Redundancy for highly critical applications.
www.mgeups.com
Can be built in to high density racks.
Single phase UPS
Pulsar MX
4/5/8/10/15/20 kVA
Continuous power supply
Two front access hot-swappables
sub-modules (power and battery)
for maintenance without load
interruption.
Automatic battery test (test period
can be set).
Internal bypass built-in to supply the
load even if the UPS fails.
Large input voltage and frequency
ranges to avoid using the batteries
unnecessarily.
Flexible
Can be used as a free-standing tower
unit or 19" rack-mounted: only 3U
for Pulsar MX 4000 and 5000,
16U for Pulsar MX Frame
LCD multilingual display with mimic
and LEDs for rapid view of the UPS
status, diagnostics and event log
Outputs: IEC 10A and 16A outlet
sockets and hardwired outputs
Built-in Powershare system for remote
reboot of the equipment connected,
sequential start-up or load shedding
while operating from battery to
maintain the power to critical loads.
Pulsar MX Frame is compatible with
three phase or single phase supplies.
Backup time: 10 mins up to 2 hours
by adding 3U battery extension
modules.
Minimum total cost
of ownership (TCO)
More power with an output
power factor of 0.9.
When the power supply needs
to be upgraded, the Pulsar MX
4000 and 5000 can be paralleled
to provide 8 kVA or 10 kVA
using the ModularEasy kit:
without extra cost on the
initial purchase.
Pulsar MX Frame is a modular
system with 5 kVA sub-modules
paralleled to provide up to 20 kVA
or 15 kVA with redundancy.
High performance UPS upgradeable
from 4 kVA to 20 kVA
Can be used for 20 to 110
servers, ideal for:
departmental networks, servers
and workstations
Pulsar MX: 10 minutes
backup, tower/rack
mounting (3U), mimic,
LCD display.
Pulsar MX has 2 sub-modules
(power electronics and battery)
which are hot swappable.
Pulsar MX Frame 15
and 20 kVA tower
and rack-mounting (16U),
modular system with
5 kVA sub-modules.
Paralleling 2 Pulsar MXs
using ModularEasy for 2N
or N+1 redundancy.
The power level can be upgraded simply and without
interruption for the existing loads as the number
of loads supplied is increased.
PULMX515UK.qxd 16/02/06 15:13 Page 1
Single phase UPS - Pulsar MX
Headquarters
140, avenue Jean-Kuntzmann
ZIRST - Montbonnot Saint-Martin
38334 Saint-Ismier Cedex - France
Tel.: +33 (0)4 76 18 30 00
PULMX515UK-02/06
Due to developments in technical standards and the equipment described in this document, we cannot be held liable for compliance with the characteristics indicated by the images and text unless they are confirmed by us. All the brand names referred to in this document are protected by copyright.
Publication: MGE UPS SYSTEMS (February 2006) - Design and rewriting: 3c-evolution.com - Integration: Pamplemousse: +33 4 79 37 87 66 – Translation: TTP: +33 4 78 66 47 99.
Specifications
Pulsar MX 4000 RT Pulsar MX 5000 RT Pulsar MX 15000 Frame 16U Pulsar MX 20000 Frame 16U
Pulsar MX RT Tower or rack-mounting: standard backup time
68 501 68 504 68 513
(14)
68 514
(15)
Pulsar MX RT Netpack: standard backup time
68 502 68 505
(with rack kit, (with rack kit,
+ NMC + rack kit casters, NMC card) casters, NMC card)
Pulsar MX EXB RT : battery extension module 68 515 68 527
(Pulsar MX Frame EXB empty to be fitted with 4 or 8 Battery sub-modules)
Pulsar MX ModularEasy: paralleling kit (2 Pulsar MX)
68 520 -
MX / EXB RT Rack Kit: rail kit for 19" rack mounting
68 002 -
IEC 32 A kit , 2 X 2 m long cables: male to
68 525 -
hardwired and female to hardwired
Pulsar MX Battery / Power electronics sub-module
68 524 / 68 522 68 524 / 68 523 68 524 / 68 523
Part numbers
1: Available from November 2006. 2: 2 Pulsar MXs can be paralleled using ModularEasy. 3: At 70% load. 4: 4 IEC C13 (10A) 2 m long cables for use with retention clips (8 cables for use with Pulsar MX Frame).
5: Frequency conversion for non-paralleled units only. 6: Economy mode, 91% in normal mode. 7: At 70% nominal rating with power factor 0.7 typical values after 3 charge/discharge cycles, with 3-5 year old
batteries. Weekly battery test without interrupting the load (daily or monthly if required). EXB compatible with 0.8 power factor loads. 8: With Pulsar MX Frame EXB (4 battery units). 9: With Pulsar MX Frame EXB
(8 battery units). 10: Solution-Pac CD-ROM supplied as standard. 11: Applicable to US models. 12: 50 dbA above 5 kVA. 13: Depending on the country, see www.mgeups.com/service. 14: 68 513 = 68 526
(empty Pulsar MX Frame) + 3 x 68 524 + 3 x 68 523. 15: 68 514 = 68 526 (empty Pulsar MX Frame) + 4 x 68 524 + 4 x 68 523.
Pulsar MX RT 4 kVA 5 kVA 15 kVA
(1)
20 kVA
(1)
Rating (kVA) / (kW) 4 kVA / 3,6 kW 5 kVA / 4,5 kW 15 kVA / 13, 5 kW 20 kVA / 18 kW
Paralleling
Maximum rating /
8 kVA / 4 kVA + 4 kVA redundancy 10 kVA / 5 kVA + 5 kVA redundancy 15 kVA / 10 kVA + 5 kVA redundancy 20 kVA / 15 kVA + 5 kVA redundancy
redundancy
(2)
5 kVA + 2 x 5 kVA redundancy 10 kVA + 2 x 5 kVA redundancy
Inputs
Technology VFI-SS-113, on-line double conversion with power factor correction, convection cooled static bypass switch
Number of phases, input connections L + N, terminals up to 6 mm
2
L + N or 3P + N, terminals up to 35 mm
2
,
separate or common AC normal and AC bypass
Nominal voltage 200/208/220/230/240/250 V 200/208/220/230/240/250 V (L + N) or 380/400/415 V (3P + N)
Voltage range without using battery
(3)
120 - 280 V 120 - 280 V (L + N), 250 - 465 V (3P + N)
Input frequency range, THDI 40-70 Hz, < 7%
Outputs
Output connections
(4)
terminals + 8 IEC C13 (10A) + 2 IEC C19 (16A) terminals + 16 IEC C13 (10A) + 4 IEC C19 (16A)
Remotely controlled Powershare sockets 2 groups (2 IEC C13 10A per group) 2 groups (4 IEC C13 10A per group)
Output voltage and frequency
(5)
, THDU, efficiency
(6)
200/208/230/240 /250 V, 50 / 60 Hz autoselect, frequency converter as standard, <2%, 97%
Backup time
(7)
Pulsar MX standard backup time 10 minutes 8 minutes 8 minutes
Pulsar MX + EXB / MX + 2 EXB / MX + 3 EXB 45 / 80 / 120 minutes 35 / 60 / 95 minutes 20 minutes
(8)
/ 35 minutes
(9)
Communications
Slots 1 minislot or 2 minislots (Frame) compatible with Minislot NMC, NMC ModBus/JBus, MC Contacts/Serial
Ports Remote Power off (RJ11), 5 output contacts (DB9), setup using Solution-Pac
(10)
(USB and DB9-serial ports),
EXB module detection (RJ45), paralleling (DB 15)
Operating conditions, standards and approvals
Performance, safety, EMC, surge protection IEC/EN 62 040-3, IEC/EN 62 040-1-1, IEC/EN 62 040-2 class A (class B as option), 4 kV IEC 61 643, UL 1778 and CSA 22.2
(11)
Operating temperature, noise, approvals, guarantee
0°C to 40°C continuous, 45 dbA
(12)
, UL, TüV, GS mark, CB, C-Tick, CE, IEC 61 931, one year
(13)
Dimensions / weight
Pulsar MX RT standard backup tower 444.5 mm high x 130.6 mm wide x 735 mm deep / 57 kg
To wer 690 mm high (795 mm casters) x 444.5 mm wide x 735 mm deep /
Pulsar MX RT standard backup rack
3U x 444.5 mm wide compatible with 800-1000 mm deep rack
250 kg Rack 16U x 444.5 mm wide, compatible with 800-1000 mm deep rack
MX EXB battery unit tower / rack
444.5 mm high x 130.6 mm wide x 650 mm deep / 3U x 444.5 mm wide / 70 kg
dimensions same as MX Frame / 230 kg for 15 kVA, 290 kg for 20 kVA
Pulsar MX ModularEasy, paralleling kit dimensions same as EXB battery unit / 10 kg -
Communications
Solution Pac 2 suite supplied for remote
supervision.
MGE's Enterprise Power Manager for supervision
via Ethernet and Teleservice. EPM is compatible
with standard network management systems
(Tivoli, CA unicenter, HP Openview).
Compatible with Network Shutdown Module
for monitoring a number of UPSs and shutting
down the servers on the network.
MGE PowerServices™
1 year guarantee, including batteries.
Associated services
(1)
Extended guarantee.
Commissioning.
Teleservice (in-band and out-of-band).
Personalised maintenance contracts.
1: Depending on the country, see www.mgeups.com/services.
2 IEC 16A outlet sockets
Output circuit protection
1 minislot for NMC, Modbus/JBus
or MC Contacts/Serial card
RJ11 remote power off
RJ45 EXB battery module detection
DB9 with 5 output contacts
EXB battery extension module power connector
DB 15 paralleling
DB 9 serial and USB ports:
Setup and supervision
Input Output
8 IEC 10A outlet sockets