Omega FP85A Owner's manual

Type
Owner's manual

Omega FP85A is a versatile flow transmitter designed to accurately measure and display flow rate, totalize flow, and provide pulse output. With its compatibility with various Omega flow sensors, the FP85A offers a wide range of applications in industries such as water treatment, chemical processing, and food and beverage. Its easy-to-use interface and customizable settings make it suitable for a variety of flow monitoring and control tasks.

Omega FP85A is a versatile flow transmitter designed to accurately measure and display flow rate, totalize flow, and provide pulse output. With its compatibility with various Omega flow sensors, the FP85A offers a wide range of applications in industries such as water treatment, chemical processing, and food and beverage. Its easy-to-use interface and customizable settings make it suitable for a variety of flow monitoring and control tasks.

Indicator
4-20 mA
FP85A
Gnd
+
-
4-20 mA
Loop
+
-
17-30V
*
A. Ground referenced PLC with internal transmitter power supply
B. Power connection for display use only
D. Power connection for display use only
C. 1 to 5 VDC recorder (C1), 4 to 20 mA indicator (C2), or ground referenced PLC (C3) connections without internal transmitter power supply
*
Refer to maximum loop impedance specification for minimum operating voltage requirements (section 10).
**1/8A fuse recommended (customer supplied)
1.1 2-Wire operation (for OMEGA FP-5200, FP-5300, FP-6000, FP-850X flow sensors).
CH - (gnd)
CH +
Power out
Recorder
1-5 VDC
CH -
(gnd)
CH +
+
-
C1
C2
FP85A
+
-
4-20 mA
Loop
+
-
17-30V
*
Gnd
FP85A
+
-
4-20 mA
Loop
+
-
17-30V
*
Gnd
+
-
24
*
VDC
Power
supply
FP85A
+
-
4-20 mA
Loop
+
-
17-30V
*
Gnd
A. Ground referenced PLC with internal transmitter power supply
B. Differential input PLC with internal transmitter power supply
CH - (gnd)
CH -
CH +
CH +
Power out
FP85A
+
-
4-20 mA
Loop
+
-
17-30V
*
Gnd
FP85A
+
-
4-20 mA
Loop
+
-
17-30V
*
Gnd
PLC
4-20 mA Input
24
VDC
*
Power
supply
C. 1 to 5 VDC recorder (C1) and 4 to 20 mA indicator (C2) connections without internal transmitter
power supply
*
Refer to maximum loop impedance specification for minimum operating voltage requirements (section 10).
**1/4 A fuse recommended (customer supplied).
1.2 3-Wire operation (for OMEGA FP-2541 flow sensors). This wiring is required for powered flow sensors that consume more than 1.5 mA DC current.
250*
+
+
-
-
24 VDC
+
-
24 VDC
PLC
4-20 mA Input
250
*
+
-
24 VDC
PLC
4-20 mA Input
250
*
250
*
Recorder
1-5 VDC
CH -
(gnd)
CH +
+
-
24
VDC
*
Power
supply
Indicator
4 -20 mA
CH -
(gnd)
CH +
+
-
24
VDC
*
Power
supply
250
*
CH -
(gnd)
CH +
+
-
24
VDC*
Power
supply
CH -
(gnd)
CH +
+
-
24*
VDC
Power
supply
PLC
4-20 mA Input
250
*
+
-
24
*
VDC
Power
supply
FP85A
+
-
4-20 mA
Loop
+
-
17-30V
*
Gnd
C3
C2
C1
Fuse**
1/8A
Fuse**
1/8A
Fuse**
1/8A
Fuse**
1/4A
Fuse**
1/4A
Fuse**
1/4A
Fuse**
1/4A
Fuse**
1/4A
Fuse**
1/8A
Fuse**
1/8A
OMEGA FP85A Flow Transmitter Instructions
CAUTION!
Remove power to unit before wiring input and output connections.
1. Loop/System Power Connections
2. Compatible Sensor Connections
OMEGA Flow Sensor:
OPEN
COLLECTOR
SENSOR
STANDARD
SENSOR
Sensor Power
Gnd
Frequency In
Frequency In
OPEN
COLLECTOR
SENSOR
STANDARD
SENSOR
Sensor Power
Gnd
Frequency In
Frequency In
OMEGA Flow Sensors:
OR
Red
Black
Shld
FP-2541
Shld
Black
Red
FP5100,
FP-5200,
FP-5300,
FP-6000,
FP-8501A
Red
Black
Shld
FP8501A
FP8502A
FP8503A
FP85A
FP85A
2.1 2-Wire Operation (sec. 1.1) 2.2 3-Wire Operation (sec. 1.2)
5. FUNCTIONS
OPTIONS
CALIBRATE
VIEW
2s 5s
Press &
hold for
access:
6. VIEW (example)
Loop output
Save:
Choose:
1
Change:
2
3
Last cal.
Flow rate
Permanent tota
l
2s
Resettable total
2s
OPTIONS =
Press keys in
sequence
OPTIONS =
Press and
hold 2s
Press and
hold 2s
quick
press
To exit without
changes:
1.
2.
1.
2.
3.
A
E
4. Installation Options
4.1 Standard Panel Mount
• Panel cutout template/instructions (included).
4.2 Optional FP85UNM Universal Mounting Kit
NPT and DIN conduit port kits available (see section 4.3).
See section 9 for ordering options.
Pipe Pipe
Panel
Panel
®
FP85-A Flow Transmitter
®
FP85-A Flow Transmitter
4.3 Optional FP85NM Integral Mounting Kit
NPT and DIN conduit port kits available.
Compatible with FP850X flow sensors (only).
Flow sensor and fitting purchased separately (see section 9).
Conduit ports
1/2 in. NPT
threaded conduit
ports (2)
PG13.5 metric
threaded conduit
ports (2)
Blind holes
for DIN conduit
connectors (8)
Conduit Port Options
NPT Ports
DIN Ports
3. Pulse Output Wiring
Pulse Gnd
Pulse Out
Shld
Red
Receiving
instrument
FP85A
Pulse Gnd
Pulse Out
Gnd.
Input
Other
instrument
FP85A
10 kΩ
+
-
5 to 30
VDC
Instrument
panel
®
FP85-A Flow Transmitter
A.
B.
C.
D.
E.
8. OPTIONS (example)7. CALIBRATE (example)
9. Accessories
1 2
3
To return to
VIEW:
quick
press
To restore original value:
quick
press
Change: Save:Choose:
Press &
hold
2s
Contrast
Flow
Totalizer
Totalizer
Output
Output
Last calibration
Unit/timebase:
h,m,s,d
K-factor
Units
- label only -
4 mA
setpoint
20 mA
setpoint
Flow
K-factor
Return to
VIEW before
removing
power
Press keys in sequence to
continue:
A
H
1 2
To return to
VIEW:
quick
press
To restore original value:
Choose:
3
Save:
Change:
quick
press
Press keys in sequence to
continue:
2s
Press &
hold
VIEW= VIEW=Totalizer
low= τ=700 ms
hi= τ=3 s
off= 100 ms
Display
averging
Flow display
Output
Output
Decimal
postion
4 mA
adjust
20 mA
adjust
Return to
VIEW before
removing
power
A
E
A.
B.
C.
D.
E.
F.
G.
H.
A.
B.
C.
D.
E.
Menu Functions A - H:
A. Selects display contrast: 4 levels
B. Sets flow units (gpm) and timebase (gpm). Flow units label: Aa - Zz, 0 - 9;
Timebase options: s=seconds, m=minutes, h=hours, d=days (timebase
effects flow display and 4 to 20 mA output)
C. Sets flow K-factor: 000.01 to 99999. (see technical notes below)
D. Set totalizer units: For label purposes only
E. Sets totalizer K-factor: 000.01 to 99999. (see technical notes below)
F. Sets 4 mA setpoint (4 mA and 20 mA setpoints are reversible)
G. Sets 20 mA setpoint
H. Sets user defined date
Technical notes:
Flow and totalizer K-factors are independent of each other. These K-factors
represent the number of pulses generated by the flow sensor for each
engineering unit measured (published in flow sensor manual).
Menu Functions A - E:
A. Selects totalizer reset options: Lock on (enables) or lock off (disables) the
VIEW menu totalizer reset security code feature (RST: -- -- -- --).
B. Selects display averaging: off = 100ms, low= τ=700ms, hi= τ=3s (also
affects 4 to 20 mA output).
C. Selects display decimal:
****
. to
**
.
**
D. Adjusts 4 mA output: 3.9 to 4.1 mA (overrides 4.00 mA factory calibration)
E. Adjusts 20 mA output: 19.8 to 21.0 mA (overrides 20.00 mA factory
calibration)
Order no. Description
FP85UNM Universal mounting kit, NPT ports
FP85UDM Universal mounting kit, DIN ports
FP85NM Integral sensor mounting kit, NPT ports
FP85DM Integral sensor mounting kit, DIN ports
FP8501 Integral sensor, 0.5 to 4 inch pipe, Polypropylene body & Titanium rotor pin
FP8502 Integral sensor, 5 to 8 inch pipe, Polypropylene body & Titanium rotor pin
FP8503 Integral sensor, 0.5 to 4 inch pipe - PVDF body & Hastelloy C rotor pin
FP8501A Integral sensor, 0.5 to 4 inch pipe, Polypropylene body & Titanium rotor pin
FP8502A Integral sensor, 5 to 8 inch pipe - Polypropylene body & Titanium rotor pin
FP8503A Integral sensor, 0.5 to 4 inch pipe - PVDF body & Hastelloy C rotor pin
107 mm
(4.2 in.)
107 mm (4.2 in.)
®
FP85A Flow Transmitter
11. Troubleshooting
Display Message Cause Solution
1) Input frequency too high
2) Display overrange
3) Display timebase too large
1) Reduce input frequency.
2) Move display decimal to right in OPTIONS menu.
3) Change display timebase (H,M,S,D) to smaller value
(e.g. LPH to LPM).
Memory corrupted
Press to restore normal operation. Settings will revert to
factory default. Recalibration is required.
K-Factor cannot be zero
Change K-Factor to a non-zero value.
2s
2s
10. Specifications
General Data
Compatible Sensors: FP-8501, FP-5300, FP-5100, FP-6000, and
FP-5200 Series (contact engineering for
additional compatible sensors).
Display Accuracy: Flow, ±0.1% of reading
Totalizers, ±0.03% of reading
Enclosure:
Rating: NEMA 4X/IP65
Material: Glass-filled polypropylene
Gasket: Silicone rubber (captive)
Screws: 8-32, self-tapping (captive)
Display:
Type: 8-digit alphanumeric dot matrix
Update rate: Flow=1s, Totalizers=100 mS
Contrast: Variable
Ranges: Flow, 0.01 to 9999.
Resettable/permanent totalizers, 0 to
99999999
Loop current, 3.90 to 21.00 mA
Environmental
Operating temperature: -15 to 70 °C (5 to 158 °F)
Storage temperature: -15 to 80 °C (5 to 176 °F)
Relative humidity: 0 to 95%, non-condensing
Agency Approvals
•CE
• Manufactured under ISO 9001
Electrical Data
Frequency range: 0.5 Hz to 500 Hz
Loop/system power: (2-wire mode) 17 to 30 VDC @ 20 mA max.
(3-wire mode) 17 to 30 VDC @ 68 mA max.
Sensor power: (2-wire mode) 5 VDC @ 1.5 mA max.
(3-wire mode) 5 VDC @ 20 mA max.
Loop:
Impedance: 1 max. @ 17 VDC,
300 max. @ 24 VDC,
600 max. @ 30 VDC
Accuracy: ±0.050 mA
Resolution: 5 µA
Update rate: 100 ms
Outputs:
Current: 4 to 20 mA (adjustable & reversible)
Pulse output: Sensor frequency, optically isolated
open-collector transistor, max. current sink
10 mA @ 30 VDC
30 mm (1.2 in.)
36 mm (1.4 in.)
(side view)
(front view)
Dimensions:
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Omega FP85A Owner's manual

Type
Owner's manual

Omega FP85A is a versatile flow transmitter designed to accurately measure and display flow rate, totalize flow, and provide pulse output. With its compatibility with various Omega flow sensors, the FP85A offers a wide range of applications in industries such as water treatment, chemical processing, and food and beverage. Its easy-to-use interface and customizable settings make it suitable for a variety of flow monitoring and control tasks.