Altronix MAXIMAL3D Installation guide

Type
Installation guide
Altronix Corp.
140 58th St. Brooklyn, NY
Maximal D Series
Single Power Supply
Access Power Controllers (fused)
Models Include:
Maximal3D
- 12VDC @ 5A or 24VDC @ 5.4A.
- Sixteen (16) PTC protected Class 2 Rated power-limited outputs.
Maximal5D
- 12VDC @ 9A.
- Sixteen (16) PTC protected Class 2 Rated power-limited outputs.
Maximal7D
- 24VDC @ 9.42A.
- Sixteen (16) PTC protected Class 2 Rated power-limited outputs.
Rev. MSCB052219 More than just power.TM
Installing Company: _______________ Service Rep. Name: __________________________________
Address: _____________________________________________ Phone #: __________________
Installation Guide
- 2 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide
Table of Contents:
Maximal D Series Overview ..................................................pg. 3
Maximal D Series Configuration Chart ..........................................pg. 3
Maximal D Series Features ...................................................pg. 3
Maximal D Installation Instructions .............................................pg. 4
Maintenance ..............................................................pg. 6
Power Supply Board LED Diagnostics ...........................................pg. 6
Access Power Controller LED Diagnostics .......................................pg. 6
Power Supply Board Terminal Identification .....................................pg. 7
Access Power Controller Terminal Identification ..................................pg. 7
Power Supply Board Stand-by Battery Specifications ..............................pg. 7
Power Supply Board Output Voltage Settings .....................................pg. 8
Access Power Controller Typical Application Diagram (for each ACM8CB) ..............pg. 8
Maximal3D and Maximal5D Battery Hookup and Tamper Switch Installation ...........pg. 9
Maximal7D Battery Hookup and Tamper Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . pg. 10
NEC Power-Limited Wiring Requirements for Maximal3 ............................pg. 11
NEC Power-Limited Wiring Requirements for Maximal5 ............................pg. 12
NEC Power-Limited Wiring Requirements for Maximal7 ............................pg. 13
FACP Hook-Up Diagrams ....................................................pg. 14
Enclosure Dimensions .......................................................pg. 16
Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide - 3 -
Maximal D Series Overview:
Maximal Access Power/Controllers distribute and switch power to access control systems and accessories. They
convert a 115VAC 60Hz input into sixteen (16) independently controlled 12VDC or 24VDC Class 2 Rated PTC
protected power-limited outputs. The outputs are activated by an open collector sink or normally open (NO) dry
trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc. Units will route power to a variety
of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The FACP
Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire
alarm disconnect feature is individually selectable for any or all of the sixteen (16) outputs. All interconnecting
equipment must be UL Listed.
Maximal D Series Configuration Chart:
Altronix
Model
Number
Power Supply
Board Output
Voltage Options
Class 2 Rated PTC
Protected Power-
Limited Outputs
(auto-resettable)
Maximum Current
Per ACM8CB Output
115VAC 60Hz Input
(current draw)
Power Supply Board
Input Fuse Rating
Power Supply
Board Battery
Fuse Rating
Agency Listings
and File Numbers
Maximal3D 12VDC @ 5A or
24VDC @ 5.4A 16 2.5A 3.5A 5A/250V
UL File # BP6714
UL 294* - UL Listed for
Access Control
System Units.
General Signaling
Equipment Evaluated to
CSA Standard
C22.2 No.205-M1983
California State Fire
Marshal Approved
Maximal5D 12VDC @ 9A 16 2.5A 2.6A 5A/250V 15A/32V
Maximal7D 24VDC @ 9.4A 16 2.5A 4.4A 5A/250V 15A/32V
*ANSI/UL 294 7th Ed. Access Control Performance Levels:
Destructive Attack - I; Endurance - I; Line Security - I; Stand-by Power - I, IV.
MaximalD Series Features:
Sixteen (16) independently trigger controlled outputs. Output options:
a) Sixteen (16) Fail-Safe filtered and electronically regulated power outputs.
b) Sixteen (16) Fail-Secure filtered and electronically regulated power outputs.
c) Any combination of the above.
Sixteen (16) Access Control System trigger inputs. Input trigger options:
a) Sixteen (16) normally open (NO) dry trigger inputs.
b) Sixteen (16) open collector inputs.
c) Any combination of the above.
Sixteen (16) unswitched filtered and electronically regulated aux. power outputs (outputs are rated @ 2.5A).
Red LEDs on ACM8CB board indicate individual outputs are triggered (relays energized).
Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the sixteen (16) outputs.
Fire Alarm disconnect input trigger options:
a) Normally open (NO) or normally closed (NC) dry trigger input.
b) Polarity reversal input from FACP signaling circuit.
Green LED on ACM8CB board indicates FACP disconnect is triggered.
FACP output relay indicates that FACP input is triggered (form “C” contact rated @ 1A/28VDC,
not evaluated by UL).
Power supply input is factory installed. It provides common power for both ACM8CB boards and all
connected access control devices.
ACM8CB board main fuses are rated @ 10A. Output PTCs are rated @ 2.5A.
Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current is 0.7A for AL600ULXB and AL1012ULXB power supply boards.
- Maximum charge current is 3.6A for AL1024ULXB2 power supply board.
Altronix Corp.
140 58th St. Brooklyn, NY
- 4 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide
Automatic switch over to stand-by battery when AC fails.
Zero voltage drop when unit switches over to battery backup (AC failure condition).
Short circuit and thermal overload protection with auto reset.
Green AC input and red DC output LED indicators on power supply board(s).
AC fail supervision (form “C” contact rated @ 1A/28VDC).
Battery fail and battery presence supervision (form “C” contact rated @ 1A/28VDC).
Enclosure accommodates up to four (4) 12VDC/12AH batteries.
Enclosure dimensions (H x W x D): 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.8mm).
MaximalD Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes
and authorities having jurisdiction. Product is intended for indoor use only.
Power Supply Board LED Diagnostics (pg. 6)
Access Power Controller LED Diagnostics (pg. 6)
Power Supply Board Terminal Identification (pg. 7)
Access Power Controller Terminal Identification (pg. 7)
Power Supply Board Stand-by Battery Specifications (pg. 7)
Power Supply Board Output Voltage Settings (pg. 8)
Access Power Controller Typical Application Diagram (pg.8)
FACP Hook-up Diagrams (pg. 14)
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top three key holes
in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding.
Place the enclosure’s upper keyholes over the three upper screws; level and secure. Mark the position of
the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the
enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to
tighten all screws (Enclosure Dimensions, pg. 16).
2. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green
grounding conductor lead. Connect unswitched AC power (115VAC 60Hz) to the terminals marked [L, N]
on power supply board. Green “AC” LED on power supply board will turn on. This light can be seen
through the LED lens on the door of the enclosure. Use 14 AWG or larger for all power connections.
Keep power-limited wiring separate from non power-limited wiring.
Minimum 0.25” spacing must be provided (Figs. 5-7, pgs. 10-12).
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or
servicing equipment. There are no user serviceable parts inside.
Refer installation and servicing to qualified service personnel.
3. Select desired DC output voltage by setting SW1 to the appropriate position on the Maximal3D power
supply, (Figs. 1 and 1a, pg. 8). Maximal5D power supply is factory set at 12VDC and Maximal7D power
supply is factory set at 24VDC.
4. Measure the output voltage of the unit before connecting any devices to ensure proper operation.
Improper or high voltage will damage these devices.
5. Output options (Fig. 2, pg. 8):
The unit will provide either sixteen (16) switched power outputs.
(a) Fail-Safe Switched Power outputs:
For Fail-Safe operation connect the positive (+) input of the access control devices to terminal
marked [NC]. Connect the negative (–) input of the access control devices to terminal marked [COM].
(b) Fail-Secure Switched Power outputs:
For Fail-Secure operation connect the positive (+) input of the access control devices to terminal
marked [NO]. Connect the negative (–) input of the access control devices to terminal marked [COM].
6. Auxiliary Power outputs (unswitched):
Connect access control devices that require constant power to the terminals marked [C] positive (+) and
[COM] negative (–).
7. Input trigger options (Fig. 2, pg. 8):
(a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open collector sink inputs.
Connect access control panel outputs, keypads, push buttons, REX PIRs, etc. to terminals marked [IN]
and [GND].
Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide - 5 -
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink positive (+) to terminals marked [IN] and the
negative (–) to terminals marked [GND].
8. Fire Alarm Interface options (Figs. 8-12, pg. 14):
A normally closed [NC] or normally open [NO] input trigger from a fire alarm control panel or a polarity
reversal input from an FACP signaling circuit will affect selected outputs.
To enable FACP Disconnect for an output turn the corresponding switch(es) [SW1-SW8] OFF on each
ACM8CB board. To disable FACP disconnect for an output turn the corresponding switch(es) [SW1-SW8]
ON on each ACM8CB board.
(a) Normally Open [NO] input:
For non-latching hook-up refer to Fig. 9, pg. 14. For latching hook-up refer to Fig. 10, pg. 14.
(b) Normally Closed [NC] input:
For non-latching hook-up refer to Fig. 11, pg. 14. For latching hook-up refer to Fig. 12, pg. 14.
(c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals marked
[+ INP –]. Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced in an alarm
condition). Jumper located next to TRG LED must be cut (Fig. 2a, pg. 7 and Fig. 8, pg. 14).
9. FACP Dry form “C” output (Fig. 2b, pg. 7):
FACP form “C” contacts can be use to trigger reporting or signaling devices.
These contact switch upon a fire alarm input trigger to the ACM8CB boards.
10. Stand-by Battery Connections (Figs. 3-7, pgs. 9-13):
For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in
the loss of output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the
terminals marked [+ BAT –] for 12VDC operation (Fig. 3a, pg. 9). Use two (2) 12VDC batteries wired in
series for 24VDC operation.
11. Battery and AC Supervision outputs (Figs. 3-4, pgs. 9-10):
It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL]
supervisory relay outputs marked [NC, C, NO] to appropriate visual notification devices.
Use 22 AWG to 18 AWG for AC Fail & Low/No Battery reporting.
12. Installation of tamper switch (Not Included) (Figs. 3b-4a, pgs. 9-10):
Mount UL Listed tamper switch (Altronix Model TS112 or equivalent) at the top of the enclosure. Slide the
tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Figs. 3b and 4a,
pgs. 9-10). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed
reporting device. To activate alarm signal open the door of the enclosure.
- 6 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect
hookup. Please follow the appropriate procedure below:
Normally Open Input: Placing a short between terminals marked [T] and [+ INP] will trigger the
Fire Alarm Disconnect. Remove the short to reset.
Normally Closed Input: Remove the wire from terminal marked [INP –] will trigger the Fire Alarm
Disconnect. Replace the wire to terminal marked [INP –] to reset.
FACP Signal Circuit Input: It is necessary to trigger the Fire Alarm System.
In all of the above scenarios the green TRG LED of the ACM8CBs will
illuminate. All outputs selected for Fire Alarm Disconnect will activate
releasing locking devices.
Note: All outputs [OUT 1 - OUT 8] must be in a normal (de-energized)
condition prior to testing. When the unit is configured for Normally Open
(Fig. 10, pg. 14) or Normally Closed (Fig. 12, pg. 14) latching operation it
is necessary to reset the Fire Alarm Disconnect by activating the
Normally Closed reset switch.
Output Voltage Test: Under normal load conditions the DC output voltage should be checked
for proper voltage level
(Power Supply Board Stand-by Battery Specifications, pg. 8).
Battery Test: Under normal load conditions check that the battery is fully charged, check
specified voltage at the battery terminals and at the board terminals marked
[+ BAT –] to ensure that there is no break in the battery connection wires.
Note: AL600ULXB and AL1012ULXB Power Supply Board maximum
charge current is 0.7A.
AL1024ULXB2 Power Supply Board maximum charge current is 3.6A.
Expected battery life is 5 years; however, it is recommended to change
batteries within 4 years or less if necessary.
Power Supply Board LED Diagnostics:
LED Power Supply Status
Red (DC) Green (AC)
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF No DC output. Loss of AC. Discharged battery.
Red (Bat) Battery Status
ON Normal operating condition.
OFF Battery fail/low battery.
Access Power Controller LED Diagnostics:
LED ON OFF
LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized.
Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide - 7 -
Power Supply Board Terminal Identification:
Terminal Legend Function/Description
L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.
+ DC –
Maximal3D - 12VDC @ 5A or 24VDC @ 5.4A to ACM8CB boards (power-limited)
Maximal5D - 12VDC @ 9A to ACM8CB boards (power-limited).
Maximal7D - 24VDC @ 9.4A to ACM8CB boards (power-limited).
AC FAIL
NC, C, NO
Indicates loss of AC power. To meet with UL requirements it is mandatory to connect
visual notification devices, connecting audible notification devices is optional.
Relay normally energized when AC power is present. Contact rating 1A/28VDC.
AC or brownout fail is reported within 1 minute of event.
BAT FAIL
NC, C, NO
Indicates low battery condition, e.g. connect to access control panel. Relay normally
energized when DC power is present. Contact rating 1A @ 28VDC. A removed battery
is reported within 5 minutes. Battery reconnection is reported within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC.
24VDC output threshold set @ approximately 21VDC.
+ BAT –
Stand-by battery connections. Connect one (1) 12VDC battery to the terminals marked
[+ BAT –] for 12VDC operation (Figs. 3 and 3a, pg. 9).
Use two (2) 12VDC batteries wired in series for 24VDC operation (Fig. 4, pg. 10).
Access Power Controller Terminal Identification:
Terminal Legend Function/Description
– Power + 12VDC or 24VDC input from power supply board.
– Control + Not applicable.
TRIGGER INPUT 1 -
INPUT 8 IN, GND
From normally open and/or open collector sink trigger inputs
(request to exit buttons, exit pir’s, etc.).
OUTPUT 1-
OUTPUT 8
NC, C, NO, COM
12VDC to 24VDC trigger controlled outputs:
Fail-Safe [NC positive (+) & COM Negative (–)],
Fail-Secure [NO positive (+) & COM Negative (–)],
Auxiliary output [C positive (+) & COM Negative (–)]
(When using AC power supplies polarity needs not to be observed),
FACP INTERFACE
T, + INPUT –
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
normally closed from an FACP signaling circuit output (Figs. 8-12, pg. 14).
FACP INTERFACE
NC, C, NO Form “C” relay contact rated @ 1A/28VDC for alarm reporting (not evaluated by UL).
Power Supply Board Stand-by Battery Specifications:
Altronix
Model: Power Supply Board Battery 20 Min. of
Backup
4 hr. of
Backup
24 hr. of
Backup
Maximal3D
AL600ULXB
(Refer to Fig. 1a, pg. 7 for Switch
[SW1] location and position)
12VDC/40AH* N/A 5.0A N/A
24VDC/40AH* N/A 5.4A 0.7A
Maximal5D AL1012ULXB
(Factory set at 12VDC) 12VDC/12AH 9.0A
Battery capacity
for emergency
stand-by:
at least 20 min.
N/A
Maximal7D AL1024ULXB2
(Factory set at 24VDC)
24VDC/12AH 7.7A 1.2A 200mA
24VDC/65AH* N/A 7.7A 1.2A
*Note: Additional battery enclosure required (Figs. 5-7, pgs. 11-13).
- 8 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide
Power Supply Board Output Voltage Settings:
+ DC ---
SW1
OFF - 24V
ON - 12V
ON
Fig. 1a - Maximal3D Power Supply Board
Fig. 1b
ON
OFF - 24V
ON - 12V
Access Power Controller Typical Application Diagram
(for each ACM8CB):
Fig. 2
Normally Open (N.O.)
Door Releasing
Device
Mag.
Lock
MAG. LOCK
Electric
Strike
Electromagnetic
Door Holders
UL Listed
Power Supply
For this application
corresponding
fuse F8 must be
removed.
Keypad
AC or DC
Power
Supply
(req'd.)
AC or DC
Power
Supply
(optional)
NC
NO
C
Access Control Panel
Output
Relay
FACP
(Fire Alarm
Control
Panel)
NC C NO COM
OUTPUT 1
LED1
F1
NC C NO COM
OUTPUT 2
IN GND
1
IN GND
2
IN GND
3
IN GND
4
IN GND
5
IN GND
6
IN GND
7
MAIN
IN GND
8
LED2 LED3 LED4 LED5 LED6 LED7 LED8
J2
FACP
NC C NO COM
OUTPUT 3
NC C NO COM
OUTPUT 4
NC C NO COM
OUTPUT 5
NC C NO COM
OUTPUT 6
NO C NC + INP --- T + RET -
NC C NO COM
OUTPUT 7
NC C NO COM
OUTPUT 8
--- +
Power
--- +
Control
F2 F3 F6 F7 F8
F4 F5
J1
J3
FACP INTERFACE
10A 250V
FACP Dry
Form "C" Output
NO C NC
FACP
1 2 3 4
ON
1 2 3 4
ON
Enabled
Disabled
FACP Interface
SW1-SW8
ON
1
ON
1
J2
--- +
Control
J1
Intact = One P/S Input
Cut = Dual P/S Input
NC C NO COM
OUTPUT 8
J3
Intact = DC Input
Cut = AC Input
TRG
FACP
Intact = Dry Input
Cut = Wet Input
LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8
Fig. 2b
Fig. 2a
Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide - 9 -
Fig. 3 - Maximal3D and Maximal5D
Power Supply
Board
NC C NO NC C NO
AC FAIL BAT FAIL
TRIGGER
AC DCAC1
EOLNOGND
SUPERVISED RESET +AUX-
- BAT +- DC +
L G N
OFF - 24V
ON - 12V
ON
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Optional
Rechargeable
Stand-by Battery
- BAT +
CAUTION: When power supply board is set for 12VDC
use only one (1) 12VDC stand-by battery.
Connect red battery lead to
the terminal marked [+ BAT]
and to the [positive (+)]
terminal of the battery.
Connect black battery lead to
terminal marked [BAT –]
and to the [negative (–)]
terminal of the battery.
Input 1150VAC, 60Hz
Line Neutral
Tamper Switch
Earth
Ground
Optional Rechargeable
Stand-by Battery
for UL294 Applications
Note: 12V batteries required
for ULC-S319 installations.
Optional Rechargeable
Stand-by Battery
for UL294 Applications
Note: 12V batteries required
for ULC-S319 installations.
CAUTION: When power supply board is set for
12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited.
Use minimum 0.25" spacing.
12AH Rechargeable batteries are the largest batteries that
can fit in this enclosure. A UL listed external battery enclosure
must be used if using the 40AH or 65AH batteries.
Fig. 3b
Fig. 3a
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
- 10 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide
Fig. 4 - Maximal7D
Power Supply
Board
NC C NO NC C NO
AC FAIL BAT FAIL
TRIGGER
AC DCAC1
EOLNOGND
SUPERVISED RESET +AUX-
- BAT +- DC +
L G N
OFF - 24V
ON - 12V
ON
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
24VDC operation:
Connect two (2) 12VDC batteries in series
Input 1150VAC, 60Hz
Line Neutral
Tamper Switch
Earth
Ground
Keep power-limited wiring separate from non power-limited.
Use minimum 0.25" spacing.
12AH Rechargeable batteries are the largest batteries that
can fit in this enclosure. A UL listed external battery enclosure
must be used if using the 40AH or 65AH batteries.
Fig. 4a
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide - 11 -
NEC Power-Limited Wiring Requirements for Maximal3D:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
One such example of this is shown below. Your specific application may require different conduit knockouts to
be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 5a).
Fig. 5
Supervisory Connections
(power-limited)
Input 115VAC, 60Hz
(non power-limited)
Optional Battery
Enclosure
(non power-limited)
Battery Connections
(non power-limited)
ACM8CB
outputs
(power-
limited)
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
Fig. 5a
- 12 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide
NEC Power-Limited Wiring Requirements for Maximal5D:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
One such example of this is shown below. Your specific application may require different conduit knockouts to
be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 6a).
Fig. 6
Supervisory Connections
(power-limited)
Input 115VAC, 60Hz
(non power-limited)
Optional Battery
Enclosure
(non power-limited)
Battery Connections
(non power-limited)
ACM8CB
outputs
(power-
limited)
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
Fig. 6a
Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide - 13 -
NEC Power-Limited Wiring Requirements for Maximal7D:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
One such example of this is shown below. Your specific application may require different conduit knockouts to
be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 7a).
Fig. 7
Supervisory
Connections
(power-limited)
Input 115VAC, 60Hz
(non power-limited)
Optional Battery
Enclosure
(non power-limited)
Battery Connections
(non power-limited)
ACM8CB
outputs
(power-
limited)
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
Fig. 6a
- 14 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide
Fig. 9 Normally Open: Non-Latching FACP
trigger input:
Fig. 8 Polarity reversal input from FACP signaling
circuit output (polarity is referenced in
alarm condition):
FACP Hook-Up Diagrams:
CUT
JUMPER
FROM FACP
OUTPUT
CIRCUIT
+
--
FACP
OUTPUT EOL
TRG
FACP
NO C NC
FACP INTERFACE
JUMPER
N.C. DR
Y
TRIGGER
INPUT
TRG
NO C NC
FACP INTERFACE
FACP
N.C. TRIGGER
INPUT
N.C. RESET
SWITCH
JUMPER
TRG
FACP
N.O. TRIGGER
INPUT
TRG
FACP
NO C NC
FACP INTERFACE
N.C. RESET
SWITCH
N.O.
TRIGGER
INPUT
JUMPER
TRG
NO C NC
FACP
Fig. 11 Normally Open FACP Latching trigger
input with reset
(This output has not been evaluated by UL):
Fig. 10 Normally Closed: Non-Latching FACP
trigger input:
Fig. 12 Normally Closed: Latching FACP trigger
input with reset
(This output has not been evaluated by UL):
Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide - 15 -
Notes:
- 16 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide
Enclosure Dimensions (H x W x D approximate):
26” x 19” x 6.25” (660.4mm x 482.6mm x 158.8mm)
4”
(101.6mm)
19”
(482.6mm)
2”
(50.8mm)
2”
(50.8mm)
4”
(101.6mm)
4”
(101.6mm)
7”
(177.8mm)
6.25”
(158.8mm)
0.85”
(21.6mm)
0.85”
(21.6mm)
0.85”
(21.6mm)
0.85”
(21.6mm)
8.9”
(226.1mm)
19”
(482.6mm)
8.4”
(213.4mm)
8.9”
(226.1mm)
8.4”
(213.4mm)
19” (482.6mm)
4” (101.6mm)
1”
(25.4mm)
7.5”
(190.5mm)
5”
(127mm)
26”
(660.4mm)
1.5”
(38.1mm)
1.0”
(25.4mm)
6.25”
(158.8mm)
8.5”
(215.9mm)
7.5”
(190.5mm)
10”
(254mm)
26”
(660.4mm)
1.25”
(31.8mm)
7”
(177.8mm)
7”
(177.8mm)
8.5”
(215.9mm)
26”
(660.4mm)
1.25”
(31.75mm)
2”
(50.8mm)
2”
(50.8mm)
Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty
IIMaximal3D/5D/7D Series H16U MEMBER
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Altronix MAXIMAL3D Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI