SenTech IR-SNIF-3 Operating instructions

Type
Operating instructions
SenTech Corporation
5745 Progress Road
Indianapolis, Indiana 46241
888/248-1988
FAX 317/248-2014
INSTALLATION AND OPERATION MANUAL
ENVIRONMENTAL SYSTEM IR-SNIF
SINGLE ZONE MONITOR
MODEL IR-SNIF-1,2,3
ii
APPLICABILITY
Information presented in this manual can be generally applied to all IR-SNIF-
1,2,3 refrigerant monitors. Specific details of programming and operator
interface apply to software version 5327k and later versions. To determine the
version of an IR-SNIF-1,2,3, press the “*” key. This will display momentary
screens that provide contact information for SenTech Corporation, the software
version and any options enabled in the monitor. If your monitor has a version
that is older than 4093 (smaller version number such as 3017), a version specific
appendix A, Programming and Operator Interface, is available. It can be
downloaded from the SenTech Corporation website, www.sentechcorp.com, or
directly from SenTech Corporation at 888-248-1988.
iii
Contents
SAFETY PRECAUTIONS and WARNINGS................................................................ 1
Model IR-SNIF-1,2,3 Specifications .............................................................................. 2
INTRODUCTION and OVERVIEW ............................................................................. 3
Functional Description................................................................................................ 3
Sensitivity to Refrigerants........................................................................................... 6
Factory Calibration ..................................................................................................... 6
PPM vs. Leak Rate...................................................................................................... 6
INSTALLATION ........................................................................................................... 7
Unpack and Inspect Material ...................................................................................... 7
Identify Location for Monitor, Sample Points and Alarms ........................................ 7
Electrical Power Connection....................................................................................... 9
Electrical Alarm Connections ..................................................................................... 9
Other External Connections...................................................................................... 11
STARTUP and PROGRAMMING............................................................................... 14
Apply Power ............................................................................................................. 14
Initial Screens............................................................................................................ 14
Normal Operation ..................................................................................................... 15
Initial Programming .................................................................................................. 15
FINAL TESTS .............................................................................................................. 21
Monitor Sequencing.................................................................................................. 21
Integration with External Devices ............................................................................ 21
Response to Refrigerant............................................................................................ 22
End-to-End System Test ........................................................................................... 24
Documentation.......................................................................................................... 24
PREVENTIVE MAINTENANCE & REPAIR ............................................................ 26
Preventive Maintenance............................................................................................ 26
Commonly Ordered Parts ......................................................................................... 26
Monitor Repair.......................................................................................................... 26
APPENDIX A: Programming and Operator Interface.................................................. 27
Summary ................................................................................................................... 27
Start-up Screens ........................................................................................................ 27
Operational Screens .................................................................................................. 28
Menu Screens............................................................................................................ 29
APPENDIX B: SenTech Room Volume Considerations ............................................. 37
APPENDIX C: Parts List and Wire List....................................................................... 41
TROUBLESHOOTING GUIDE .................................................................................. 43
SenTech Manufacturer's Limited Warranty.................................................................. 46
1
SAFETY PRECAUTIONS and WARNINGS
The following general safety precautions and warnings must be observed during
all phases of installation, operation, service and repair of equipment. Failure to
comply with these precautions, given here and elsewhere in the manual violates
safety standards of design, manufacture, and intended use. SenTech
Corporation assumes no liability for the customer’s failure to comply with these
requirements.
Definitions of safety symbols used on equipment and in manuals.
AC Voltage Terminal: Indicates areas of equipment where AC line
voltages are used and present a potential risk of electrocution. Areas
using line voltages should not be accessed during operation.
AC-to-DC Power Supply: Indicates AC line voltages are used and
present on portions of the power supply, including the heat sinks. A
potential risk of electrocution exists. Areas using line voltages should not
be accessed during operation.
Protective Grounding Terminal: The protective ground is to prevent
electric shock in case of an electrical fault. This symbol indicates that the
terminal must be connected to earth ground before operation of the
equipment.
Caution: This sign calls attention to a procedure or practice which if not
adhered to could result in damage or destruction to a part of the product.
Other information and precautions:
Input Power: Power should be supplied through a two-pole circuit breaker
located in a reasonable proximity to the equipment. Ensure that the voltages are
correct and an appropriate ground connection is provided.
Do Not Open the Monitor with Power Applied: Line voltages exist on the
terminal board inside the monitor and on the power supply inside (including the
heat sinks). The door to the monitor and the power supply itself are marked with
AC Voltage shock hazard warning labels. Remove power prior to opening the
door.
Installation, Maintenance and Repair: These functions should only be done by
qualified personnel following the instructions outlines in this manual. This is
Installation Category III equipment.
Pollution Degree: This equipment is designed for a Pollution Degree of 1.
Cleaning: This equipment should be cleaned by wiping with a soft clean cloth.
Intended Purpose: This equipment is designed to be used as a continuous
refrigerant monitor. It should not be used for any other purpose.
2
Model IR-SNIF-1,2,3 Specifications
Size: 10” x 12.5” x 4.75” (25.4cm x 31.2cm x 12cm)
Weight: 16 lbs. (7.2 kg)
Power: 120 or 240 Volt 50/60hz (41 Watts)
(voltage must be specified at time of order)
Temperature: 32 deg F – 125 deg F (0 deg C – 50 deg C)
Humidity: 0 – 95 % non-condensing
Atmospheric
Pressure:
75-106 Kpa
Equipment rated for indoor use only
Range: 10 – 1000 ppm Standard
Tube Length: 0 – 250 ft (0 – 76 m)
Trip Point: Low Alarm 0 – 1000 ppm
Main Alarm 0 – 1000 ppm
High Alarm 0 – 1000 ppm
Leak Wait: Varies from seven (7) seconds to three (3) minutes
depending on refrigerant concentration
Alarm
Output:
Low, Main and High alarm relays, each with four (4) form
C contacts rated 5 amps maximum
Analog
Output:
0 – 10 volt proportional to 0 – 1000 ppm
4-20 mA proportional to 0-1000 ppm (optional)
Computer
Interface:
RS-485 (optional)
3
INTRODUCTION and OVERVIEW
The SenTech Environmental System IR-SNIF-1,2,3 single zone monitor provides
an early warning of developing refrigerant leaks. The unit samples ambient air
and measures the amount of halogen based refrigerant gas in the air sample.
When the proportion of refrigerant present exceeds a trip point, the system goes
into alarm mode. Should the system assess the presence of refrigerant as a
leak, using SenTech’s “LEAK WAIT” algorithm, the user is notified. By
discovering a leak shortly after it starts, the potential loss can be reduced to
ounces of refrigerant, saving money and helping protect the environment.
Functional Description
The refrigerant monitor is composed of four major functional blocks: Pneumatics,
Infrared Bench, Control Electronics and Power Supply. Refer to figure 1 for an
overall block diagram.
Figure 1 Overall Block Diagram
Pneumatics: Refer to the figure 2 for pneumatics block diagram. Tubing from
the area to be monitored and from a reference air source (either fresh, outside
air, or interior conditioned air that is free of refrigerants) is connected to the valve
manifold. The electronics alternates between energizing the Sample air and the
Auto zero air solenoids. The diaphragm pump draws air from the selected inlet
and feeds the air through an orifice restrictor, through the infrared bench and to
the exhaust port located on the lower right side of the unit. The pressure switch
4
monitors the pressure created by the flow from the pump and the restriction
created by the orifice. Should pressure fall, a flow failure is detected, and signal
is sent to the electronics.
Figure 2 Pneumatics Diagram
Infrared Bench: Refer to the figure 3 for Infrared Bench diagram. The infrared
bench has an integrated source circuit with infrared source at one end and an
integrated detector circuit with filter and detector at the other. Presence of
refrigerant in the sample air will cause a change in the output of the detector.
Figure 3 Infrared Bench
Control Electronics: Refer to the figure 4 for control electronics block diagram.
The signal from the infrared bench is analyzed by the control circuit and
converted into a digital measurement in ppm (parts per million). The ppm level is
compared to trip points set for Low, Main and High alarm levels. If the ppm level
exceeds the Low alarm threshold, the “Leak Wait” algorithm is used to determine
5
whether the monitor has experienced a transient exposure, or a leak truly exists.
If the ppm level remains above the Low alarm threshold on completion of leak
wait, the Low alarm relay is energized. If the signal continues to increase, the
main alarm relay will be energized and ultimately the high alarm relay. Once the
system enters Low, Main or High alarm, it will remain in that mode until the
problem is cleared and the system is reset.
Figure 4 Control Electronics Diagram
Power Supply: Refer to the figure 5 for Power Supply diagram. Power is
supplied to the monitor through terminals 1, 2 and 3 of the terminal board. Line
voltage is fed through the fuse on the left side of the monitor (not shown), and to
the diaphragm pump and power supply. The power supply converts AC line
voltage to dc voltage. DC Voltage is fed through the terminal board to all of the
electrical components of the monitor.
Figure 5 Power Supply Diagram
6
Sensitivity to Refrigerants
The system is sensitive in varying
amounts to all of the halogen-based
refrigerants, those containing
molecules of fluorine, chlorine or
both. As part of the initial setup, the
specific refrigerant to be monitored is
entered into the system. The control
electronics compensates for the
differing sensitivities, resulting in a
true ppm reading for the refrigerant
specified.
Factory Calibration
The IR-SNIF-1,2,3 is calibrated at
the factory prior to shipment. The
system maintains accuracy through
automatic rezeroing. Periodically,
the system switches to the fresh air
inlet, and reestablishes a reference
signal to which it compares sample
air. This process eliminates the
potential variations caused by
changes that develop in electronics
as components age. If a change in
infrared energy or detection of the
infrared energy develops, that
change will be first measured in the
reference signal, then also in the
sample. The ppm level is based on
the ratio of the sample to the
reference. This ratio eliminates the
effect of any variations, and
eliminates the need to periodically
calibrate a monitor in the field.
PPM vs. Leak Rate
The relationship between the actual
amount of product lost and the
resulting ppm level refrigerant in the
air is complex. There is no direct
relationship between the amount of
refrigerant leaking and the
concentration being measured. The
size of the room, the location of the
pick up point, the location of the leak
and airflow in the room will all affect
the actual concentration at the inlet.
However, by judicious location of the
inlets (see installation section) and
maintaining the alarm set points at a
level not too far above ambient,
leaks should be detected
substantially before they otherwise
would be noticed. See Appendix B
for a detailed discussion of room
volume considerations. This
appendix will help to provide a
correlation between pounds of
refrigerant lost over a given period to
the ppm level measured. This
correlation can be developed for a
specific application.
7
INSTALLATION
Unpack and Inspect Material
IR-SNIF-1,2,3 Package: The IR-
SNIF-1,2,3 package contains the
following material:
1. IR-SNIF-1,2,3 Single Zone
Monitor
2. Installation and Operation
Manual
3. Hose barb fittings and 10
micron tube end filters
(one hose barb and filter
for each inlet two of
each are provided)
4. CTS/Warranty form to be
completed and returned to
Sentech
Optional Purchases: The IR-SNIF-
1,2,3 package may also contain the
following material:
1. Plastic FRPE tubing, ¼ inch
OD for sample tube
2. Combination Horn/Strobe
alarm
3. Horn alarm
4. Strobe alarm
Other Required Material: The
following material is required but not
provided by SenTech:
1. Primary power wiring
2. Wiring for connection to alarm
devices or other building
systems
3. Relay contactors for building
system loads greater than 5
amps
4. ¼ inch tubing (if not
purchased from SenTech, or if
copper tube is required by
local code
If any material is missing, or appears
to be damaged, contact Sentech
Corporation for assistance.
Identify Location for Monitor,
Sample Points and Alarms
Monitor Location: ASHRAE-15
specifies that the refrigerant monitor
is to be located in the mechanical
room. There are two interpretations
of this: the unit itself is to be
installed in the mechanical room; or
the sample point is to be located in
the mechanical room. Because the
IR-SNIF-1,2,3 is an active air draw
monitor, it can be installed nearly
anywhere in the vicinity of the area
to be monitored.
If local codes allow, the monitor can
be installed at the entrance to the
mechanical room, with the sample
tube routed into the mechanical
room and the fresh air reference
routed to an appropriate location. If
the monitor is located outside the
mechanical room, a fitting should be
installed and an exhaust tube routed
either into mechanical room, or
outdoors. If it is routed outdoors, it
must not be located near the fresh
air reference.
If local codes require the monitor to
be physically installed in the
mechanical room, it should be
installed in the best location for ease
of use and routing of sample and
fresh air tubing. If the monitor is
installed in the same room as the
8
sample pick-up-point, no exhaust
tube is required.
Caution: Liquid can affect
the performance of the
monitor. Pick-up-points
must be protected from
exposure to water and other
liquids.
Sample Location: Since the
monitor measures the concentration
of refrigerant in the air, the pick up
point should be mounted where it is
most likely to sense leaking
refrigerant. The criteria to consider
in selecting the sample pick up point
location include:
1. As close to the area of
potential leaks as possible.
On the ‘downstream’ side of
the air flow pattern in the
room.
2. Since refrigerants are
typically heavier than air, the
pick up tube should be
terminated approximately 18
inches above the floor.
3. The sample tube should be
located such that it will
require no more than 250 feet
(75 m) of tubing.
Reference Location: Since the
monitor compares a fresh air
reference to the sample, care must
be taken in choosing a location. The
fresh air reference tube should be
routed to a location that will be free
of refrigerant. This can be, but does
not necessarily have to be, located
outdoors. If the fresh air reference is
routed outdoors, the following criteria
should be used:
1. The tube end filter must be
protected from the elements.
Water, ice or insects can
partially obstruct the tube end
filter and change the
reference signal.
2. The tube end filter must be
located such that it can be
inspected as part of the
recommended quarterly
preventive maintenance.
3. The tube end filters must not
be located near exterior
HVAC equipment, or any
potential source of
refrigerant.
Exhaust Location: The exhaust
tube is required only if the monitor is
not located in the same room as the
sample pick-up-point. If an exhaust
tube is installed, it should be run to
the room being monitored, or to an
exterior location. An exhaust tube
must not be terminated near the
fresh air reference.
Alarm Location(s): A combination
horn/strobe alarm is recommended
for a mechanical room. The alarm
should be located inside the room
such that it can be seen and heard
from any area of the room.
Additionally, a strobe alarm can be
installed at each entrance to the
room to alert the user of an alarm
prior to entry to the room itself. Note
that the IR-SNIF-1,2,3 has visual
indicators of its alarm status. If the
monitor is installed at the entrance to
the room, a strobe should not also
be required.
9
Electrical Power Connection
Caution: All installation
wiring, service and
maintenance should be
performed by a qualified
electrician in accordance
with national and local
codes.
TB-1 Power Wiring: The IR-SNIF-
1,2,3 monitor is designed to operate
on only 110 or 240 vac, but not both.
It will operate on either 50 or 60 hz.
The power supply in the monitor
automatically detects the supply
voltage. The diaphragm pump is
designed to operate only on 110-120
vac or on 220-240 vac. Refer to
figure 6 for a diagram of the terminal
board.
Figure 6.
Connect primary power to TB1 as
follows:
1. Connect Earth Ground to
TB1-1
2. Connect AC Line to TB1-2
3. Connect AC Neutral or
Common to TB1-3
Caution: Verify that the
monitor is designed for the
appropriate line voltage.
Connection of the incorrect
voltage will damage the
unit.
It is strongly recommended that
power be supplied from a two-pole
circuit breaker, located in reasonable
proximity to the system. Power
MUST NOT be supplied by plugging
into a wall socket. The unit is a
continuous monitor, and as a
continuous monitor should be
provided dedicated, permanent
power. If a wall socket is used, there
is a risk that the unit will
inadvertently be unplugged, putting it
off-line.
Electrical Alarm Connections
Alarm-to-Relay Connection: The
IR-SNIF-1,2,3 monitor alarm relay
sockets have two sets of NO/NC dry
contacts. Refer to figure 7 for a
diagram of the relay socket.
Earth Ground
AC Line In
AC Neutral In
1 2 3 4 56 7 8
Analog 1 (rs485 TX)
Analog 2 (rs485 GND)
Analog GND (rs485 RX)
10
Figure 7.
The terminals are grouped as
follows:
Terminal 5 = Common
Terminal 1 = NC
Terminal 3 = NO
Terminal 6 = Common
Terminal 2 = NC
Terminal 4 = NO
Caution: Ensure that
external relay connections
do not touch relay control
terminals 7 and 8. A short
circuit from the alarm wiring
to the relay control wiring
could damage the monitor,
the alarms or both.
Alarm-to-Relay Connection: The
typical Alarm connection uses the
common terminal and normally open
(NO) terminal to switch AC line
voltage to the strobe alarm, horn
alarm or combination horn strobe.
Unless specified otherwise, SenTech
Corporation recommends the
following connections for alarms:
1. Strobe Alarm, or Strobe
portion of Combination
Horn/Strobe connected
through LOW RELAY,
terminals 6 and 4.
2. Horn Alarm, or Horn portion of
Combination Horn/Strobe
connected through MAIN
RELAY, terminals 6 and 4.
Caution: Ensure that
external relay connections
do not touch relay control
terminals 7 and 8. A short
circuit from the exhaust fan
wiring to the relay control
wiring could damage the
monitor, the alarms or both.
Fan-to-Relay Connection: The IR-
SNIF-1,2,3 monitor alarm relay can
support a load of up to 5 amps at line
voltage. The typical high-speed
exhaust fan will have a startup
current in excess of the relay rated
amp capacity. A pilot relay or
contactor will normally be required to
energize an exhaust fan. Unless
specified otherwise, SenTech
Corporation recommends the
following connections for exhaust
fans:
1. Fan, pilot relay or contactor
connected through HIGH
RELAY, terminals 6 and 4.
BMS-to-Relay Connection: The
IR-SNIF-1,2,3 monitor alarm relay
can provide alarm indications to the
typical building management system
(BMS) for Low, Main and High alarm
levels. This connection is normally
accomplished by switching a control
voltage through the normally open
4 3
2 1
8 7
6 5
Normally Open Terminals
Normally Closed Terminals
Common Terminals
11
(NO) contacts of the respective
relay. Unless specified otherwise,
SenTech Corporation recommends
the following relay connections for
building management systems:
1. BMS discrete input connected
through LOW, MAIN and/or
HIGH RELAYS, terminals 5
and 3.
Other External Connections
TB1 Outputs: The IR-SNIF-1,2,3 is
designed to provide two standard 0-
10 volt analog outputs or two
optional 4-20 mA analog outputs or
optional rs-485 interface for use with
ACC 070 SenTech COMM LINK PC
to Refrigerant Monitor Interface, or
ACC 065 SenTech Remote Control
Panel Interface. Refer to Figure 8
for a diagram of the terminal board.
Figure 8.
0–10 Volt Analog Outputs: The IR-
SNIF-1,2,3 monitor provides two 0
10 volt analog output proportional to
0–1000 ppm. Analog 1 provides a
signal proportional to the current
ppm level. Analog 2 provides a
signal proportional to the peak ppm
level measured. For applications
where the IR-SNIF-1,2,3 is installed
inside a mechanical room, the
analog 1 signal can be used to drive
an optional remote analog display at
the entrance to the room. This
signal could be used to provide an
analog input to building management
systems for remote monitoring of the
ppm level and for trending of levels.
This signal should NOT be used as a
replacement for discrete alarm relay
connections to a BMS. Analog
output connections are as follows:
1. Use twisted pair wire for
analog 1 connection, or four
conductor twisted wire for
both analog 1 and analog 2.
Typical low voltage solid
conductor wire is suitable for
this signal. Shielded cable is
preferred, but not always
required.
2. Route twisted pair wire into
the monitor and along the wire
harness from the back-plate
to the TB1 on the back-plate.
Secure the twisted pair
periodically to the wire
harness using tie wraps.
3. Connect the appropriate wires
to TB1-6, analog 1 plus, TB1-
7, analog 2 plus, and TB1-8,
reference ground.
4–20 mA Optional Analog
Outputs: The IR-SNIF-1,2,3
monitor provides optional 4–20 mA
analog outputs in place of the
standard 0-10 volt analog outputs.
To identify whether a monitor has 4-
20 mA analog output installed,
Earth Ground
AC Line In
AC Neutral In
1 2 3 4 56 7 8
Analog 1 (rs485 TX)
Analog 2 (rs485 GND)
Analog GND (rs485 RX)
12
examine the control board installed
on the door of the monitor. Locate
the chip sockets labeled U13 and
U14. U13 and U14 are located in
the center of the board,
approximately 3.5 inches and 2
inches from the bottom of the board.
If the monitor is configured for the
standard 0-10 volt analog outputs,
the sockets will be empty. If
configured for 4-20 mA outputs, the
sockets will have 4-20 mA drive
chips installed. Connection to the 4-
20 mA outputs is the same as for 0-
10 volt outputs.
RS-485 Optional Serial Output:
The IR-SNIF-1,2,3 monitor provides
an optional RS-485 interface in place
of the analog outputs. This interface
is for use with ACC 070 SenTech
COMM LINK PC to Refrigerant
Monitor Interface, or ACC 065
SenTech Remote Control Panel
Interface.
This interface provides the ability to
display the refrigerant levels in each
area and modify setpoints via a pc
based interface. Used in conjunction
with the ACC 070 COMM LINK, the
interface allows for complete remote
monitoring of multiple refrigerant
monitors in the same facility.
This interface also provides the
ability to display the refrigerant levels
in each area and modify setpoints
via a digital remote control interface.
Used in conjunction with the ACC
065 Remote Control Panel Interface,
the RS-485 interface allows for
complete remote control and
monitoring of multiple refrigerant
monitors in the same facility.
To identify whether a monitor has rs-
485 interface installed, examine the
control board installed on the door of
the monitor. Locate the connectors
labeled P6 and P8. Connector P6 is
located on the upper left corner of
the board (as you look at the board
from inside the door). Connector P8
is located on the center of the right
side of the board. If the rs-485
interface is installed, the cable
normally connected to the P8 (right
side) will be absent, and a cable will
be connected to P6 (upper left
corner). If your monitor is configured
for analog output, and rs-485 is
required instead, contact SenTech
Corporation technical support for
assistance.
RS-485 digital connections are as
follows:
1. Use twisted wire for RS-485
connection, either twisted
triple wire, or four conductor
twisted wire. Shielded cable
is preferred, but not always
required.
2. Route twisted pair wire into
the monitor and along the wire
harness from the back-plate
to the TB1 on the back-plate.
Secure the twisted wire
periodically to the wire
harness using tie wraps.
3. Connect the transmit
conductor to TB1-6.
4. Connect the receive
conductor to TB1-8.
5. If twisted triple wire is used,
connect the remaining wire to
TB1-7, reference or shield
ground.
6. If two twisted pairs are used,
connect one conductor from
13
each pair to TB1-7, reference
ground or shield.
Custom Control Inputs/Outputs:
The IR-SNIF-1,2,3 monitor has the
capability to be programmed for
additional optional inputs or outputs.
The control circuit in the monitor is
versatile and can accommodate
additional analog or discrete
measurement and control signals.
This circuit also has the capability to
provide additional discrete control
signals. Please contact SenTech
Corporation technical support to
determine whether specific
requirements can be provided.
14
STARTUP and PROGRAMMING
Apply Power
Caution: Before applying
power, double-check all
wiring.
Once the installation has been
completed, and wiring has been
checked, close the door to the
monitor and apply power. The unit
will go through its normal startup
checks and warm-up procedure. It is
important that the door remain
closed to ensure a proper operation.
Initial Screens
If the IR-SNIF-1,2,3 has never been
programmed, it will access default
memory settings and display the
following screen:
Once the defaults have been stored,
or if the monitor has been previously
programmed, the following screen
will be displayed. Since the monitor
is factory calibrated, and factory
programmed during quality control, it
should display this screen on initial
application of power.
Following memory initialization, the
monitor will display the copyright
screen.
The monitor will next display two
Contact and Model Information
screens. (Note: these screens can
be accessed anytime during normal
operation by pressing the “*” key.)
Following display of the contact and
model information screens, the IR-
SNIF-1,2,3 will restore any alarms
that have been saved into memory.
The corresponding lights and relays
will be energized. Any external
alarms, exhaust fans or building
management system connections
will be activated. The monitor will
then display the following optics
warm-up screen.
restore from memory
RESETTING DEFAULTS
SenTech
Corporation
Phone 1-888-248-1988
www.sentechcorp.com
Model IR-SNIF-1,2,3
Version 3017
Option Code 0
www.sentechcorp.com
SenTech Corporation
IR-SNIF-1,2,3
Gas Monitor
Copyright (c) 2003
Optics Warm up
Timer 540 12:00
Press EN
T for Menu
15
On completion of the warm-up, the
monitor will enter Auto zero mode
and begin normal operation.
If during the startup, a fault condition
is detected, follow the instructions on
the screen, and refer to the trouble-
shooting section of this manual.
Normal Operation
During normal operation, the monitor
will display one of two basic screens.
First, it will measure the fresh air
reference and display the Auto Zero
screen. Then it will measure the
sample air and display the Auto
Sample screen.
The Auto Zero measurement will
take approximately 25 seconds, and
will be performed approximately
every 3 minutes. If the monitor
senses refrigerant in the sample air,
it will lengthen the Auto Zero time to
approximately 45 seconds.
The Auto Sample measurement will
be taken for between 1 minute and 3
minutes, depending on the tube
length programmed into the monitor.
This screen will display the ppm
reading, the time of day and the
refrigerant programmed for the
sample area.
Initial Programming
Once the IR-SNIF-1,2,3 has
completed warm-up, and entered
Auto Zero, it can be programmed.
While in Auto Zero or Auto Sample
modes, press the “ENT” key to
access the main menu.
Key selections 1, 2 and 3 are used to
display current alarms, manually
initiate Auto Zero and enter the
Manual Override mode. These
functions are discussed in Appendix
A of manual.
To program the monitor, press the
“4” key to enter Setup. The monitor
will require a password to access the
setup screens. There are five setup
passwords: 111, 222, 333, 444, 999.
The first four passwords can be
changed to user-defined codes. 999
cannot be changed.
If an incorrect password is entered,
the fourth line of the screen will
change to “Access Denied” and the
monitor will return to normal
operation.
** Auto Zero**
Timer 24 12:00
Press ENT for Menu
Auto Sample AREA 1
PPM 0 12:00
R-134A
Press ENT for Menu
1)…Alarms
2)…Rezero
3)…Manual
4)…Setup ABORT
* SenTech Monitor *
ENTER PASSWORD
Followed By ENT
0
* SenTech Monitor *
ENTER PASSWORD
Followed By ENT
ACCESS DENIED
16
When the correct password has
been entered the monitor will display
the setup screen.
Press the “3” key to enter System
Setup. System setup consists of two
screens that allow the user to
change passwords, change system
flags, test the alarm circuits and set
the time and date. The user can
toggle from one screen to the other
by using the left and right arrow
keys.
Key selections 1 and 3 are used to
change passwords required to enter
setup and to test the alarm relay
integration with building wiring.
Refer to Appendix A of manual for
instructions to change passwords.
The alarm test function is described
in the Final Test section of this
manual.
Press the “2” to enter the System
Flags screens. The system flag
screen will display information for
nine settings, displayed on two
screens. Press the ENT key to
move the cursor from one line to the
next, and press the left arrow key to
move from one line to the previous.
The autozero flag can be used to
limit the frequency of autozero
cycles. It can be set between 0 and
100. If a 0 is entered, the monitor
will enter an autozero cycle after
every area is sampled (this is the
normal default configuration).
Increasing this number will allow the
monitor to skip the autozero cycle if
the raw measurement from the IR-
Bench has not changed significantly.
That is, if the raw signal varies by
less than plus or minus 10 millivolts,
and the autozero flag is set to 10, the
monitor will not perform an autozero
cycle. NOTE: This is effectively
reducing the extreme low-level
sensitivity of the monitor. If this
feature is desired, set this flag by
increasing it in small steps, 1 or 2
digits at a time, until the monitor
stops autozeroing after every zone.
The password flag can be set to
either 0 or 1. If a 1 is entered, the
monitor will require the user to enter
a password to perform any functions
of the monitor. This feature is useful
if the monitor is installed in a public
area, and controlled access to the
monitor is needed. This flag is set to
0 by default.
Press the “ENT” to move the cursor
to the horn relay flag. The horn relay
flag can be set to 0, 1, 2 or 3. This
flag changes the function of the horn
relay to control an audible alarm.
With the flag set to the 0, the horn
relay will be disabled. The monitor
can be programmed to allow the
horn relay to be de-energized while
the monitor is still in alarm. This
1)…IR Setup
2)…N/A
3)…System Setup
4)…Contact ABORT
1)…Change Code
2)…System Flags
3)…Alarm Test
ABORT
-
>
4)…Date/Time
<
-
ABORT
17
feature is useful when the user is
troubleshooting an alarm, and wants
to work in silence. Set the horn relay
flag to 1 to activate the horn relay
when the monitor is in LOW alarm.
Set the horn relay flag to 2 to
activate the horn relay when the
monitor is in MAIN alarm. Set the
horn relay flag to 3 to activate the
horn relay when the monitor is in
HIGH alarm. This flag is set to 2 by
default.
The unit number flag is used to
identify the monitor on a RS-485
network, if that option has been
purchased. This flag is set to 1 by
default.
Press the “ENT” key to move the
cursor to the next entry. When all
entries have been viewed, press the
“ENT” key again to display the
second system flag screen
The slope flag is used for
circumstances where an individual
zone might be exposed to large
levels of refrigerant. This flag will
hold the monitor in its current mode,
whether it be autosample or
autozero, if the raw measurement
has not leveled off to a constant
measurement. For instance, after an
extremely large level of refrigerant
has been measured, the monitor
might run in autozero longer than
expected if the measured level is still
falling. Set this flag to the factory
default of 50 if no large levels are
expected. Set this flag lower if large
levels are expected.
Press the “ENT” key to move the
cursor to the TWA ALARM flag. This
flag is reserved for future
implementation of TWA
measurement. This flag should be
left at the factory default of 0.
Press the “ENT” key to move the
cursor to the FULL SCALE flag. This
flag is used to adjust the full scale
measurement for the analog output.
The factory default is 1000, meaning
that the 0-10 volt analog output
corresponds to 0-1000 ppm. This
flag should be left at the factory
default unless a custom
measurement range has been
implemented in the monitor. Consult
factory technical support for further
information if needed.
Press the “ENT” key to move the
cursor to the TWA refresh flag. This
flag is used to save peak ppm
measurements if Trending is not
implemented. A TWA refresh rate of
5 minutes corresponds to a
theoretical ten-hour time weighted
average (5 minute refresh rate times
120 saved data points yields ten-
hour average). As with the TWA
ALARM flag, this feature is not yet
implemented.
Press the “ENT” key to move the
cursor to the next entry. When all
entries have been viewed, press the
SLOPE FLAG 50 -
TWA ALARM 0
FULL SCALE 1000
TWA REFRESH 5
AU
TOZERO FLAG 0 -
PASSWORD FLAG 0
HORN RELAY FLAG 0
UNIT NUMBER FLAG 1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50

SenTech IR-SNIF-3 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI