Board Dimensions (L x W x H) (approximate):
8.5” (215.9mm) x 4.5” (114.3mm) x 2” (50.8mm)
Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.com
Ø
0.156”
(3.96mm)
3.7”
(93.98mm)
0.5”
(12.7mm)
6.7”
(170.18mm)
0.75”
(19.01mm)
4.5”
(114.3mm)
8.5”
(215.9mm)
UL Recognized component for Access Control System Units (UL 294)
Standard for Safety for Fire Protective Signaling Systems (UL 1481).
Agency Approvals
Specifications
AL1024ULXB2 is a UL Recognized power supply/charger that converts a 115VAC,
60Hz input into a single 24VDC non power-limited output.
AL1024ULXB2
UL Recognized Power Supply/Charger
Rev. DSAL1024ULXB2_03152013
Overview
AL1024ULXB2
Agency Listings:
• ULRecognizedcomponentforAccessControl
System Units (UL 294), Power Supplies for
Fire Protective Signaling Systems (UL 1481).
Input:
• Input115VAC/60Hz,4.2amp.
Output:
• 24VDCoutput.
• 8ampcontinuoussupplycurrentwith10amp
supply current during alarm.
• Filteredandelectronicallyregulatedoutput.
• Shortcircuitandthermaloverloadprotection.
• MaximumRipple:250mVP/P
Battery Backup:
• Built-inchargerforsealedleadacidor
gel type batteries.
• Maximumchargecurrent3.6amp.
Battery Backup (cont’d):
• Automaticswitchovertostand-bybattery
when AC fails.
• Zerovoltagedropwhenswitchedovertobattery
backup.
Visual Indicators:
• ACinputandDCoutputLEDindicators.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatteryandbatterypresencesupervision
(form“C”contacts).
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• 98.27BTU/Hr.
• SystemACinputVArequirement:483VA.
Mechanical:
• Productweight(approx.):1.15 lbs. (0.52 kg).