2 Frequency Converter Control
2.1 Introduction
This section describes the optional display interfaces
available for the frequency converter, the inputs and
outputs, and the control terminal functions.
The following optional interfaces are available:
•
Numerical Local Control Panel (LCP 21).
•
Graphical Local Control Panel (GLCP or LCP 102).
Use the selected interface to adapt parameter settings or
read status.
Commands given to the frequency converter are indicated
on the selected interface display. Fault logs are maintained
within the frequency converter, for fault history. The
frequency converter issues warnings and alarms for fault
conditions arising within or external to the frequency
converter itself. Usually, the fault condition is found outside
of the frequency converter.
2.2 Status Messages
Status messages appear in the bottom of the display. The
left part of the status line indicates the active operation
model of the frequency converter.
The center part of the status line indicates the references
site. The last part of the status line gives the operation
status, for example:
•
Running.
•
Stop.
•
Standby.
Other status messages may appear and are related to the
software version and frequency converter type.
2.3 Frequency Converter Inputs and
Outputs
The frequency converter operates by receiving control
input signals. The frequency converter can also output
status data or control auxiliary devices.
Control input is sent to the frequency converter in 3 ways:
•
Via the optional LCP connected by cable to the
frequency converter, operating in [Hand On]
mode. These inputs include start, stop, reset, and
speed reference.
•
Via serial communication from a eldbus,
connected to the frequency converter through
the RS485 serial port, or through a communi-
cation option card. The serial communication
protocol:
- Supplies commands and references to
the frequency converter.
- Programs the frequency converter.
- Reads status data from the frequency
converter.
•
Via signal wiring connected to the frequency
converter control terminals. Improperly connected
control wiring can result in the frequency
converter failing to start or to respond to a
remote input.
2.3.1 Input Signals
The frequency converter can receive 2 types of remote
input signals: digital or analog. Digital inputs are wired to
terminals 18, 19, 20 (common), 27, 29. Analog or digital
inputs are wired to terminals 53 or 54 and 55 (common). A
switch placed under the LCP sets the terminal functions.
Some options include additional terminals.
Analog signals can be either voltage (0 V to +10 V DC) or
current (0–20 mA or 4–20 mA). Analog signals can be
varied like dialing a rheostat up and down. The frequency
converter can be programmed to increase or decrease
output in relation to the amount of current or voltage. For
example, a sensor or external controller may supply a
variable current or voltage. The frequency converter
output, in turn, regulates the speed of the motor
connected to the frequency converter in response to the
analog signal.
Digital signals are a simple binary 0 or 1 acting as a switch.
A 0-24 V DC signal controls the digital signals. A voltage
signal lower than 5 V DC is a logic 0. A voltage higher than
10 V DC is a logic 1. 0 is open, 1 is close. Digital inputs to
the frequency converter are switched commands such as
start, stop, reverse, coast, reset. (Do not confuse these
digital inputs with serial communication formats where
digital bytes are grouped into communication words and
protocols).
The RS485 serial communication connector is wired to
terminals (+) 68 and (-) 69. Terminal 61 is a common
terminal. It is used for terminating shields only when the
control cable is run between frequency converters, and not
between frequency converters and other devices.
Parameters for
conguring
the input and output using
NPN and PNP.
These parameters cannot be changed while the motor is
running.
Frequency Converter Control
18 02/2017 All rights reserved. BAS-SVM04B-EN
2