©Copyright Task Force Tips LLC 2000-2020 LIM-025 June 23, 2010 Rev08
2
Table Of Contents
1.0 MEANING OF SIGNAL WORDS
2.0 SAFETY
3.0 GENERAL INFORMATION
3.1 USE WITH SALT WATER
3.2 VARIOUS MODELS TERMS
3.2.1 MECHANICAL SPECIFICATIONS
3.3 ELECTRIC INSTALLATION
3.4 PATTERN CONTROL
3.5 FLUSH CONTROL
3.6 STANDARD / LOW PRESSURE KNOB (MAX-FORCE)
4.0 USE OF MAX SERIES NOZZLES
5.0 FLOW CHARACTERISTICS
5.1 STREAM TRAJECTORY DATA
5.2 FLOW CHARTS
6.0 USE WITH FOAM
6.1 FOAM ASPIRATING ATTACHMENTS
7.0 WARRANTY
8.0 MAINTENANCE
8.1 FIELD LUBRICATION
8.2 SERVICE TESTING
8.3 REPAIR
9.0 EXPLODED VIEW AND PARTS LIST
10.0 OPERATION AND INSPECTION CHECKLIST
PERSONAL RESPONSIBILITY CODE
The member companies of FEMSA that provide emergency response
equipment and services want responders to know and understand the
following:
1. Fireghting and Emergency Response are inherently dangerous activities
requiring proper training in their hazards and the use of extreme caution
at all times.
2. It is your responsibility to read and understand any user’s instructions,
including purpose and limitations, provided with any piece of equipment
you may be called upon to use.
3. It is your responsibility to know that you have been properly trained in
Fireghting and /or Emergency Response and in the use, precautions, and
care of any equipment you may be called upon to use.
4. It is your responsibility to be in proper physical condition and to maintain
the personal skill level required to operate any equipment you may be
called upon to use.
5. It is your responsibility to know that your equipment is in operable
condition and has been maintained in accordance with the manufacturer’s
instructions.
6. Failure to follow these guidelines may result in death, burns or other
severe injury.
FEMSA
Fire and Emergency Manufacturers and Service Association
P.O. Box 147, Lynneld, MA 01940 • www.FEMSA.org
SUPPORTING MATERIALS
The following documents contain supporting safety and operating information
pertaining to the equipment described in this manual.
TASK FORCE TIPS
ELECTRIC REMOTE NOZZLES
ELECTRIC REMOTE WIRING DIAGRAM
TASK FORCE TIPS LLC 3701 INNOVATION WAY, VALPARAISO, IN 46383-9327
(800) 348-2686 (219) 462-6161 FAX (219) 464-7155
MADE IN USA • TFT.COM
LESS ELABORATE WIRING
SYSTEMS MAY BE USED BY
ELIMINATING UPPER CONTROL
OR REMOTE CONTROL STATIONS
LIM-040 August 1, 2018 Rev05©Copyright Task Force Tips LLC 1998-2018
©Copyright Task Force Tips LLC 2008-2019 LIY-500 April 8, 2019 Rev14
MANUAL: Remote Control (RC)
Monitor Electrical Controls
Supplemental Instructions for use with RC Monitor Manual
INSTRUCTIONS FOR INSTALLATION, SAFE OPERATION AND MAINTENANCE
Understand manual before use. Operation of this device without understanding the manual and
receiving proper training is a misuse of this equipment. Obtain safety information at www.tft.
com/serial-number
TASK FORCE TIPS LLC
MADE IN USA • tft.com
3701 Innovation Way, IN 46383-9327 USA
800-348-2686 • 219-462-6161 • Fax 219-464-7155
SECTION 4.1
Monitor Mounted
Operator Station
SECTION 4.2
Panel Mount
Operator Station
(Y4E-RP)
SECTION 4.3
Panel Mount With Display
Operator Station
(Y4E-RP-D)
SECTION 4.4
Tethered
Operator Station
(Y4E-CT-##)
SECTION 4.5
Tethered Operator Station
With Display
(Y4E-CT-##-D)
SECTION 4.6
Wireless
Operator Station
(YE-RF-##)
SECTION 4.7
Wireless Operator Station
With Display
(YE-RF-##-D)
SECTION 3.0
SECTION 4.0
Electrical Controls Installation and Operation
SECTION 4.11
Monitor Position Display
(Y4E-DISP)
SECTION 4.12
Remote Auxiliary Function
Interface Control
(YE-REMAUX)
SECTION 4.13
Electric RC Monitor Aerial
Truck Installation
SECTION 4.16
Electric Nozzle Actuator
SECTION 4.17
Valve Kits
(YE-VK-PH)
SECTION 5.0
Troubleshooting
SECTION 4.14
Multiplex Interface Control (YE-CAN#)
SECTION 4.15
Ethernet Interface Control
SECTION 4.9
Toggle Switch Monitor
Operator Station
(Y4E-TS)
SECTION 4.10
Monitor Communication
Interface Control
(Y4E-COMM)
SECTION 4.8
Joystick
Operator Station
(Y4E-JS)
©Copyright Task Force Tips, Inc. 2009 LTT-135 July 28, 2009 Rev00
NOZZLE TRAJECTORY
ELEVATION FACTORS
TASK FORCE TIPS, INC.
MADE IN USA • www.tft.com
3701 Innovation Way, Valparaiso, IN 46383-9327 USA
800-348-2686 • 219-462-6161 • Fax 219-464-7155
1.0 To estimate elevation angle when vertical and horizontal distances to target are known:
1.1 Find the maximum height and reach at 30° from the appropriate trajectory curve in LIM-030 or LIM-035.
1.2 Calculate the Height Factor by dividing the vertical distance to the target by maximum height from step 1.1.
1.3 Calculate the Reach Factor by dividing the horizontal distance to the target by maximum reach from step 1.1.
1.4 On the graph of nozzle trajectory elevation factors, plot the intersection of the Height Factor and Reach factor from steps 1.2 and 1.3. If this point lies
on or between the curves given, estimate the appropriate elevation angle. If this point lies within the shaded region of the graph, then a higher flow or
pressure must be used to reach the target.
2.0 To estimate maximum reach for a given elevation angle above 0°:
2.1 From the graph of nozzle trajectory elevation factors, choose the trajectory curve for the desired elevation angle.
2.2 Find the point where this trajectory curve intersects the height of discharge (zero height line).
2.3 Estimate the Reach Factor at this point using the scale across the top of the graph.
2.4 Multiply this Reach Factor by the reach at 30° elevation from the appropriate trajectory curve in LIM-030 or LIM-035.
3.0 To estimate maximum height for a given elevation angle above 0°:
3.1 From the graph of nozzle trajectory elevation factors, choose the trajectory curve for the desired elevation angle.
3.2 Find the maximum height on this trajectory curve.
3.3 Estimate the Height Factor at the maximum height using the scale on the left side of the graph.
3.4 Multiply this Height Factor by the height at 30° elevation from the appropriate trajectory curve in LIM-030 or LIM-035.
Stream reach and height at non-optimal elevations can be estimated as a factor of the performance at the optimal 30° elevation.
Refer to LIM-030 and LIM-035 for effective stream trajectories of Task Force Tips Masterstream nozzles at 30° elevation.
This graph cannot be used to estimate maximum reach for elevation angles below 30°.
-45
-1.5
-1.0
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.
Reach Factor (compared to 30° elevation)
Height Factor (compared to 30° elevation)
IF TARGET IS IN THIS REGION,
FLOW AND/OR PRESSURE MUST
BE INCREASED.
LIM-040
Electric Remote Nozzle
LIY-500
Remote Control (RC) Monitor
Electrical Controls
LIA-025
Foam Aspirators Manual
LTT-135
Nozzle Trajectory
Elevation Factors