580J***(D,F)
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNIT
TWO STAGE COOLING CAP ACITY CONTROL WITH NOVATIONt COIL
SIZES 08, 12, 14 WITH PURONR (R--410A) REFRIGERANT
Submittal Data
®
This product has been designed and manufactured
to meet Energy Star® criteria for energy efficiency.
However, proper refrigerant charge and proper air
flow are critical to achieve rated capacity and effi-
ciency. Installation of thi s product should follow all
manufacturer’s refrigerant charging and air flow in-
structions. Failure to confirm proper charge and
air flow may reduce energy efficiency and short-
en equipment life.
DESCRIPTION
580J***(D,F) units are hi gh--efficiency, single--packaged
electric cooling, gas heating units that are pre--wired and
pre--charged with PuronR (R--410A) HFC refrigerant.
Units utilize an all aluminum flat micro --channel tube
with louvered fins c ondenser coil—NOVATIONt.The
units are factory tested in both heating and cooling modes.
These units meet the ASHRAE 90.1--2007 and Energy
Star minimum efficiency levels as well as also meeting
2010 efficiency standa rds.
STANDARD FEATURES
Base Unit
S Puron (R-- 410A) HFC refrigerant
S ARI certified efficiency levels up to 11.1 EER
S Rated in accordance with ARI Standard 360
S Designed in accordance with Underwriters’ Laboratories Std
1995 and listed by UL and UL, Canada
S Two--stage cooling capacity control
S Non -- corrosive composite sloping design; side or center drain
condensate pan. Meets ASHRAE Standard 62
S Standard cooling operating range from 40_Fupto115_F
(4_Cupto46_C). Field installable accessory extends the
minimum down to --20_F(--29_C).
S Convertible from vertical to horizontal airflow for slab mounting
S Two--inch disposable return air filters
S Thru--the--bottom power and gas entry capability
S Single point gas and electric connections
S 24--volt control circuit protected with resettable circuit breaker
and 75--VA transformer
S Belt drive, constant torque, permanently lubricated
evaporator–fan motor
S Totally enclosed condenser motors with permanently lubricated
bearings
S Low--pressure and high--pressure switches
S Full perimeter base rail with built--in rigging adapters and fork
truck slots
S Centralized Terminal Board for component and unit wiring
connections
Cabinet
S Access panels with easy grip handles and NO--STRIP screw
collar
S Pre--painted exterior panels and primer--coated interior panels
tested to 500 hours salt spray protection
S Fully insulated cabinet
S Tool--less filter access door
Refrigerant System
S Acutrolt refrigerant metering system
S Liquid line filter drier
S Scroll compressors with internal line--break overload protection
S Copper
tube, aluminum fin evaporator coil
S NOVATION all aluminum condenser coil
S Removable gauge line plugs for reading refrigerant pressure
with unit panels in place
Gas Heat
S IGC solid -- state gas heat exchanger control for on -- board
diagnostics, anti--cycle protection, LED error code designation,
burner control logic and energy saving indoor fan motor delay
S Gas efficiencies up to 82%
S Designed in accordance with ANSI Z21.47 (design and test
standard for gas furnaces) and ANSI Z233.1 (National Fuel Gas
code relating to appliance installation requirements)
S Induced draft combustion
S Redundant gas valve, with up to 2 stages of heating
S Flame roll--out safety protector
S Solid--state electronic direct spark ignition system
2
STANDARD FEATURES (cont.)
Standard Warranty
S 15--year gas heat exchanger -- Stainless Steel
S 10--year gas heat exchanger -- Aluminized
S 5--year compressor
S 3--year NOVATION condenser coil
S 1--year parts
SUBMITTAL DATA
Job Na m e
Architect
Enginee r
Contrac tor
Unit Designation
PERFORMANCE DATA
Unit Operating Weight lb
Cooling
Gross Total Capaci ty: Btuh
at Condenser Air Temperature _F
Gross Sensible Capacity: Btuh
Compressor Power Input: kW
Indoor Entering db _Fwb _F
Airflow External Static Pressure in.wg
Indoor Fan Motor Size Hp
Exhaust Fan Motor Size Hp
Curb Weight lb
Heating
Heating Capacity:
Stage 1 Btuh
Stage 2 Btuh
Heating Capacity Total Btuh
Stage 1 kW
Stage 2 kW
Heating Capacity Total kW
ELECTRICAL DATA
Power Supply to Unit Volts Phase Hz
Minimum Circuit Amps Maximum Overcurrent Protection
580J***(D,F)
3
OPTIONS AND ACCESSORIES
FACTOR Y--INSTALLED OPTIONS (FIOPs)
j Open protocol RTU--MP controller communicate s to
LON, MODBUS, BACNET and Johnson N2 protocols.
j Through the base connectors for gas and electric
conduit/piping
j Stainless steel gas heat exchanger (includes tubes,
vestibule plate and collector box)
j Economizer with dry bulb sensing and barometric
relief
j Economizer with enthalpy sensing and barometric
relief
j 2 position motorized outdoor air damper
j Non--fused disconnect
j Powered 115--volt convenience outl et
j Non--powered 115--volt convenience outlet
j High static evaporator fan motor
j Return Air smoke detector
j Supply Air smoke detector
j CO
2
sensor
j Condenser hail guard -- louvered style
OPTIONAL WARRANTIES
j Complete Unit Parts only up to 5 years
j Complete Unit Parts and Labor up to 5 years
Many other optional wa rranties are a vaila ble.
See the Commercial Start--Up and Optional Extended
Warranty Price price pages for further information.
FIELD INSTALLED ACCESSORIES
j Economi$ert IV-- electromechanical, gear driven with
Belimo actuator (2--10v DC signal) and controller
j Economi$ert2 --compatible with DDC controls; gear
driven with Belimo actuator (4 --20mA) signal and
no controller
j Power exhaust
j Two--position motorized outdoor air damper
j Manual outdoor air damper 25%
j Manual outdoor air damper 50%
j Roofcurb -- 14 inch (356mm) tall
j Roofcurb -- 24 inch (610mm) tall
j Thru--the--bottom connections--electrical only
j Thru-- the--bottom connections--electrical and gas
j Condenser hail guard -- louvered style
j Flue shield
j Flue discharge deflector
j Liquid propane (LP) conversion kit
j High altitude conversion kit
j Phase monitor (loss of phase/phase reversal)
j Winter start kit, down to 25_F(--4_C)
j Low ambient head pressure controller,
downto0_F(--18_C)
j Low ambient head pressure controller,
down to --20_F(--29_C)
j Time Guard II compressor anti--cycle protection
Economizer Sensors
j Single Dry bulb control
j Differential Dry bulb control
j Single enthalpy control
j Differential enthalpy control
j CO
2
-- wall mounted
j CO
2
-- duct mounted
j CO
2
-- unit mounted
580J***(D,F)
4
CERTIFI ED DIMENSION 580J*08, 12D
C08500
580J***(D,F)
5
CERTIFI ED DIMENSION 580J*08, 12D
C08501
580J***(D,F)580J***(D,F)
6
CERTIFIED DIMENSION 580J*14D
C08502
580J***(D,F)
7
CERTIFIED DIMENSION 580J*14D
C08503
580J***(D,F)580J***(D,F)
8
ROOF CURB DETAILS
580J*08,
580J*08,
12,
12,
14(D,F)
14(D,F)
ROOFCURB
ACCESSORY
CRRFCURB003A01
CRRFCURB004A01
1’ - 2”
(356)
2’ - 0”
(610)
UNIT SIZE
UNIT SIZE
C08547
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurr ing obligations.
E2008 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed i n U.S.A. Edition Da te: 11/08
Replaces: NEW
Catalog No.SUB580J ---03
580J***(D,F)
/