Danfoss Termix VMTD-F MIX-I Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss Termix VMTD-F MIX-I Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
InstallationGuide
TermixVMTD-FMIX-I
1.0TableofContents
1.0TableofContents.............................................1
2.0VMTD-FMIX-IFunctionaldescription................2
3.0Safetynotes.....................................................3
SafetyNotesgeneral...........................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
4.2Start-up..............................................................6
4.3Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
6.0Controls..........................................................10
6.1Heatingcircuit......................................................10
6.2DHWtemperaturecontrol........................................12
6.3Other.................................................................12
6.4Extras................................................................14
6.5Maintenance........................................................14
7.0Troubleshooting..............................................15
7.1Troubleshootingingeneral......................................15
7.2TroubleshootingDHW............................................15
7.3TroubleshootingHE...............................................16
7.4Disposal.............................................................17
Declaration.........................................................19
DanfossHeating
VI.GP .W2.02/LUK40250
DEN-GT
1
InstallationGuideTermixVMTD-FMIX-I
2.0VMTD-FMIX-IFunctionaldescription
Districtheatingsubstationfordirectheatingand
instantaneousdomestichotwaterwiththermostaticcontrol.
Designedforwall-mounting.
Application
TheTermixVMTD-FMIX-Iisacompletesolutionwithbuilt-in
waterheaterandheatingsystemwithdifferentialpressurecontrol
andmixingloop.TheTermixVMTD-FMIX-Iisapplicableforfor
single-familyhousesandfordecentralizedsystemsinmulti-family
houses.
Districtheating(DH)
Thesubstationisprefabricatedwithadifferentialpressure
controller,ttingpieceandsensorpocketforinsertionofa
heatmeteraswellasstrainerandballvalves.Furthermorethe
substationisdeliveredwithamixingloopincludingpump,controls
andnon-returnvalve.
Heating(HE)
Theheatingcircuitisdesignedfordirectconnection.The
differentialpressurecontrollersetstheoptimumoperation
conditionsforradiatorthermostatsinordertoenableindividual
temperaturecontrolineachroom.Themixingloopcreatesa
suitabletemperaturelevele.g.foroorheating.Inordertoenable
atimedependenttemperaturecontrolprogram,azonevalvewith
actuatorandaroomthermostatcanbeincludedasanoption.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerand
theheatexchangerandthetemperatureisregulatedwithaow
compensatedtemperaturecontrollerwithintegrateddifferential
pressurecontroller.TheheatexchangercoolsouttheDHwater
veryefciently,therebycreatinganexcellentoperatingeconomy.
TheDanfossIHPTvalveensuresastablehotwatertemperature
byvaryingloads,supplytemperaturesandbyhighandvarying
differentialpressurewithouttheneedforreadjustingthevalve.
Thisprotectstheheatexchangeragainstoverheatingandlime
scaleformation.FurthermoretheIHPTvalvehasanintegrated
idletemperaturecontroller,whichkeepsthehousesupplyline
warm.Thisshortensthewaitingperiodsduringsummerwhen
theheatingsystemisinreducedoperation,whichisidealwhere
highcomfortisrequested.
2
DEN-GT
VI.GP .W2.02/LUK40250
DanfossHeating
InstallationGuideTermixVMTD-FMIX-I
3.0Safetynotes
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
DanfossHeating
VI.GP .W2.02/LUK40250
DEN-GT
3
InstallationGuideTermixVMTD-FMIX-I
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Optionalhotwatercirculation(HWC)
2.Districtheating(DH)supply
3.Districtheating(DH)return
4.Coldwatermains(CWM)
5.Domesticcoldwater(DCW)
6.Domestichotwater(DHW)
7.Heating(HE)supply
8.Heating(HE)return
Connectionsizes:
DH+HE:
G¾”(int.thread)
CWM+DCW+DHW:
G¾”(int.thread)
Dimensions(mm):
Withoutcover:
H770xW535xD150
Withcover:
H800xW540xD242
Weight(approx.):25kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
4
DEN-GT
VI.GP .W2.02/LUK40250
DanfossHeating
InstallationGuideTermixVMTD-FMIX-I
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Thightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
DanfossHeating
VI.GP .W2.02/LUK40250
DEN-GT
5
InstallationGuideTermixVMTD-FMIX-I
4.2Start-up
Start-up,Heatingwithmixingloop
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Ifthesystemoperatesinaccordancewithdesign,itcanbeput
toregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderoorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemll.
Underoorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderoorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderoorheatingcontroller.Thepumpmustbestoppedif
allunderoorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
6
DEN-GT
VI.GP .W2.02/LUK40250
DanfossHeating
InstallationGuideTermixVMTD-FMIX-I
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossHeating
VI.GP .W2.02/LUK40250
DEN-GT
7
InstallationGuideTermixVMTD-FMIX-I
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
10
Circulatorpump,HE
N
Circulationconnection
31
Differentialpressurecontroller
2
Singlecheckvalve
41A
Fittingpiece,coldwatermains
7
Thermostaticcontroller,HE
41BFittingpiece,energymeter
9
Strainer
74
IHPTcontroller,DHW
8
DEN-GT
VI.GP .W2.02/LUK40250
DanfossHeating
InstallationGuideTermixVMTD-FMIX-I
5.2Schematicdiagram
DHW
DCW
CWM
DH
Supply
HE
Supply
DH
Return
HE
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
B
Heatexchanger,DHW
10
Circulatorpump
41A
Fittingpiece,coldwatermains
2
Singlecheckvalve
14
Sensorpocket,energymeter
41BFittingpiece,energymeter
7
Thermostaticvalve
18
Thermometer
74
IHPTcontroller
9
Strainer
31
Differentialpressurecontroller
DHW:DomesticHotWater
DCW:
DomesticColdWater
CWM:
ColdWaterMains
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
HESupply:HeatingSupply
HEReturn:HeatingReturn
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:PN10(PN16versionsareavailableonenquiry)
Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0,5bar
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
DanfossHeating
VI.GP .W2.02/LUK40250
DEN-GT
9
InstallationGuideTermixVMTD-FMIX-I
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsouttheuctuationsin
pressurearrivingfromthedistrictheatingnetwork.Theoperating
pressureinthesubstationisthusheldsteady.
6.1.2RAVKcontroller
HEtemperaturecontrol
TheHEowtemperatureintheheatingcircuitiscontrolledbythe
HEtemperaturecontroller.
Thermostaticcontrol
ThetemperatureoftheHEowlineisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
RAVKcontroller(25-65°C).Thetemperaturesettingisasfollows:
1=25°C
2=35°C
3=45°C
4=55°C
5=65°C
Thevaluesareintendedasaguide.
10
DEN-GT
VI.GP .W2.02/LUK40250
DanfossHeating
InstallationGuideTermixVMTD-FMIX-I
6.1.3Circulationpump
ALPHA2pumpshavebothvariablespeedpressurecontrolled
operation,andstandardselectablethreespeedoperation.
TheuniqueAUTOADAPTfeatureallowsthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
ALPHA2Lpumpshavebothvariablespeedpressurecontrolled
operation,andstandardselectablethreespeedoperation.The
variablespeedmodulatingmodesallowthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
UPSpumpsareacompleterangeofcirculatorpumpswith3
speeds.
EnergylabellinguptoclassB
6.1.4TP7000
TP7000electronic7dayprogrammableroomthermostat.
Signalsfromtheroomthermostatcanbeusedtocontrolzone
valves.
DanfossHeating
VI.GP .W2.02/LUK40250
DEN-GT
11
InstallationGuideTermixVMTD-FMIX-I
6.2DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
6.2.1IHPT180controller(45–65°)
IHPTisaself-actingow-compensatedtemperaturecontrollerwith
integrateddifferentialpressurecontroller.
TheIHPToperatesatitsbestatDHsupplytemperaturesofupto
100°C.
Byturningthehandlefortemperaturesettingin(+)direction
thesettingisincreased,byturningitin(-)directionthesettingis
decreased.
Turns*DHWTemperatureSetting[°C]
064
1
61
258
3
55
4
52
5
48
6
44
7
43
*Startposition:Handleturnedfullyin(+)direction.
Thevaluesareintendedasaguide.
6.3Other
6.3.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom
excessivepressure.
Theblow-offpipefromthesafetyvalvemustnotbeclosed.The
blow-offpipeoutletshouldbeplacedsothatitdischargesfreely
anditispossibletoobserveanydrippingfromthesafetyvalve.
Itisrecommendedtochecktheoperationofsafetyvalvesat
intervalsof6months.Thisisdonebyturningthevalveheadin
directionindicated.
12
DEN-GT
VI.GP .W2.02/LUK40250
DanfossHeating
InstallationGuideTermixVMTD-FMIX-I
6.3.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditionsand
themanufacturer’sinstructions.
6.3.3GTUPressureEqualizer
TheGTUPressureEqualizerabsorbstheexpansiononthe
secondarysideoftheTermixwaterheatersandcanbeusedasa
substitutetothesafetyvalve.
Furthermorethepressureequalizerabsorbsapossibleincreasein
pressure,soadischargeoutletisomitted.
TheGTUPressureEqualizermaynotbeappliedinsystemswithhot
watercirculation.
6.3.4Fittingpiece
Thesubstationisequippedwithattingpieceforenergymeter.
Assemblyofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater
onthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththeenergymeter.Do
notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand
tightenallthreadedconnections.
Sensorpocket,energymeter
Thesensorsoftheenergymeterismountedinthesensorpockets.
DanfossHeating
VI.GP .W2.02/LUK40250
DEN-GT
13
InstallationGuideTermixVMTD-FMIX-I
6.4Extras
6.4.1Circulationpipe
Thecirculationpipesetismounteddirectlyonthecontroller.
Thesetincludescirculationpipe,singlecheckvalveandtting.
Whenmountingthehotwatercirculationdirectlyonthecontroller
thehotwatercirculationtemperaturewillbeequaltotheidle
temperature.Theidletemperatureisafewdegreeslowerthanthe
setdomestichotwatertemperature.
6.5Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
14
DEN-GT
VI.GP .W2.02/LUK40250
DanfossHeating
InstallationGuideTermixVMTD-FMIX-I
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace.
Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout.
Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
Idletemperaturetoolow(forstations
equippedwithIHPT).
Setpointtoolow.
Turnthermostatin(+)direction.
DanfossHeating
VI.GP .W2.02/LUK40250
DEN-GT
15
InstallationGuideTermixVMTD-FMIX-I
7.3TroubleshootingHE
ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
(radiatorcircuit).
Cleangate/strainer(s).
ThelterintheenergymeteronDHcircuit
clogged.
Cleanthelter(afterconsultingtheDH
plantoperator).
Defectiveorwronglyadjusteddifferential
pressurecontroller.
Checktheoperationofthedifferential
pressurecontrollercleanthevalveseatif
required.
Sensordefectiveorpossiblydirtinthe
valvehousing.
Checktheoperationofthethermostat
cleanthevalveseatifrequired.
Automaticcontrols,ifany,wronglysetor
defective-possiblypowerfailure.
Checkifthesettingofthecontroller
iscorrectseeseparateinstructions.
Checkthepowersupply.Temporary
settingofmotortomanual”controlsee
instructionsonautomaticcontrols.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
thatitturns.Checkifthereisairtrappedin
thepumphousingseepumpmanual.
Thepumpissetattoolowspeedof
rotation.
Setthepumpathigherspeedofrotation.
Pressuredropthepressuredropon
theradiatorcircuitshowslowerthan
recommendedoperatingpressure.
Fillwateronthesystemandcheckthe
functioningofthepressureexpansion
vesselifrequired.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperature
adjustedtoolow.
Adjustaccordingtoinstructions.
Defectiveradiatorvalves.
Checkreplace.
Unevenheatdistributioninbuilding
becauseofincorrectlysetbalancingvalves,
orbecausetherearenobalancingvalves.
Adjust/installbalancingvalves.
Diameterofpipetosubstationtoosmallor
branchpipetoolong.
Checkpipedimensions.
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
DHsupplytemperaturetoohigh.
Wrongsettingofthermostatorof
automaticcontrols,ifany.
Adjustautomaticcontrols,see
instructionsforautomaticcontrols.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callautomaticcontrolsmanufactureror
replacetheregulator.
Defectivesensoronself-actingthermostat.
Replacethermostatorsensoronly.
DHsupplytemperaturetoolow.
Wrongsettingofautomaticcontrols,ifany.
Adjustautomaticcontrolsseeinstructions
forautomaticcontrols.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callinautomaticcontrolsmanufactureror
replacecontroller.
Defectivesensoronself-actingthermostat.
Replacethermostatorsensoronly.
Wrongplacement/ttingofoutdoor
temperaturesensor.
Adjustlocationofoutdoortemperature
sensor.
Strainerclogged.Cleangate/strainer.
16
DEN-GT
VI.GP .W2.02/LUK40250
DanfossHeating
InstallationGuideTermixVMTD-FMIX-I
ToohighDHreturntemperature.
Toosmallheatingsurface/toosmall
radiatorscomparedtothetotalheating
requirementofthebuilding.
Increasetotalheatingsurface.
Poorutilizationofexistingheatingsurface.
Defectivesensoronself-actingthermostat.
Makesuretheheatisdistributedevenly
acrossthefullheatingsurfaceopenall
radiatorsandkeeptheradiatorsinthe
systemfromheatingupatthebottom.It
isextremelyimportanttokeepthesupply
temperaturetotheradiatorsaslowas
possible,whilemaintainingareasonable
levelofcomfort.
Thesystemissinglepipeloop.
Thesystemshouldfeatureelectronic
controlsaswellasreturnsensors.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Ventthesystem.
Defectiveorincorrectlysetradiator
valve(s).Singlepipeloopsystemsrequire
specialone-piperadiatorvalves.
Checkset/replace.
Dirtinthemotorizedvalveorinthe
differentialpressurecontroller.
Checkcleanout.
Defectivemotorizedvalve,sensoror
automaticcontroller.
Checkreplace.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Noiseinsystem.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Heatloadtoohigh.
Defectivemotorizedvalve,sensoror
electroniccontroller.
Checkreplace.
7.4Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
DanfossHeating
VI.GP .W2.02/LUK40250
DEN-GT
17
InstallationGuideTermixVMTD-FMIX-I
18
DEN-GT
VI.GP .W2.02/LUK40250
DanfossHeating
Declaration
Declarationofconformity
Declarationsignature
Declarationofcompliance
We:
GeminaTermixA/S
MemberoftheDanfossGroup
Navervej15-17
DK-7451Sunds
doherebyonourownresponsibilitydeclarethatthefollowingproducts:
TermixSubstations
coveredbythisdeclarationisinconformitywiththefollowingdirective(s),
standard(s)orothernormativedocument(s),
providedthattheproductsareusedinaccordancewithourinstructions.
EUDirectives:
MachineryDirective2006/42/EEC
ENISO14121-1Safetyofmachinery-Riskassessment
EN60204-1-Safetyofmachinery-Electricalequipmentofmachines
EMCDirective2004/108/EEC
EN61000-6-22007Electromagneticcompatibility
-Genericstandard:Immunityindustry
EN61000-6-32007Electromagneticcompatibility
-Genericstandard:Emissionforresidential,commercialandlightindustry
PEDDirective97/23/EEC
AllsubstationsthatfallsunderArticle3.3andcategory1shallnotbeCE-marked
accordingtothisdirective,howeverallessentialsafetyrequirementsfromthe
PEDDirective97/23/EECarefollowedtoensurehydraulicsafety
Thisdeclarationisimmediatelyannulled,iftheproductisinterferedwithinanyway,
whichinterfereswiththeabovementioneddirectivesandstandards,
withoutthewrittenconsentfromGeminaTermixA/S.
2010.01.05Sunds
Timeandplace
LarsGinnerup
Responsibleforquality
InstallationGuideTermixVMTD-FMIX-I
ProducedbyDanfossA/S©12/2011
/