  • Hello! I am an AI chatbot trained to assist you with the Munters Icedry 1400 Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Originalinstructions
Usermanual
IceDry800/1400
Desiccantdehumidier
190TGB-1037-G1307©MuntersEuropeAB2013
Importantuserinformation
Intendeduse
Muntersdehumidiersareintendedtobeusedforthe
dehumidicationofair.Anyotheruseoftheunit,or
usewhichiscontrarytotheinstructionsgiveninthis
manual,cancausepersonalinjuryanddamagetotheunit
andotherproperty.
Nomodicationoftheunitisallowedwithoutprior
approvalbyMunters.Attachmentorinstallation
ofadditionaldevicesisonlyallowedafterwritten
agreementbyMunters.
Warranty
Thewarrantyperiodisvalidfromthedatetheunit
leftourfactory,unlessotherwisestatedinwriting.
Thewarrantyislimitedtoafreeexchangeofpartsor
componentswhichhavefailedasaresultofdefectsin
materialsorworkmanship.
Allwarrantyclaimsmustincludeproofthatthe
faulthasoccurredwithinthewarrantyperiodand
thattheunithasbeenusedinaccordancewiththe
specications.Allclaimsmustspecifytheunittypeand
fabricationnumber.Thisinformationisstampedonthe
identicationplate,seesectionMarking.
Itisaconditionofthewarrantythattheunitforthefull
warrantyperiodisservicedandmaintainedbyaqualied
MuntersengineerorMuntersapprovedengineer.
Accesstospecicandcalibratedtestequipmentis
necessary.Theserviceandmaintenancemustbe
documentedforthewarrantytobevalid.
AlwayscontactMuntersforserviceorrepair.Operating
faultscanoccuriftheunitismaintainedinsufcientlyor
incorrectly.
Safety
Informationaboutdangersareinthismanualindicated
bythecommonhazardsymbol:
W W
W
ARNING! ARNING!
ARNING!
Indicatesapossibledangerthatcanleadtopersonalinjury.
CA CA
CA
UTION! UTION!
UTION!
Indicatesapossibledangerthatcanleadtodamagetothe
unitorotherproperty,orcauseenvironmentaldamage.
NOTE!Highlightssupplementaryinformationforoptimal
useoftheunit.
ConformitywithDirectives
Thedehumidierisinconformitywiththeessential
safetyrequirementsoftheMachineryDirective
2006/42/EC,theLowVoltageDirective2006/95/EC
andtheEMCDirective2004/108/EC.The
dehumidierismanufacturedbyanISO9001:2008
accreditedmanufacturingorganisation.
Copyright
Thecontentsofthismanualcanbechangedwithout
priornotice.
NOTE!Thismanualcontainsinformationwhichis
protectedbycopyrightlaws.Itisnotallowedtoreproduceor
transmitanypartofthismanualwithoutwrittenconsentfrom
Munters.
Pleasesendanycommentsregardingthismanualto:
MuntersEuropeAB
TechnicalDocumentation
P.O.Box1150
SE-16426KISTASweden
e-mail:t-doc@munters.se
iiImportantuserinformation190TGB-1037-G1307
Tableofcontents
Importantuserinformation...............ii
Intendeduse...........................
ii
Warranty...............................
ii
Safety..................................
ii
ConformitywithDirectives............
ii
Copyright..............................
ii
Tableofcontents...........................iv
1Introduction.................................1
1.1General................................
1
1.2Aboutthismanual.....................
1
1.3Safetyandcautions...................
1
1.4Marking................................
3
1.5Supervisionofoperation..............
3
1.6Faultindications.......................
3
2Productdesign..............................4
2.1Productdescription...................
4
2.2Principleofoperation..................
4
3Transport,inspectionandstorage.......5
3.1Movingtheequipment................
5
3.2Packaginganddeliveryinspection...
5
3.3Storingtheequipment................
5
4Installation...................................6
4.1General................................
6
4.2Safety..................................
6
4.3Siterequirements.....................
6
4.4Mirrorhandedductconnections......
7
4.5Wheretoinstallthedehumidier.....
8
4.6Ducting.................................
8
4.6.1Generalrecommendations...
8
4.6.2Processairinlet................
9
4.6.3Dryairoutletduct..............
9
4.6.4Reactivationairintake........
9
4.6.5Ductworkforwetairoutlet.....
10
4.7Installationexamplescoldstorage
room(freezer).........................
11
4.8Electricalconnections................
13
4.9Pre-startsettings......................
14
4.10Pre-startchecks.......................
14
4.11Airowcheckandadjustment........
15
5Operation....................................16
5.1General................................
16
5.2Safety..................................
16
5.3Quickstop..............................
16
5.4Operatorpanel........................
17
5.5Operatingtheunit.....................
19
5.5.1General.........................
19
5.5.2Start.............................
19
5.5.3Restartafterpowerfailure.....
19
5.5.4Stop.............................
20
6Serviceandmaintenance.................21
6.1Safety..................................
21
6.2General................................
21
6.3Serviceoptions........................
21
6.4Extendedwarranty....................
21
6.5Serviceandmaintenanceschedule..
22
7Faulttracing.................................24
7.1General................................
24
7.2Safety..................................
24
7.3Faulttracinglist........................
24
8Technicalspecication....................26
8.1Dimensionsandservicespace.......
26
8.2Technicaldata.........................
27
8.3Sounddata.............................
28
9Scrapping....................................29
10ContactMunters............................31
ivTableofcontents190TGB-1037-G1307
IceDry800/1400
1Introduction
1.1General
Muntersmanufacturesawiderangeofefcientdehumidiersdesignedfordifferentusesandapplications.
PleasecontactyournearestMuntersofceifyouhaveanyquestionsregardingtheinstallationofyour
dehumidier,orvisitthewebsiteatwww .munters.com.
Theunitisinspectedandcheckedpriortoleavingthefactorytoguaranteeconsistentqualityandmaximum
reliability.Forproductdata,seesectionTechnicalspecication.
1.2Aboutthismanual
Thismanualiswrittenfortheuserofthedehumidier.Itcontainsnecessaryinformationforhowtoinstall
andusethedehumidierinasafeandefcientway.Readthroughthemanualbeforetheunitisinstalledand
used.
1.3Safetyandcautions
Everymeasurehasbeentakeninthedesignandmanufactureofthedehumidiertoensurethatitmeetsthe
safetyrequirementsofthedirectivesandstandardslistedintheECDeclarationofConformity.
Theinformationinthismanualincludessuggestionsforbestworkingpracticeandshallinnowaytake
precedenceoverindividualresponsibilitiesorlocalregulations.
Duringoperationandotherworkwithamachineitisalwaystheresponsibilityoftheindividualtoconsider:
Thesafetyofallpersonsconcerned.
Thesafetyoftheunitandotherproperty.
Theprotectionoftheenvironment.
Forinformationaboutthesafetysymbolsusedinthismanual,seesectionImportantuserinformation.
190TGB-1037-G1307Introduction1
IceDry800/1400
W W
W
ARNING! ARNING!
ARNING!
-Theunitisnotintendedforuseinhazardous(classied)areaswhereexplosionsafetycompliantequipment
isrequired.
-Theunitmustnotbesplashedwithorimmersedinwater.
-Donotconnecttheunittoothermainsvoltagethanspeciedontheunit’sidenticationplate,seesectionMarking.
-Themainspowersupplyispermanentlyconnectedtothemainpowerswitchoftheunit.
-Donotoperatetheunitnearanyheat-generatingdevicesorammableanddangerousmaterials.
-Donotinsertngersoranyotherobjectsintotheairvents.
-Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
-Thedehumidiercanrestartautomaticallyafterapowercut.Alwayssetandlockthemainpowerswitchinthe
OFFpositionbeforecarryingoutanyservicework.
-Useonlyapprovedliftingequipmenttopreventaccidents.
-AlwayscontactMuntersforserviceorrepair.
2Introduction190TGB-1037-G1307
IceDry800/1400
1.4Marking
Figure1.1Locationoflabels
0919 190XXX XXXXX
0,72 kW
Max
5,4 kW
M unters E urope AB
Isafjordsgatan 1
164 26 Kista, Sw eden
M
4,38 kW
M ade in Sw eden
Fabr. N o.
Fabr. year 2009
3 ~ 400V 50 H z
Type
IP 44
IceDry800
Explanationof"Fabr.No"ontheidenticationplate:
09=yearofmanufacture,19=weekofmanufacture,190XXX=articlenumber,XXXXX=serialnumber
1.Identicationplate2.Dryairoutlet
3.Wetairoutlet4.Processairinlet
5.Reactivationairinlet
1.5Supervisionofoperation
Thedehumidieriscontrolledandmonitoredfromtheoperatorpanellocatedonthefrontoftheunit.
1.6Faultindications
Faultsareclearlyindicatedontheoperatorpanel.TheashingLEDsindicatewhichcomponentthat
requiresattentionformaintenanceorreplacement.
190TGB-1037-G1307Introduction3
IceDry800/1400
2Productdesign
2.1Productdescription
ThedesiccantdehumidiersintheIceDryserieshavebeendevelopedtoeffectivelydehumidifytheairin
coldstoresinordertominimisefrostandicebuild-up
Thedehumidierisequippedwithanencapsulatedrotorunit.Therotorcasingisconstructedofdurable
thermosetplasticandcontainsisolatedsectionsthatprovideaprecisebalanceforthedehumidication,
reactivationandheatrecoveryairows.
TheelectricalcontrolsystemcomplieswiththeEN60204(IEC60204)standards.Foroperating
temperature,seesection8.2,Technicaldata.
ThedehumidierismanufacturedinaccordancewithuniformEuropeanstandardsandestablished
requirementsforCE-marking.
2.2Principleofoperation
2
1
4
3
Figure2.1Principleofoperation
1.Processair
2.Dryair
3.Reactivationair
4.Wetair
Thedesiccantrotorismadeofacompositematerialthatishighlyeffectiveinattractingandretainingwater
vapour.Therotorisdividedintwozones.Theairowtobedehumidied,processair,passesthrough
therotor'slargestzoneandthenleavestherotorasdryair.Sincetherotorrotatesslowly,theincomingair
alwaysmeetsadryzoneontherotor,thuscreatingacontinuousdehumidicationprocess.
Theairowthatisusedtodrytherotor,reactivationair,isheated.Thereactivationairpassesthrough
therotorintheoppositedirectiontotheprocessairandleavestherotoraswetair(warm,moistair).This
principleenablesthedehumidiertoworkeffectively,evenatfreezingtemperatures.
4Productdesign190TGB-1037-G1307
IceDry800/1400
3Transport,inspectionandstorage
3.1Movingtheequipment
Thedehumidierisdeliveredonapalletandmustbehandledcarefully.Allpaneldoorsontheunitmustbe
closedduringtransport.Providedthatthedehumidierisstillsecuredtoitsdeliverypallet,itcanbemoved
usingafork-lifttruck.
Weightofthedehumidiercanbefoundinsection8,Technicalspecication.
3.2Packaginganddeliveryinspection
1.Checkthedeliveryagainstthedeliverynote,orderconrmationorotherdeliverydocumentationand
checkthateverythingisincludedandnothingisdamaged.
2.ContactMuntersimmediatelyifthedeliveryisnotcompleteinordertoavoidinstallationdelays.
3.Iftheunitistobeputintostoragepriortoinstallation,seesectionStoringtheequipment.
NOTE!Ifinstallationisnottobecarriedoutimmediatelyafterarrivaloftheequipment,itisadvisabletoleave
thepackagingmaterialinplaceonthedehumidier,ortore-usethepackagingmaterialtoprovidetemporary
protectionfortheunitduringlatertransportationtothesiteandduringinstallation.
4.Removeallpackagingmaterialfromtheunit,checkcarefullytomakesurethatnodamagehasoccurred
duringtransportation.
5.AnyvisibledamagemustbereportedinwritingtoMunterswithin5daysandpriortoinstallationof
theunit.
6.Disposeofthepackagingmaterialaccordingtolocalregulations.
NOTE!G3ltercartridgesforprocessandreactivationairareincludedinthedelivery.Onecartridgeismounted
onthedehumidierprocessairinletandoneontheoutsideofthecold-storageroom,inthereactivationairinlet.
3.3Storingtheequipment
Thefollowingisimportantifthedehumidieristobestoredpriortoinstallation:
Placethedehumidierinanuprightpositiononahorizontalsurface.
Protectthedehumidierfromphysicaldamage.
Storethedehumidierundercoverandprotectitfromdust,frost,rainandaggressivecontaminants.
190TGB-1037-G1307Transport,inspectionandstorage5
IceDry800/1400
4Installation
4.1General
IceDrydehumidiersareintendedforinstallationincoldstoreswithambientairdowntominus25°C.
Theseconditionsrequirethatinstallationinstructionsarefollowedcarefullyasfaultyinstallationcanresult
inseriousoperationaldisturbances.
Iftheunitistobeputintostoragepriortoinstallation,seesection3.3,Storingtheequipment.
4.2Safety
W W
W
ARNING! ARNING!
ARNING!
Themainspowersupplyispermanentlyconnectedtothemainpowerswitchoftheunit.Adjustments,
maintenanceandrepairsmustonlybecarriedoutbyauthorisedpersonnel.
W W
W
ARNING! ARNING!
ARNING!
Thewetairoutletishot.Toavoidburnsfromunintendedcontact,makesureitisinsulated.
CA CA
CA
UTION! UTION!
UTION!
Thebuilt-inheaterrequiresacontinuouspowersupplytopreventfunctionaldisorder.Onlyswitchofftheunit's
powerincaseofemergency.
CA CA
CA
UTION! UTION!
UTION!
Condensationiseasilyformedontheinsideoftheductduetothehighhumidityofthereactivationair.Toavoid
condensation,theductworkmustbeinsulated
CA CA
CA
UTION! UTION!
UTION!
Activatethemainswitchforthedehumidierassoonastheunithasbeeninstalled.Thisallowsthebuilt-inheater
tooperateandpreventsinternaliceformation.
CA CA
CA
UTION! UTION!
UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
CA CA
CA
UTION! UTION!
UTION!
Iftheprocessairowdamperisfullyopen,thehighcoldairdensityinthecold-storageroomcoulddamagethe
processairfan.
CA CA
CA
UTION! UTION!
UTION!
Failuretocorrectlyadjusttheprocessandreactivationairowscouldcausetheunittomalfunction.
4.3Siterequirements
Thedehumidierisadaptedtooperationinsidecoldstores.Thepermittedoperationaltemperatures
arefromminus25to0°C.Itisimportantthattheintendedinstallationsitemeetsthelocationandspace
6Installation190TGB-1037-G1307
IceDry800/1400
requirementsfortheequipmentinordertoachievethebestpossibleperformanceandfacilitateservicing.
Therefore,complywiththerecommendedservicespaces,seesection8.1,Dimensionsandservicespace.
NOTE!Theunitmustberemovedfromthecoldstoreatcertainserviceintervals.Haveextracablesforunit
connectionavailable.
4.4Mirrorhandedductconnections
Thefrontandbackpanelsareinterchangeable,sothattheconnectionsforprocessanddryairmaybe
situatedeitherontheleftorrightsideoftheunit.
Thedehumidiersaredeliveredwiththeprocessanddryairconnectionsontheleftsideoftheunit.Ifitis
requiredtothechangetheorientation,sothattheconnectionsareontherightsideoftheunit,proceed
asfollows.
W W
W
ARNING! ARNING!
ARNING!
Ensurethatmainpowerisisolatedfromthedehumidierpriortochangingtheorientatinoftheprocessanddryair
connections.
B
A
C
D
E
F
1.Removethetwobolts(B)securingthefrontpanelandcarefullyremovethepanel.
2.Removethetwoboltssecuringtherearpanelandcarefullyremovethepanel.
3.Removethetwobolts(A)andwasherssecuringthecontrolandtoppanels,thencarefullyremovethe
toppanel.
4.Removethecableductcovers(C),re-routethecablesandtthecontrolpanel(D)ontotheoppositeside
oftheunit.Retthecableductcovers.
5.Loosentherotorstop(E)andthetwoltermonitors(F).Removethecableties.
6.Fittherotorstopandltermonitorsontheoppositesideoftheunit.Tiethecables.
7.Fitthefront,rearandtoppanelsintheirnewpositions.
190TGB-1037-G1307Installation7
IceDry800/1400
4.5Wheretoinstallthedehumidier
Selectaplacewherethedehumidiercausestheleastdisturbancetothecold-storageroomactivities,while
allowingformaintenanceworksuchasprocesslterreplacement.
Whentheunitisinstalledonabaseframe,thebaseframemustbedesignedinsuchawaythatitcaneasilybe
removedfromthecoldstore/freezer.Makesureopeningsforforkliftareincluded.
Thedehumidiermustbeplacedsothatthereisnoriskoftheprocessintakeandltericingup.Icenormally
formsnearthedoorsandair-locksofthecoldstorewherewarm,humidairowsin.
Installthedehumidierinsuchawaythatthereactivationairandwetairductsareasshortaspossible,max
1.5m.Seesection4.7,Installationexamplescoldstorageroom(freezer).
4.6Ducting
4.6.1Generalrecommendations
NOTE!Vibrationreduction.Ifthereisaneedtoforreductionofvibrationsfromthedehumidier,contactMunters
forinstructions.RefertostandardEN1299+A1:2008.
Duetothecoldsurroundingsandriskoffreezing,itisvitalthatallductingareinstalledaccordingto
instructions.Seealso4.7,Installationexamplescoldstorageroom(freezer).
Tofacilitateeasytransferofthedehumidieroutofthecold-storageroomforservice,allductconnections
shouldbeeasilydisassembled.Shouldthedehumidier,despitethisrecommendation,beinstalledinsucha
waythatitcannotbeeasilyremovedforservice,itisimportantthattheminimumservicespacerequirements
aremet,see8.1,Dimensionsandservicespace.Avapour-tightconnectionbetweenthewallandtheductisvital.
Preferably,polyurethanefoamshouldbeusedifthetemperatureissufcientlyhighduringapplication.
Wheninstallingductworkbetweenthedehumidierandtheinletandoutletconnections,thefollowing
recommendationsshouldbeobserved:
Thelengthofductworkshouldbekeptasshortaspossibletominimisestaticairpressurelosses.
Tomaintainperformance,allrigidprocessorreactivationairductworkjointsmustbeairandvapour
tight.
Thedesignoftheductconnectionsshouldfacilitateeasydisconnectionoftheunitforserviceoutside
thecold-storageroom.
Condensationeasilybuildsupontheinsideoftheductduetothehighhumidityofthereactivationair.
Toavoidcondensation,theductworkmustbeinsulated.
Theprocessairductworkshouldbeinsulatedtopreventcondensationfromdevelopingontheoutside
oftheductwheneverthetemperatureoftheairwithintheductfallsbelowthedewpointoftheambient
airthroughwhichtheductworkisrouted.
Thewetairleavingthedehumidierwilleasilycausecondensationontheinsideoftheductwallsdueto
thehighmoisturecontent.Thismustbeavoidedbyinsulatingtheducts.
Ensurethataccessforoperationandservicingisnotrestrictedwhendesigningandinstallingducting.
Formoreinformation,seesection8.1,Dimensionsandservicespace.
Toreducenoiseand/orvibrationbeingtransmittedalongrigidductwork,goodquality,airtightexible
connectionsshouldbetted.
Ductsmounteddirectlyontothedehumidiershouldbeadequatelysupportedtominimisetheloadand
stressduetotheweightandmovementoftheducting.
8Installation190TGB-1037-G1307
IceDry800/1400
Dampersforbalancingtheairowmustbeinstalledinthereactivationairinletduct.Correctairows
areessentialformaintainingtheoperatingefciencyoftheunit.Forairowadjustmentdetails,see
section4.11,Airowcheckandadjustment.
Processairpressureandowareadjustedusingtheprocessairfan'sfrequencyconverter.Ifthisisthe
case,itisnotnecessarytohaveadamperinthedryairduct.
Thetotalresistanceintheprocessandreactivationductworkmustnotexceedtheperformancerating
ofthefansttedinthedehumidier.Fordetailsofminimumavailablestaticpressure,seechapter
8.2,Technicaldata.
4.6.2Processairinlet
Thedehumidierhasanexternallterboxfortheprocessairinlet.Ifthereisariskoftheprocessairlter
icingup,aductshouldbeconnectedtoretrieveprocessairfromadrylocation5-10metresfromthedoor
opening.Thelterboxcanthenbemovedtotheinletsideoftheduct.
4.6.3Dryairoutletduct
Channeloutthedryairfromthedehumidieranddistributeitsothatitmixeswiththewarm,humidairthat
normallyentersthecoldstoreabovethedoorsandair-locksthatareopenedregularly.Installanadjustable
damperintheduct.
4.6.4Reactivationairintake
Placethereactivationairintakeandlterboxoutsidethecoldstore.Mountthelterboxdirectlyonthewall.
Theducttothedehumidierreactivationairintakeshouldbeatmost1.5metreslong,andmustbeinsulated
topreventicebuild-up.Thisalsoappliestothesectionofductpassingthroughthewall.Anadjustable
damperisinstalledintheduct.
Topreventtheoutgoingwetairhumidifyingtheincomingreactivationair,thereactivationairintakemustbe
positionedatleast2metresfromthewetairoutlet
A.Reactivationair
B.Wetair
1.Filterbox
2.Condensatedrains
Figure4.1Inletforreactivationairandoutletforwetair.
3.Vapour-tightgrommet
190TGB-1037-G1307Installation9
IceDry800/1400
4.6.5Ductworkforwetairoutlet
Thewetairductmustbemadeofplasticoranothercorrosionresistantmaterial.Itmustbeabletohandle
temperaturesbetween-30°Cand75°C,benomorethan1.5metreslongandbeinsulatedtopreventice
formation.Thisalsoappliestothepartoftheductpassingthroughthewall.
Becauseofitshighmoisturecontentthewetairleavingthedehumidierwillcondenseontheinsideof
theductwalls.Duetothelowambienttemperaturethereisariskoficeformation.Thewetairductmust
thereforebeinsulated.
Horizontalductsmustbeinstalledwithaslightdecline(awayfromthedehumidier)todrainaway
possiblecondensation.Thedeclinemustbeatleast2cm/mofduct.
5mmdrainholesshouldbemadeatlowpointsoftheducttopreventwateraccumulationintheduct.
Topreventtheoutgoingwetairfromhumidifyingtheincomingreactivationair,thewetairoutletmust
beplacedatleast2metresfromthereactivationinlet.SeeFigure4.1.
NOTE!Alwaysdrillthedrainholesontheoutsideofthecoldstorage/freezerroomwall.
W W
W
ARNING! ARNING!
ARNING!
Thewetairoutletishot.Toavoidburnsfromunintendedcontact,makesureitisinsulated.
10Installation190TGB-1037-G1307
IceDry800/1400
4.7Installationexamplescoldstorageroom(freezer)
Muntersrecommendsthefollowinginstallations.Ifindoubt,contactMuntersforadvice.
Notetheservicespacerequirementsinsection8.1,Dimensionsandservicespace.
A
B
Figure4.2Positionabovedoor/airlock
A.ProcessairinletB.Dryairoutlet
2 - 3 m
Figure4.3Positionbehindscreen.
190TGB-1037-G1307Installation11
IceDry800/1400
5 - 10 m
Figure4.4Positionfarawayfromdoor/airlock.
5 - 10 m
Figure4.5Processairductfarawayfromdoor/airlock.
CA CA
CA
UTION! UTION!
UTION!
Activatethemainswitchforthedehumidierassoonastheunithasbeeninstalled.Thisallowsthebuilt-inheater
tooperateandpreventsinternaliceformation.
Theopeningsofinletandoutletductsmustbewellsealedduringinstallationandoperationstops,whenthe
dehumidierisnormallyswitchedoff.Thispreventsiceformationinductsanddehumidiercausedby
unintendedventilationandlowtemperatureinthecold-storageroom.
12Installation190TGB-1037-G1307
IceDry800/1400
4.8Electricalconnections
W W
W
ARNING! ARNING!
ARNING!
Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
Allunitsaredeliveredcompletewithallinternalcablinginstalledandconguredtothevoltageand
frequencygivenontheIDplate.
NOTE!Supplyvoltagemustnotvarymorethan10%ofthespeciedoperatingvoltage.
Theunitmustbeadequatelyconnectedtoearth.
Forconnectiondetails,refertotheIDplate,Electricalcircuitdiagramsorsection8.2,Technicaldata.The
connectioncableandmainfusesmustbesuitabletotheunitbeinginstalled.
Connecttheunitwithaexiblecabletoawallmountedsocket.Thiswaytheunitcaneasilybedisconnected
fromthepowersupplybyremovingtheplugfromthesocket.
190TGB-1037-G1307Installation13
IceDry800/1400
4.9Pre-startsettings
Ondeliverytheoperationalparametersaresetforuseinacoldstore.
Theapplicationdoesnotrequiretheconnectionofexternalsensorsorexternalinput/outputsignals.
4.10Pre-startchecks
W W
W
ARNING! ARNING!
ARNING!
Themainpowersupplyispermanentlyconnectedtothemainpowerswitchoftheunit.Adjustments,maintenance
andrepairsmustonlybecarriedoutbyauthorisedpersonnel.
Beforestartingthedehumidierforthersttime,ensurethatthemainpowersupplyisisolatedfromthe
dehumidierandcarryoutthefollowingchecks:
1.MakesurethatthemodeselectorswitchonthedehumidierisintheOFFposition..
2.Makesurethattheairintakeltersareundamagedandproperlytted,andthatallareasinsidetheunit
arecleanandfreefromice.
3.Visuallyinspectallductingandductconnectionstomakesurethatallconnectionshavebeencorrectly
installedandthattherearenosignsofdamagetothesystem.Alsocheckthatallductsarefreefrom
obstaclesblockingtheairpassage.
4.Checkthattheincomingpowersupplyvoltageiscorrectandthatthecablesarecorrectlyconnected.
5.Afterconnectingtheprocessfantopower,checkthefanturningdirection.
6.Openthedehumidier'sfrontpanel.
7.Startthedehumidierandcheckthatthefanisturning.
8.Switchoffthedehumidierandcheckthefanjustbeforeitstops.Makesureithasaclockwiserotation
9.Makesurethattheunit'spowersupplyandmainswitchareonassoonastheunithasbeeninstalledinthe
cold-storageroom.Ifnot,checkifthereisiceintheunit.
10.Setthedamperforthereactivationairowfullyopen.
11.Setthedamperfortheprocessairow50%open.
CA CA
CA
UTION! UTION!
UTION!
Iftheprocessairowdamperisfullyopen,thehighcoldairdensityinthecold-storageroomcoulddamagethe
processairfan.
CA CA
CA
UTION! UTION!
UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
14Installation190TGB-1037-G1307
IceDry800/1400
4.11Airowcheckandadjustment
ContactMuntersServicefordehumidierinstallationandadjustment.TheaddressestoMunterscanbe
foundonthebackpageofthismanual.
CA CA
CA
UTION! UTION!
UTION!
Iftheprocessandreactivationairowsarenotproperlyadjusted,theunitcanmalfunction.Theairowmustbeset
tomaximum10%abovethespeciednominalvaluelistedinsection8.2,Technicaldata.
1.Byadjustingthedampersinstalledinthedryairoutletandreactivationairinletducts,theprocessand
reactivationairowscanbechangedtotherequiredsetting.
2.Startthedehumidierforapproximately10minutestoallowthereactivationheatertoreachitsnormal
operatingtemperature.Seesection5.5,Operatingtheunit.
3.Checkthatthetemperaturedifferencebetweenreactivationairdownstreamoftheheater,andthe
regenerationtemperatureisapprox.95°C(tolerancelimitis±5°C).
4.Ifthetemperaturedifferenceliesoutsideofthetolerancelimit,thereactivationairdampercanbe
adjustedinsmallsteps(whichcausesthetemperatureindicatortostabiliseaftereachadjustment)until
reactivationtemperatureiswithinthespeciedtolerances.
Example:
Inletairtemperature=15°C
Reactivationairtemperature=110°C
Temperatureincrease=95°C
190TGB-1037-G1307Installation15
IceDry800/1400
5Operation
5.1General
ThedehumidierisequippedwithanoperatorpanelthatcontainsmodeswitchandLEDindicators.The
modeswitchoftheoperatorpanelhastwooperatingmodes:
MAN(Manualmode):
Thedehumidiersfans,rotorandreactivationheateroperatecontinuouslywithfullcapacity.
AUT(Automaticmode)-notapplicable.
5.2Safety
W W
W
ARNING! ARNING!
ARNING!
Inthecaseofapowercut,thedehumidierwillrestartautomaticallywhenthepowersupplyisrestored.
CA CA
CA
UTION! UTION!
UTION!
Atinitialstart-uporwhenrestartingafteraservicestop,themainpowerswitchmusthavebeenonforatleast12
hoursbeforestarting.Thisisnecessarytoremoveanyicebuild-upinsidetheunit.
CA CA
CA
UTION! UTION!
UTION!
Beforestartingtheunit,thereactivationairinletandwetairoutletmustbethoroughlychecked.Anyicemustbe
removed.Toavoidmalfunction,itisimportanttohaveclearairpassagethroughouttheductwork.
CA CA
CA
UTION! UTION!
UTION!
Topreventdamagetothefans,theunitmustnotberunforlongerthanafewminutespriortosetting-uptheprocess
andreactivationairows.
CA CA
CA
UTION! UTION!
UTION!
Donotturnoffthemainpowerswitch.Thiscanleadtoiceformationandmalfunctionofthedehumidier.
5.3Quickstop
Themodeswitchisusedtostartandstoptheunitinnormaloperation.Incaseofanemergency,usethemain
powerswitchonthedehumidier,seesection5.4,Operatorpanel.
CA CA
CA
UTION! UTION!
UTION!
Onlyusethemainpowerswitchtostoptheunitinthecaseofanemergency.Thenormalshutdownsequencewill
notbefollowed.Thefansstopandtheheatercanbeveryhot,whichcanresultindamagetotheheaterandother
componentsclosetoit.
16Operation190TGB-1037-G1307
/