TROUBLESHOOTING
Code Fault
Description 1st diagnostic
H3100
extended
no
blocking fault
blocking fault
10 610
Exterior sensor fault, no signal. A function has been activated that re-
quires an outdoor sensor. => Application
incompatible with Dorchester DR-SG,
should be deactivated.
20 All Dorchester DR-SG T° sensor fault, no
signal.
Check sensor B2 wiring (terminals
X22.1 and X22.2).
26 612
Common temperature sensor fault
(Flow output).
A shared B10 ow sensor has been con-
gured. This function must not be acti-
vated on Dorchester DR-SG
28 All Fumes sensor short circuited Check the exhaust temperature sensor
on BX1 (terminals X22.9 and X22.10).
30 614 Circuit 1 output temperature sensor fault. One or more heating sensors have been
congured. This function must not be
activated on Dorchester DR-SG
32 616 Circuit 2 output temperature sensor fault.
40 All Dorchester DR-SG temperature sensor
fault, no signal or short circuited.
Check the B7 sensor wiring (terminals
X22.3 and X22.4).
46 53
Flow feedback temperature sensor fault. A shared B70 ow sensor has been
congured. This function must not be
activated on Dorchester DR-SG
50 All DHW sensor 1 fault. Check the B3 sensor (terminals X21.1
and X21.2).
83 BSB short circuit
No communication
84 BSB Address collision
91 Problem with the EEPROM. Contact After Sales.
98 0 Extension module 1 error. Check the ribbon cable of the bus con-
nected to the AVS75 at address 1 or 2.
Caution: perform the addressing opera-
tion with the power o. Check that the
AVS75 is correctly powered at 230V.
99 0
Extension module 2 error.
110
412
Safety thermostat activated: Thermostat
is triggered after the Dorchester DR-SG
reaches a temperature that is too high.
431
Number of 110/420 faults (auto control
of the Dorchester DR-SG
sensor) in 24
hours is too high.
Check the sensor wiring or change sen-
sor
432
Tank temperature too high: The value
read by the Dorchester DR-SG sensor is
too high.
Seen by sensor B2 (terminals X22.1
and X22.2)
436
Tank temperature too high: The value
read by the Dorchester DR-SG sensor is
too high.
Seen by sensor B7 (terminals X22.3
and X22.4)
437
The number of 110/426 faults (rise in
temperature too rapid) in 24 hours is too
high.
111
Temperatures in the Dorchester DR-SG
tank too high reaching the maximum lim-
it of the thermostat cut-o temperature.