3. INSTRUMENT CONFIGURATION
• Remove instrument from case by loosening safety screw, grab bezel and slide out of case.
• Refer to Figure 15, Page 22, for jumper selection of Relay/SSR selection and AL1 Cool relay NO/
NC selection. Default factory settings are Main/Relay, AL1 Cool/Relay Normally open.
• Locate jumper V2 in Figure 14, page 21 and place in the open position.
• Slide instrument back in case and apply power. Display will now show CnF.
• Press the FUNC button until P1 is displayed.
• Refer to Parameter List on page 23. Using the UP arrow, select appropriate P1 code for Input
type and standard range.
• Press the FUNC button until next parameter is displayed.
• Repeat for each parameter to be changed.
• When configuration is complete, remove instrument from case, place jumper V2 in the closed
position, return instrument into case and secure with safety screw.
• Apply power to instrument, Upper display will show process temperature, lower display will
show setpoint.
• Using UP and DOWN arrows, temperature setpoint can be adjusted.
• Refer to Manual page 36 in for Control Parameters if PID tuning is required.
• Instrument is now ready for use.
NOTE: The preceding Quick Start instructions are the basic settings required to install, wire, and
get the controller operating. It is assumed that the operator is familiar with PID temperature
controllers. Please refer to the complete installation and operation manual for additional
functions and instructions.