAG
TEST
16
32
15
31
14
30
13
29
12
28
11
27
10
26
9
25
8
24
7
23
6
22
5
21
4
20
3
19
2
18
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
1CH
17CH
ON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSO
ON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSO
PWR
NET+NET
REM
GND+24
REM
LOCAL
PCI-NET
DIGITA
PCI-NETPCI-NET
RS-232
NET
POWER
LSC
TERM
CAN-TX CAN-RX
RESET
50-022180-02
C
PCI 2005
STATUSNE T
54-022180-
ANALOG COMAN1AN2AN3AN4
ANALOGS
CW
TP1
TB2
J10
J9
C43
TB1
LED2
LED6
LED3
SR1
IND1
C29
J8
J4
J5
J2
LED4 LED5
J6
J3
LED1
J7
J1
D6D5D4D3
TB3
CONCENTRATEUR
LAN de l'immeuble
Logiciel de commande d’éclairage
Le module d'interface Ethernet (MIE) peut être raccordé à
n'importe quel régulateur du réseau.
Adaptateur de CA
Câble de style
téléphonique RS-232
avec tête d'adaptateur
Réseau RS-485
versles autres
panneaux
de commande
de l'éclairage
Interface Ethernet
Module (MIE)
14
Conexión del EIM con el panel de iluminación
Del software de interfaz de Ethernet
14. En la pantalla de aceptación de Configuraciones de
funcionamiento, seleccione el botón Guardar/Reiniciar.
15. Una vez que aparezca la pantalla de aceptación
Guardar/Reiniciar, cierre el explorador web. Ya está
completa la configuración.
Recuerde reestablecer las configuraciones TCP/IP de la red
de su computadora a sus configuraciones originales. Si
necesita volver a conectarse a través de las páginas web
del servidor, deberá asegurarse de que su computadora
esté configurada para comunicarse en la misma subred
del dispositivo EIM. En vez de escribir la dirección
predeterminada en la dirección del explorador, deberá
utilizar la dirección IP asignada de la unidad.
Conexión del EIM con el panel de iluminación
Una vez que la configuración esté finalizada, será necesario
conectar el dispositivo al panel del control de iluminación,
por medio de los siguientes pasos:
1. Conecte el cable de comunicaciones de estilo
telefónico incluido al cabezal adaptador de 9 clavijas
provisto.
2. Conecte el cabezal adaptador de 9 clavijas al puerto
serial del módulo de interfaz de Ethernet.
3. Conecte el otro extremo del cable de comunicaciones
estilo telefónico al puerto COM estilo RJ11 en el panel
del control de iluminación. (En algunos controladores,
hay dos conectores estilo RJ11. Conecte el cable con el
conector etiquetado como RS-232.)
4. Conecte un extremo del cable Ethernet al puerto RJ45
del módulo de interfaz de Ethernet, y el otro extremo
del cable a la red Ethernet.
5. Enchufe el adaptador de alimentación incluido con el
dispositivo.
ADJ
LCD
RSC POWERRSC LINK
ICD LINK
VCC
GND
TCK
TDO
TDI
TMS
JTAG
TEST
16
32
15
31
14
30
13
29
12
28
11
27
10
26
9
25
8
24
7
23
6
22
5
21
4
20
3
19
2
18
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
1CH
17CH
ON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSO
ON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSOON +24 OFF LSO
PWR
NET+NET
REM
GND+24
REM
LOCAL
PCI-NET
DIGITA
PCI-NETPCI-NET
RS-232
NET
POWER
LSC
TERM
CAN-TX CAN-RX
RESET
50-022180-02
C
PCI 2005
STATUSNET
54-022180-
ANALOG COMAN1AN2AN3AN4
ANALOGS
CW
TP1
TB2
J10
J9
C43
TB1
LED2
LED6
LED3
SR1
IND1
C29
J8
J4
J5
J2
LED4 LED5
J6
J3
LED1
J7
J1
D6D5D4D3
TB3
CONCENTRADOR
LAN del edificio
Software del control de iluminación
El EIM puede conectarse con cualquier controlador en la red.
Adaptador de CA
Cable estilo telefónico
RS-232con cabezal
de cable adaptador
Red RS-485 con
otros paneles
de control de
iluminación
Interfaz Ethernet
Módulo (EIM)
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, GA 30269
CooperControl.com
© 2014 Eaton
All Rights Reserved
Printed in USA
P/N: 9850-000436-00
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton est une marque de commerce
déposée. Toutes les autres marques
de commerce sont la propriété de leur
propriétaire respectif.
Eaton es una marca comercial
registrada. Todas las marcas comerciales
son propiedad de sus respectivos
propietarios.
WARRANTIES AND LIMITATION OF LIABILITY
Please refer to www.coopercontrol.com under the Legal section for our terms and conditions.
GARANTIES ET LIMITATION DE LA RESPONSABILITÉ LÉGALE
Veuillez consulter la section juridique de www.coopercontrol.com pour connaître nos conditions générales
GARANTÍAS Y LIMITACIONES DE RESPONSABILIDAD CIVIL
Remítase a la sección Legal del sitio web www.coopercontrol.com para conocer nuestros términos y condiciones.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Cooper Lighting Ethernet Interface Module, EIM Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI