Vertiv Liebert® ITA™ 10kVA User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
Liebert® ITA User
Manual 10kVA UPS
Safety Precautions
This user manual contains the information concerning the installation and operation of Liebert® ITA 10kVA UPS
(hereinafter referred to as UPS).
Please carefully read this user manual prior to installation.
Warning
1. The UPS must be installed and commissioned by engineers designated by the manufacturer or its agent. Failure to
observe this could result in personnel safety risk, UPS malfunction and invalidation of warranty.
2. The UPS has been designed for commercial and industrial use only, and is not recommended for use in life support
applications.
3. This is a Class A UPS product. In a residential environment, this product may nevertheless cause radio interference, in
that case, the user is required to take additional measures to reduce the interference.
4. Never dispose of the battery module in a fire because it may explode and endanger personnel safety when exposed to
flame.
Note
1. The standard UPS has the external battery module, the output terminals of the UPS may carry live voltage even when
the UPS is not connected to AC mains.
2. Before moving or re-wiring the UPS, disconnect all the inputs and make sure that the UPS is completely shutdown. Or
else, the output end may carry live voltage.
3. The operating environment and the storage method will affect the life and reliability of the UPS, it is not recommented to
use the UPS for a long time in the following environments:
Places where the temperature and relative humidity are outside the technical specification (temperature: 0°C ~ 40°C,
relative humidity: 5%RH ~ 95%RH).
Places where direct sunlight and near heat source are present.
Places where vibrations or shocks are present.
Places where dusty, corrosive substances, salts or flammable gases are present.
4. Keep the air inlet and outlet well-ventilated. Poor ventilation will increase the internal temperature, which will shorten the
life of the UPS components and that of the UPS.
5. Liquid or other irrelevant external objects are prohibited inside the UPS.
6. In case of a fire, a dry chemical fire extinguisher is essential. Using a foam fire extinguisher will cause an electric shock.
7. The life of the battery module will be shortened with the rise of the ambient temperature. To ensusre noraml UPS
operation and enough back-up time, the battery module should be replaced periodically. Only Emerson-authorized
technicians are permitted to replace the battery module.
8. If the UPS will remain idle for a long time, it must be stored in a dry environment. The storage temperature should be
-20°C ~ +55°C for standard UPS (with battery modules), and be -40°C ~ +70°C for long back-up UPS (with no battery
modules).
9. The UPS is a professional equipment with a total rated power larger than 1kW. The equipment complies with IEC
61000-3-12 provided that the short-circuit ratio is larger than or equal to 250 at the interface point between the user’s power
supply and the power grid. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the
power supply department if necessary, that the UPS is connected only to a power supply with a short-circuit ratio Rsce
larger than or equal to 250.
10. The UPS output cable must be not longer than 10m.
11. The backfeed protection unit is external. For the using method, refer to UF-BFP-63A Backfeed Protection Unit User
Manual.
12. In Normal mode, the output neutral line of the UPS is connected with the input neutral line. Upon the mains failure, the
output neutral line will be suspended, which results in the output neutral line unconnected.
Conformity and standards
The UPS complies with CE 2006/95/EC (LV Safety) and 2004/108/EC (EMC), and with the following product standards for
UPS:
IEC 62040: 2008 General and safety requirements
IEC62040-2: EMC requirements, Class C2 compliant
IEC62040-3: Performance requirements and test methods
The UPS installation should follow the above instructions and use the accessories specified by the manufacturer.
Warning: high leakage current
1. Reliable earth connection is essential before the input power (AC mains and battery included) is connected.
2. Earth leakage current is bigger than 3.5mA, and less than 5% of the input current.
3. Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into
account when selecting instantaneous RCCB or RCD.
4. Note that the earth leakage current of the load will flow through the RCCB or RCD.
5. This equipment must be earthed in accordance with the local electrical codes.
Warning: backfeed voltage
Before operating the circuit, isolate the UPS firstly, and then check the dangerous voltage between the ports, and that
between the ports and earth.
Maintainable components
1. All internal maintenance and servicing procedures of the equipment should be carried out only by trained personnel.
Components behind the protective cover which can only be removed by using a tool are restricted to service personnel.
2. The UPS meets the safety requirements completely in operator access area. Only service personnel can contact with the
hazardous voltage inside the UPS. However, the risk of contacting these voltages is minimized because the components
with hazardous voltage may be contacted only by using a tool to remove the protective cover. No risk will exist if you follow
the general norms and in accordance with the procedures recommended in this manual on equipment operation.
Warning: battery high voltage
1. All the physical service and maintenance of the battery are performed by the trained technicians.
2. Operation on the battery will result in electric shock and high short-circuit current, therefore, before operating the battery,
the following should be observed:
Remove the watches, rings and other metal objects.
Use the tools with insulation handle.
Weare rubber gloves and shoes.
Avoid to place the tools and metal objects on the battery surface.
Cut off the charge power supply before connecting or disconnecting the battery terminals.
Check whether the battery is earthed accidently, if yes, please disconnect the earthing. Contacting any earth battery
parts will result in electric shock. Therefore, make sure that the battery is not earthed during installation and
maintenance.
3. Battery manufacturers provide the details of the precautions to be observed when working on, or in the vicinity of the
batterys. These precautions should be followed implicitly at all times. Attention should be paid to the recommendations
concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities.
Contents
Chapter 1 Product Introduction ........................................................................................................................................... 1
1.1 Features................................................................................................................................................................ 1
1.2 Model Configurations ............................................................................................................................................ 1
1.3 Appearance And Components.............................................................................................................................. 2
1.3.1 Appearance ............................................................................................................................................... 2
1.3.2 Components .............................................................................................................................................. 2
1.4 Operating Principle ............................................................................................................................................... 3
1.5 UPS State And Operation Mode ........................................................................................................................... 3
1.5.1 Normal Mode ............................................................................................................................................. 4
1.5.2 Bypass Mode............................................................................................................................................. 4
1.5.3 Battery Mode ............................................................................................................................................. 5
1.5.4 ECO Mode................................................................................................................................................. 5
1.5.5 Fault State ................................................................................................................................................. 5
1.5.6 Maintenance Bypass Mode ....................................................................................................................... 5
1.6 Specifications........................................................................................................................................................ 6
Chapter 2 Single UPS Installation And Commissioning ...................................................................................................... 8
2.1 Unpacking Inspection............................................................................................................................................ 8
2.2 Installation Preparation ......................................................................................................................................... 8
2.2.1 Location ..................................................................................................................................................... 8
2.2.2 Environmental Requirements .................................................................................................................... 8
2.2.3 Installation Tools...................................................................................................................................... 10
2.3 External Protective Devices ................................................................................................................................ 10
2.3.1 Battery Input ............................................................................................................................................ 10
2.3.2 UPS Output ............................................................................................................................................. 10
2.4 Mechanical Installation........................................................................................................................................ 10
2.4.1 Tower Installation .................................................................................................................................... 10
2.4.2 Rack Installation ...................................................................................................................................... 12
2.5 Connecting Power Cables .................................................................................................................................. 15
2.5.1 Connecting I/O Cables............................................................................................................................. 16
2.5.2 Connecting Battery Cables ...................................................................................................................... 20
2.5.3 Connecting 10A Charger Cable............................................................................................................... 23
2.6 Single UPS Commissioning ................................................................................................................................ 24
2.6.1 Check Before Startup .............................................................................................................................. 24
2.6.2 Single UPS Parameters Setting............................................................................................................... 25
2.6.3 Normal Mode Startup............................................................................................................................... 25
2.6.4 Battery Mode Startup............................................................................................................................... 26
Chapter 3 Parallel UPS Installation And Commissioning .................................................................................................. 28
3.1 Features.............................................................................................................................................................. 28
3.2 Requirements ..................................................................................................................................................... 28
3.3 Mechanical Installation........................................................................................................................................ 28
3.4 Connecting Cables.............................................................................................................................................. 29
3.4.1 Connecting I/O Cables............................................................................................................................. 29
3.4.2 Connecting Parallel Signal Cables .......................................................................................................... 30
3.5 Setting Parallel Addresses.................................................................................................................................. 31
3.6 Commissioning Parallel System.......................................................................................................................... 31
3.6.1 Check Before Startup .............................................................................................................................. 31
3.6.2 Startup Commissioning For Parallel System ........................................................................................... 31
Chapter 4 Display Panel.................................................................................................................................................... 33
4.1 LED Display Panel .............................................................................................................................................. 33
4.1.1 UPS State Indicators ............................................................................................................................... 33
4.1.2 UPS Load Battery Capacity And Fault Orientation Indicators.................................................................. 33
4.1.3 Control Keys ............................................................................................................................................ 35
4.2 LCD Display Panel.............................................................................................................................................. 35
Chapter 5 UPS Operation Instructions .............................................................................................................................. 38
5.1 Check Before Power-On ..................................................................................................................................... 38
5.2 UPS Power-On ................................................................................................................................................... 38
5.3 Turning On UPS.................................................................................................................................................. 39
5.4 Battery Self-test .................................................................................................................................................. 39
5.4.1 Battery Power-On Self-test ...................................................................................................................... 40
5.4.2 Battery Manual Self-test .......................................................................................................................... 40
5.4.3 Battery Periodic Self-test ......................................................................................................................... 40
5.5 Turning Off UPS.................................................................................................................................................. 41
5.6 UPS Power-off .................................................................................................................................................... 42
5.7 Transferring UPS Operation Mode...................................................................................................................... 42
5.7.1 Transferring UPS To Bypass Mode From Normal Mode Manually .......................................................... 42
5.7.2 Transferring UPS To Bypass Mode From Overload Protection ............................................................... 42
5.7.3 Transferring UPS To Inverter Mode From Bypass Mode Manually ......................................................... 42
5.7.4 Transferring UPS To Battery Mode From Mains Failure.......................................................................... 43
5.7.5 Transferring UPS To Bypass Mode From Inner Overheating Protection ................................................. 43
5.7.6 Transferring UPS Fault State Upon Output Short Protection................................................................... 43
5.7.7 Transferring UPS To Maintenance Bypass Mode From Inverter Mode ................................................... 43
5.7.8 Transferring UPS To Inverter Mode From Maintenance Bypass Mode ................................................... 43
5.8 UPS Complete Shutdown ................................................................................................................................... 44
5.9 Auto Startup........................................................................................................................................................ 44
5.10 UPS Monitoring................................................................................................................................................. 44
Chapter 6 Communication................................................................................................................................................. 45
6.1 Connecting USB Communication Cable ............................................................................................................. 45
6.2 Installing Communication Assembly (Optional)................................................................................................... 45
6.2.1 SIC Card.................................................................................................................................................. 45
6.2.2 JBUS/MODBUS Adapter Card ................................................................................................................ 45
6.2.3 RS485 Card............................................................................................................................................. 46
6.2.4 RS232 Card............................................................................................................................................. 46
6.2.5 Dry Contact Card..................................................................................................................................... 46
6.2.6 Extended Dry Contact Card..................................................................................................................... 46
6.3 Connecting REPO Cable .................................................................................................................................... 46
Chapter 7 Maintenance And Troubleshooting ................................................................................................................... 47
7.1 Fan Maintenance ................................................................................................................................................ 47
7.2 Battery Maintenance ........................................................................................................................................... 47
7.3 Cleaning UPS ..................................................................................................................................................... 48
7.4 Checking UPS Status ......................................................................................................................................... 48
7.5 Checking UPS Functions .................................................................................................................................... 48
7.6 Troubleshooting .................................................................................................................................................. 48
Chapter 8 Options ............................................................................................................................................................. 51
8.1 Option List........................................................................................................................................................... 51
8.2 Battery Module.................................................................................................................................................... 51
8.2.1 List Of Battery Module Options................................................................................................................ 51
8.2.2 Appearance Of Battery Module ............................................................................................................... 52
8.2.3 Backup Timetable Of Standard Battery Module For Single UPS ............................................................. 53
8.3 POD .................................................................................................................................................................... 53
8.3.1 1-Input 1-Output 1 + 1 Parallel POD........................................................................................................ 53
8.3.2 3-Input 1-Output 1 + 1 Parallel POD........................................................................................................ 54
8.3.3 3-Input 1-Output 3 + 1 Parallel POD........................................................................................................ 55
8.3.4 Output Power Distribution Unit ................................................................................................................ 56
8.4 Complete Set Of Cables ..................................................................................................................................... 57
8.4.1 Parallel Signal Cables.............................................................................................................................. 57
8.4.2 Battery Cables ......................................................................................................................................... 57
8.5 Guide Rail For Rack Installation.......................................................................................................................... 57
8.6 Communication Options And Monitoring Options ............................................................................................... 57
8.7 10A Charger ....................................................................................................................................................... 58
8.8 Assembly Of LCD Display Panel......................................................................................................................... 59
8.9 Battery Shared Module Of UF-BSO-0100 ITA UPS ............................................................................................ 60
Appendix 1 Operation Guide For UPS Parallel Power Distribution ................................................................................... 62
Appendix 2 Glossary ......................................................................................................................................................... 63
Chapter 1 Product Introduction 1
Liebert® ITA 10kVA UPS User Manual
Chapter 1 Product Introduction
The Liebert® ITA 10kVA UPS (UPS for short) is an intelligent online UPS system with sine wave output developed by
Emerson Network Power Co., Ltd. The UPS offers reliable and high quality AC power to the precision instrument.
The UPS uses modular design, and rack/tower installation can be used depending on your requirements. It is
applicable to supplying AC power to small scale computer center, network, communication system, automatic control
system and precision instrument.
This chapter introduces the features, model configurations, appearance, components and operating principle of the
UPS.
1.1 Features
The UPS features include:
Compatible with two mains input modes: 3-phase and single-phase input mode, with automatic input recognition
function
Capable of parallel connection to achieve up to 3 + 1 parallel redundant power
High-frequency double conversion topology structure, with high input power factor, wide input voltage range, and
output immune to power grid interference, thus adaptable to areas with unstable mains supply
High power density
Full digital control technology based on DSP to achieve high system reliability with self-protection and fault
diagnosis functions
Excellent intelligent battery management to extend the battery life
Display panel with both LCD and LED indication to help you learn about the UPS operation status and operating
parameters
2U thickness. Tower installation and rack installation are optional to meet different installation requirements
Capable of ECO power supply mode, which helps you save energy to the maximum extent
Flexible network management with Emerson monitoring software
Fan fault self-test and automatic recognition functions
SNMP card optional, providing network communication function
Capable of connecting multiple battery strings, extending the power supply time of battery mode
1.2 Model Configurations
Two types are available for the UPS: standard model and long back-up model. The model configurations are listed in
Table 1-1.
Table 1-1 Model configurations
Model Type
Product
number
Weight (net weight/gross
weight, kg)
Size (W × H × D,
mm) Description
Standard
model UHA1R-0100 01200775 20.8/24.8 435 × 85 × 660
Configured with battery
modules. See 8.2 Battery
Module for the structure and
connection of the battery
modules
Long
back-up
model
UHA1R-0100L 01200770 21.5/25 435 × 85 × 660
You need to select the battery
modules acccording to the
requirements or connect the
external battery modules by
yourself
2 Chapter 1 Product Introduction
Liebert® ITA 10kVA UPS User Manual
1.3 Appearance And Components
1.3.1 Appearance
The UPS appearance is shown in Figure 1-1.
Figure 1-1 UPS appearance
1.3.2 Components
Front panel
As shown in Figure 1-2, the UPS front panel provides ventilation holes and display panel.
Ventilation holeDisplay panel
Figure 1-2 UPS front panel
Rear panel
As shown in Figure 1-3, the UPS rear panel provides DIP switch, parallel port, ventilation hole, bypass terminal block,
input MCB, bypass MCB, battery port, USB port, REPO port, 10A charger control port, intelligent card slot and I/O
terminal block.
DIP switch Parallel port
Intelligent card slot
Bypass terminal block
Input MCB
Bypass MCB
Battery port
I/O terminal block10A charger control port
USB port
Ventilation hole
REPO port
Figure 1-3 UPS rear panel
Chapter 1 Product Introduction 3
Liebert® ITA 10kVA UPS User Manual
Note
Non-authorized personnel are prohibited from opening the UPS chassis cover.
1.4 Operating Principle
The operating principle of the UPS is shown in Figure 1-4.
Input filter
Input filter
Rectifier/PFC Inverter
Internal
charger
Battery input
Mains
Bypass
Output
L1
L2
L3 L1 output
N
PE
Bypass MCB
Figure 1-4 UPS operating principle
1. The UPS is composed of mains input, I/O filter, rectifier/PFC, inverter, bypass, internal charger, battery input and
UPS output.
2. When the mains is normal, close the bypass MCB, and the internal charger will charge the battery. Before the UPS
is turned on, the output voltage is zero. After the UPS is turned on, the electronic transfer switch connects the inverter
to the load, and the mains supplies DC power to the inverter through the rectifier/PFC circuit. The inverter then
converts DC power into pure sine wave AC power, and supplies the AC power to the load through the electronic
transfer switch.
3. When the mains is abnormal, the rectifier/PFC circuit boosts the battery voltage and supplies it to the inverter. The
inverter then converts it into pure sine wave AC power, and supplies the AC power to the load through the electronic
transfer switch.
4. After the mains restores, the UPS will automatically transfer from Battery mode to Normal mode, the mains
supplies DC power to the inverter through the rectifier/PFC circuit, and then the electronic transfer switch supplies the
AC power to the load.
1.5 UPS State And Operation Mode
The UPS state and operation mode include: Normal mode, Bypass mode, Battery mode, ECO mode, Fault state and
Maintenance Bypass mode.
The operation schematic diagrams of Normal mode, Bypass mode, Battery mode and Maintenance Bypass mode are
shown in Figure 1-5.
Note
Only when the UPS output power distribution unit (POD for short) is configured, the Maintenance Bypass mode is valid.
4 Chapter 1 Product Introduction
Liebert® ITA 10kVA UPS User Manual
Normal mode Bypass mode
Battery mode Maintenance Bypass mode
Figure 1-5 Operation schematic diagram
1.5.1 Normal Mode
When the mains input is normal, the load is supplied with voltage-stabilizing and frequency-stabilizing power by the
mains after processing of the rectifier and the inverter, and meanwhile, the charger is charging the battery, the
operation mode is Normal mode. In Normal mode, the mains indicator and the inverter indicator are on.
1.5.2 Bypass Mode
If the overload overtime, inverter or rectifier fault appears during the UPS operation in Normal mode, the UPS will
transfer to Bypass mode, that is, the load is powered by the bypass source, which comes directly from the mains
input. If the rectifier is normal, the internal charger will charge the battery. In Bypass mode, the inverter indicator is off;
the mains indicator and the inverter indicator are on.
Note
In case of mains failure or mains voltage out of range (120Vac ~ 253/264/276Vac) in Bypass mode, the UPS will turn off and stop
the output.
Chapter 1 Product Introduction 5
Liebert® ITA 10kVA UPS User Manual
1.5.3 Battery Mode
Upon mains failure, rectifier overload or mains voltage out of range (120Vac ~ 288Vac), the rectifier and the internal
charger will stop running, and the battery will supply power to the load through the inverter. The battery indicator and
the inverter indicator are on, and the buzzer alarms every 3.3 seconds, which notifies you that the UPS is in Battery
mode.
Note
1. The battery has been fully charged before delivery. However, transportation and storage will inevitably cause some capacity
loss. Therefore, it is required to charge the battery for eight hours before the UPS is put into operation for the first time, to ensure
the adequate back-up time for the battery.
2. The battery cold start can also be used to start the UPS from Battery (charged) mode upon mains failure. Therefore, the
battery power can be used independently for improving the system availability to some extent.
3. In Battery mode, when the battery voltage is low, the buzzer beeps rapidly (once per second), and the corresponding
measures must be done in time.
1.5.4 ECO Mode
In ECO mode, when the bypass voltage is within 220Vac ± 10% and the frequency is within 50Hz ± 2Hz, the load is
supplied by the bypass and the bypass indicator is on. When the bypass voltage is abnormal, the load is supplied by
the inverter. The ECO mode is an energy-saving operation mode. For power equipment insensitive to power grid
quality, you can use ECO mode for power supply through the bypass to reduce the power loss.
When the bypass voltage is normal, the inverter is in no-load state. The load is supplied by the bypass and the
bypass indicator is on.
Note
1. In ECO mode, if the bypass failure or abnormal bypass voltage appears when the output is not overloaded, the UPS will
transfer to Normal mode. However, if the bypass failure or abnormal bypass voltage appears when the output is overloaded, the
UPS will not transfer to Normal mode, but will shut down the bypass.
2. In ECO mode, the efficiency of the UPS is up to 97%.
3. Different voltage types have different voltages and frenency ranges.
1.5.5 Fault State
In Normal mode, the UPS will transfer to the Bypass mode if the inverter failure or UPS overtemperature appears. In
Battery mode (with no bypass mains), the UPS will turn off and stop the output if the inverter failure or UPS
overtemperature appears. If a UPS failure occurs, the fault indicators will turn on, the buzzer will keep beeping, and
the corresponding indicator will blink.
Note
In Fault state, if the bypass fails or the bypass voltage is abnormal when the output is not overloaded, except for the faults which
can cause turn-off, the UPS will transfer to the inverter for supply power, such as radiator over-hot. However, if the bypass fails
or the bypass voltage is abnormal when the output is overloaded, the UPS will not transfer to the inverter for supply power, and
will turn off the bypass.
1.5.6 Maintenance Bypass Mode
If maintenance and repair for the UPS are needed, you can switch the load to the Maintenance Bypass through the
maintenance bypass MCB, and the power to the load is not interrupted. The maintenance bypass MCB is located on
the front panel of the POD, and the capacity meets the requirements of the total load capacities. Refer to Liebert® ITA
10kVA UPS Parallel Power Distribution Unit User Manual for the detailed introductions of the POD.
6 Chapter 1 Product Introduction
Liebert® ITA 10kVA UPS User Manual
Note
When the UPS has malfunctions and can not work normally, please get in touch with the nearest Emerson branch office or local
service center. It is prohibited to repaire the UPS by yourself, otherwise the personnel injury and damage to the equipment will
occur.
1.6 Specifications
The specifications are listed in Table 1-2.
Table 1-2 Specifications
Standard model Long back-up model
Item UHA1R-0100 UHA1R-0100L
Rated voltage Single-phase: 220Vac, 3-phase: 380Vac, voltage type of 230Vac and 240Vac is available
Voltage range
176Vac ~ 288Vac, at full load
120Vac ~ 176Vac, linear derating
120Vac, at half load
Frequency 50/60Hz ± 5Hz
Input
Power factor Single-phase: 0.99, 3-phase: 0.95
Rated power 10kVA/9kW (25°C ~ 40°C)
Voltage 220/230/240Vac ± 3%
Frequency
In Normal mode: the output tracks the bypass frequency when the bypass frequency is
within 50/60Hz ± 5Hz;
In Battery mode, the output frequency is within 50/60Hz ± 0.2Hz;
Bypass frequency tracking range: ±10%
Frequency tracking
rate 0.2Hz/s (default), 1Hz/s
Power factor 0.9 (10kVA)
Crest factor 3:1
Voltage harmonic
distortion 3% (linear load), 5% (non-linear load)
Load regulation rate 2%
Power grid regulation
rate 2%
Dynamic response
recovery time 60ms
Overload capacity
105% ~ 125% rated load, 5min; 125% ~ 150% rated load, 1min; above 150% rated load,
500ms (Normal mode);
105% ~ 125% rated load,60s; above 125% rated load, 500ms (Battery mode)
Bypass voltage 120Vac ~ 253/265/276Vac
Output
Mains efficiency 93%
Type Sealed, lead-acid, maintenance-free battery (12V/7Ah)
Cell No. 16 × 2
Rated voltage 192Vdc
Recharge duration
(standard UPS) Six hours to 90% rated capacity Depended on the external battery
capacity
Battery
Charge current 2A 4A
Mains←→Battery 0ms
Transfer time Inverter←→Bypass 4ms
Noise 50dB
Panel display mode LED/LCD (optional)
Safety CCEE (GB4943-1995)/GB4943
Storage Standard GB/T4798.1-86
Transportation Standard GB/T4798.12-96
Conduction emission IEC/EN 62040-2
Immunity I 16A, IEC/EN61000-3-3; 16A < I 75A, IEC/EN61000-3-11
EMC
Harmonic current I 16A, IEC/EN61000-3-2; 16A < I 75A, IEC/EN61000-3-12
YD/T1095-2001 level 2 15%
Chapter 1 Product Introduction 7
Liebert® ITA 10kVA UPS User Manual
Standard model Long back-up model
Item UHA1R-0100 UHA1R-0100L
Surge protection IEC/EN 61000-4-5, endurance level 4 (4kV) (live line to earth), level 3 (2kV) (among live
lines)
Protection level IP20
Operating temperature 0°C ~ 40°C
Storage temperature -40°C ~ +70°C (battery excluded); -20°C ~ +55°C (battery included)
Relative humidity 5% ~ 95%, non-condensing
Ambient
condition
Altitude < 1500m, derating in accordance with GB/T3859.2 when higher than 1500m 
Size W × H × D 435mm × 85mm × 660mm
Standard model 24.8kg
Weight Long back-up model 25kg
8 Chapter 2 Single UPS Installation And Commissioning
Liebert® ITA 10kVA UPS User Manual
Chapter 2 Single UPS Installation And Commissioning
This chapter introduces the installation, cable connection and commissioning of the single UPS.
Each site has its peculiarity, so this chapter provides the guidance with general installation procedures and methods
for the installation engineer who should conduct the installation according to the actual conditions.
Warning: professional installation
1. The UPS should be installed by an Emerson-authorized engineer according to the information contained in this chapter. If any
problem is found, please get in touch with Emerson local service center immediately.
2. The UPS shall not be powered on without approval of the commissioning engineer.
3. The UPS installation must be carried out by professionals strictly. For other equipment which is not introduced in this manual,
the detailed information about mechanical installation and electrical installation are delivered with the equipment.
2.1 Unpacking Inspection
After the UPS arrival, you should unpack it and check the following items:
1. Visually inspect the UPS appearance for transportation damage. If any problem is found, please notify the carrier
immediately.
2. Check the accessories and models against the delivery list. If any problem is found, please notify the dealer
immediately.
2.2 Installation Preparation
2.2.1 Location
To extend the UPS life, the chosen place must offer:
Convenient wiring
Adequate operator access area
Good ventilation to meet the heat dissipation requirements
No corrosive gas, like sulfur dioxide
No excessive moisture or heat source
No excessive dust
Compliance with fire-fighting requirements
Operating temperature compliant with the specifications, see Table 1-2 for details
2.2.2 Environmental Requirements
UPS room
The UPS is designed for indoor installation, which should be installed in a clean and well-ventilated environment, to
keep the environmental temperature within the specifications.
The internal fans provide forced air cooling for the UPS. Cooling air enters the UPS through the ventilation holes on
the rear panel, and exhausts the hot air through the front ventilation holes. Therefore, do not obstruct the ventilation
holes. Maintain at least 200mm clearances between the front, rear, top, bottom, side panels of the UPS and the wall
or adjacent equipment (see Figure 2-1), to avoid obstructing the UPS ventilation and heat dissipation. Otherwise, the
UPS internal temperature will rise, which will shorten the UPS life.
If necessary, an indoor exhaust fan should be installed to keep the indoor temperature from rising. An air filter should
be used in a dusty environment where the UPS is to be operated.
Chapter 2 Single UPS Installation And Commissioning 9
Liebert® ITA 10kVA UPS User Manual
General view
500mm
200mm
Cabinet
Wall
200mm
Cabinet
Wall
Top view Front view
Figure 2-1 Cabinet installation clearances
Note
1. The UPS should be installed only on the concrete surface or other non-flammable surfaces.
2. As shown in Figure 2-1 (top view), the demonstration of the clearance between the rear panel of the cabinet and the wall is
500mm. The clearance should not be less than 200mm, it needs to be considered according to the actaul situation for the sake of
maintenance convenience.
Battery room
A small amount of hydrogen and oxygen will be generated at the end of battery charging, therefore, you must ensure
that the fresh air ventilation of the battery installation environment meets the EN50272-2001 requirements.
The battery ambient temperature should keep constant, because the ambient temperature is the main factor to affect
the battery capacity and life. The battery standard operating temperature is 20°C, operation above this temperature
will shorten the battery life, and operation below this temperature will reduce the battery capacity. If the battery
average temperature in operation rises from 20°C to 30°C, the battery life will be reduced by 50%; if the battery
temperature in operation exceeds 40°C, the battery life will be decreased exponentially. In general, the allowable
environmental temperature of the battery is 15°C ~ 25°C. The battery should be kept away from heat and ventilation
holes.
When the UPS uses an external battery, you must install a battery protective device (such as a fuse or a circuit
breaker) in areas near the battery, and use the shortest wiring distance for the connection between the protective
device and the battery.
10 Chapter 2 Single UPS Installation And Commissioning
Liebert® ITA 10kVA UPS User Manual
Storage environment
When the UPS does not need to be installed immediately, the UPS must be stored indoors to be protected from the
excessive moisture or overtemperature environment. The battery requires dry and low temperature, well-ventilated
environment for storage, and the most suitable storage temperature is 20°C ~ 25°C.
Warning: battery hazards
During the battery storage, the battery must be periodically charged according to the battery instructions. When the battery is
charged, you can connect the UPS to the mains temporarily to charge and activate the battery.
2.2.3 Installation Tools
Prepare installation tools according to Table 2-1. The tools must be insulated and ESD-proof processed prior to use.
Table 2-1 Installation tools list
Installation tool Specification Application
Cross screwdriver EJ5100mm Remove the screws of the top protective cover of the UPS, or open the chassis
Wire-pressure plier YT-12 Press wires for I/O terminal block
Diagonal plier MTC3C Make I/O cables
Slotted screwdriver EJ375mm Connect I/O cables
2.3 External Protective Devices
The circuit breaker or other protective devices must be installed at the external AC input end of the UPS. This section
provides the general guidance for qualified installation engineer. The qualified installation engineer should learn about
the local wiring regulations and other related information.
2.3.1 Battery Input
If the battery module option is provided by Emerson, the battery module has a built-in overcurrent protective device.
Otherwise, the external battery cabinet should equip a DC compatible circuit breaker to provide overcurrent protection
for the UPS and its batteries.
2.3.2 UPS Output
A protective device must be installed for the UPS output power distribution. The protective device must be different
from the input power distribution protection air breaker, and should provide overload protection (see Table 2-4).
2.4 Mechanical Installation
Two installation modes are available: tower installation and rack installation. You can select an appropriate installation
mode according to the actual conditions.
2.4.1 Tower Installation
1. Adjust the display panel.
1) Press the spring buckles on two sides of the display panel at the same time, and pull out the display panel.
2) Rotate the display panel 90° counter clockwise.
3) Insert the display panel into the plastic bracket.
The operation procedures of the display panel are shown in Figure 2-2 when the mode is changed from the rack
installation to the tower installation.
Chapter 2 Single UPS Installation And Commissioning 11
Liebert® ITA 10kVA UPS User Manual
123
Plastic bracketDisplay panel Spring buckle
Figure 2-2 Adjusting display panel
Note
1. For the tower installation, you need to adjust the display panel; for the rack installation, ignore this step.
2. When adjusting the display panel, you do not need to open the chassis of the UPS.
3. When adjusting the display panel, you must turn off the UPS.
2. Install the plastic panel.
1) Take out the plastic panel from the UPS package.
2) Align the plastic panel with the UPS display panel, and gently press the metal buckles on both sides of the plastic
panel into the square holes on the UPS front panel according to the direction shown in Figure 2-3.
Square hol
e
Display panel
Plastic panel
Figure 2-3 Installing plastic panel
Note
You do not need to take off the UPS when removing the plastic panel. Press the two ends of the plastic panel with hands, and
gently pull out the plastic panel to remove it.
3. Take out the support bases from the accessories, assemble a pair of support bases together through the
fastenings, as shown in Figure 2-4, and put them onto the flat installation table.
12 Chapter 2 Single UPS Installation And Commissioning
Liebert® ITA 10kVA UPS User Manual
Figure 2-4 Installing support base
4. If battery module installation is necessary, take out the support base extensions delivered with the battery module,
and then assemble the support base extensions and the support bases together through the fastenings, as shown in
Figure 2-5.
Fastening
Support base
extension
Support base Support base
Figure 2-5 Installing support base with support base extension
5. Place the UPS and the battery module (if configured) on the support bases and support base extensions. Each
UPS needs two pairs of the support bases, as shown in Figure 2-6.
UPS
Support base
UPS
Support
base
Battery
module
Figure 2-6 Installing UPS and battery module
2.4.2 Rack Installation
Installation procedures for UPS
1. Install the plastic panel, refer to 2.4.1 Tower Installation for the procedures.
2. Take out the two brackets and six M4 × 10 screws from the accessories of the UPS, and fix the two brackets onto
the battery module using the M4 × 10 screws through installation hole 1, as shown in Figure 2-7.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Vertiv Liebert® ITA™ 10kVA User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI