Specifications
1 And 1-
1
/2 Ton Systems
60 HZ 50 HZ
AIR COOLED SYSTEM
with Outdoor Condensing Unit with Centrifugal Condensing Unit with Outdoor Condensing Unit with Centrifugal Condensing Unit
Split System Self-Contained Split System Self-Contained
1 T
on 1.5 Tons 1 Ton 1.5 Tons 1 Ton 1.5 Tons 1 Ton 1.5 Tons
E
vaporator MMD12E MMD18E MMD12A MMD18A MMD11E MMD17E MMD11A MMD17A
Condensing Unit PFH014A PFH020A MM2CF MM2CF PFH013A PFH019A MM2CF MM2CF
Net Capacity Data*BTUH (kW) High Fan Speed
80 F (27.7) DB Total 14,100 (4.1) 19,800 (5.8) 13,300 (3.9) 19,300 (5.7) 14,400 (4.2) 21,200 (4.2) 13,400 (3.9) 20,800 (6.1)
50% RH Sensible 11,600 (3.4) 15,500 (4.5) 11,300 (3.3)
15,300 (4.5) 11,700 (3.4) 16,000 (4.7) 11,300 (3.3) 15,900 (4.7)
75 F (23.9 C) DB Total 13,000 (3.8) 18,400 (5.4) 12,300 (3.6) 18,000 (5.3) 13,300 (3.9) 19,800 (5.8) 12,400 (3.6) 19,500 (5.7)
50% RH Sensible 11,200 (3.3) 15,000 (4.4) 10,900 (3.2) 14,900 (4.4) 11,300 (3.3) 15,600 (4.6) 10,900 (3.2) 15,500 (4.5)
72 F (22.2 C) DB Total 12,400 (3.6)
17,700 (5.2) 11,800 (3.5) 17,300 (5.1) 12,700 (3.7) 19,000 (5.6) 11,900 (3.5) 18,700 (5.5)
50% RH Sensible 10,900 (3.2) 14,800 (4.3)
10,600 (3.1) 14,600 (4.3) 11,000 (3.2) 15,300 (4.5) 10,700 (3.1) 15,200 (4.5)
Net Capacity Data*BTUH (kW) Low Fan Speed
80 F (26.7) DB Total 14,000 (4.1) 19,300 (5.7) 13,300 (3.9) 18,800 (5.5) 14,300 (4.2) 20,600 (6.0) 13,400 (3.9) 20,300 (5.9)
50% RH Sensible 10,500 (3.1) 13,800 (4.0) 10,200 (3.0) 13,700 (4.0) 10,600 (3.1) 14,400 (4.2) 10,200 (3.0) 14,200 (4.2)
75 F (23.9 C) DB Total 12,900 (3.8) 18,000 (5.3) 12,300 (3.6) 17,700 (5.2) 13,200 (3.9) 19,200 (5.6) 12,400 (3.6) 18,900 (5.5)
50% RH Sensible 10,100 (3.0) 13,500 (4.0) 9,900 (2.9) 13,400 (3.9) 10,200 (3.0) 14,000 (4.1) 9,900 (2.9) 13,900 (4.1)
72 F (22.2) DB Total 12,300 (3.6) 17,200 (5.0) 11,800 (3.5) 16,900 (5.0) 12,600 (3.7) 18,400 (5.4) 11,900 (3.5) 18,200 (5.3)
50% RH Sensible 9,900 (2.9) 13,300 (3.9) 9,700 (2.8) 13,100 (3.8) 10,000 (2.9) 13,800 (4.0) 9,700 (2.8) 14,200 (4.2)
60 HZ 50 HZ
WATER COOLED GLYCOL COOLED WATER COOLED GLYCOL COOLED
Self-Contained Self-Contained Self-Contained Self-Contained
1 Ton 1.5 Tons 1 Ton 1.5 Tons 1 Ton 1.5 Tons 1 Ton 1.5 Tons
Evaporator MMD14W MMD20W MMD14W MMD20W MMD13W MMD19W MMD13W MMD19W
Net Capacity Data*BTUH (kW) High Fan Speed
80F (26.7) DB Total 15,000 (4.4) 22,000 (6.4) 13,700 (4.0) 19,900 (5.8) 15,000 (4.4) 23,000 (6.7) 13,900 (4.1) 21,300 (6.2)
50% RH Sensible 12,500 (3.7) 16,600 (4.9) 12,000 (3.5) 15,800 (4.6) 12,400 (3.6) 15,500 (4.5) 12,000 (3.5) 16,400 (4.8)
75 F (23.9 C) DB Total 13,900 (4.1) 20,500 (6.0) 12,800 (3.8) 18,600 (5.4) 13,900 (4.1) 21,300 (6.2) 12,900 (3.8) 20,000 (5.9)
50% RH Sensible 12,000 (3.5) 16,100 (4.7) 11,600 (3.4) 15,400 (4.5) 12,000 (3.5) 15,100 (4.4) 11,600 (3.4) 15,900 (4.7)
72 F (22.2 C) DB Total 13,300 (3.9) 19,600 (5.7) 12,300 (3.6) 17,900 (5.2) 13,300 (3.9) 20,400 (5.6) 12,400 (3.6) 19,200 (5.6)
50% RH Sensible 11,800 (3.5) 15,800 (4.6) 11,400 (3.3) 15,100 (4.4) 11,800 (3.5) 14,900 (4.4) 11,400 (3.3) 15,700 (4.6)
Net Capacity Data*BTUH (kW) Low Fan Speed
80 F (26.7) DB Total 14,600 (4.3) 21,100 (6.2) 13,400 (3.9) 18,900 (5.5) 14,500 (4.2) 23,900 (7.0) 13,500 (4.0) 20,700 (6.1)
50% RH Sensible 11,000 (3.2) 14,800 (4.3) 10,500 (3.1) 13,900 (4.1) 11,000 (3.2) 17,300 (5.1) 10,600 (3.1) 14,600 (4.3)
75 F (23.9 C) DB Total 13,500 (4.0) 19,700 (5.8) 12,500 (3.7) 17,800 (5.2) 13,500 (4.0) 22,200 (6.5) 12,600 (3.7) 19,300 (5.7)
50% RH Sensible 10,700 (3.1) 14,400 (4.2) 10,200 (3.0) 13,600 (4.0) 10,600 (3.1) 16,900 (5.0) 10,300 (3.0) 14,300 (4.2)
72 F (22.2 C) DB Total 12,900 (3.8) 18,900 (5.5) 12,000 (3.5) 17,100 (5.0) 12,900 (3.8) 21,200 (6.2) 12,100 (3.5) 18,600 (5.4)
50% RH
Se
nsibl
e 10,400 (3.0) 14,200 (4.2) 10,000 (2.9) 13,400 (3.9) 10,400 (3.0) 16,500 (4.8) 10,100 (3.0) 14,000 (4.1)
60 HZ 50 HZ
CHILLED WATER
Self-Contained Self-Contained
1.5 Tons 1.5 Tons
Evaporator MMD23C MMD22C
Capacity Data BTUH (kW) High Fan Speed
80 F (26.7) DB Total 21,800 (6.4) 21,800 (6.4)
50% RH Sensible 16,000 (4.7) 16,000 (4.7)
75 F (23.9 C) DB Total 14,300 (4.2) 14,300 (4.2)
50% RH
Se
nsible 13,100 (3.8) 13,100 (3.8)
72 F (22.2 C) DB
T
otal 11,000 (3.2) 11,000 (3.2)
50% RH
Se
nsible 11,000 (3.2) 11,000 (3.2)
C
apacity Data
B
TUH (kW) Low Fan Speed
80 F (26.7) DB
Total 17,100 (5.2) 17,100 (5.2)
50% RH
Sensible 12,800 (3.7) 12,800 (3.7)
75 F (23.9 C) DB
Total 11,300 (3.1) 11,300 (3.1)
50% RH
Sensible 10,300 (3.0) 10,300 (3.0)
72 F (22.2 C) DB
Total 8,500 (2.5) 8,500 (2.5)
50% RH
Sensible 8,500 (2.5) 8,500 (2.5)
*The ne
t c
a
p
ac
ity data has fan motor heat factored in for all ratings and the entering air condition of 72˚F (22.2˚C), 50% RH is the standard rating condition of ASHRAE 127-2001