Honeywell PRO TH3110D Installation guide

Type
Installation guide

This manual is also suitable for

PRO TH3000 Series
Non-Programmable Digital Thermostat
® U.S. Registered Trademark. Patents pending.
Copyright © 2009 Honeywell International Inc.
All rights reserved.
Installation
Guide
69-1929EFS-01
This manual covers the following models
TH3110D: For 1 Heat/1 Cool systems
• TH3210D:For2Heat/1Coolheatpumpsystemsonly
(Pullthermostatfromwallplateandturnovertofindmodelnumber.)
System Types
TH3110D:
Gas, oil, or electric heat with air
conditioning
• Warmair,hotwater,high-
efficiencyfurnaces,1Heat/1
Coolheatpumps,steam,gravity
• Heatonly
• Heatonlywithfan
• Coolonly
• 750mVheatingsystems
TH3210D:
• 2Heat/1Coolheatpumps
Must be installed by a trained, experienced technician
Readtheseinstructionscarefully.Failuretofollowtheseinstructions
candamagetheproductorcauseahazardouscondition.
Need Help?
Forassistancewiththisproductpleasevisithttp://customer.honeywell.com
orcallHoneywellCustomerCaretoll-freeat1-800-468-1502
Installation Guide
69-1929EFS—01 2
ENGLISH
MCR29390
PULL HERE
HIPS
M29389
Wallplate installation
Removethewallplatefromthe
thermostatasshownatleft,then
followdirectionsbelowformounting.
1. Pullwiresthroughwirehole.
2. Position wallplate on wall, level and mark
hole positions with pencil.
3. Drill holes at marked positions as shown
below,thentapinsuppliedwallanchors.
4. Place wallplate over anchors, insert and
tightenmountingscrews.
Pullatbottomtoremovethermostat
fromwallplate.
CAUTION: ELECTRICAL HAZARD
Cancauseelectricalshockorequipmentdamage.Disconnectpowerbeforebeginning
installation.
Drill3/16"holesfordrywall.Drill7/32"holesforplaster.
Wallanchors
Wirehole
MERCURY NOTICE
Ifthisproductisreplacingacontrolthatcontainsmercuryinasealedtube,donot
placetheoldcontrolinthetrash.Contactyourlocalwastemanagementauthorityfor
instructionsregardingrecyclingandproperdisposal.
Mountingscrews
PRO TH3000 series
3 69-1929EFS—01
ENGLISH
MCR29391
Power options
TH3110D Terminal block shown
Connect C forprimaryACpower
(optionalifbatteriesareinstalled).
Keep wires in this
shaded area
Insertbatteriesforprimaryorbackuppower
TH3110D:
C 24Vaccommon.For2transformer
systems,usecommonwirefrom
coolingtransformer.
B Changeovervalveenergizedin
heating
R 24Vacpowerfromheating
transformer
Rc 24Vacpowerfromcooling
transformer
O Changeovervalveenergizedin
cooling
G Fan relay
Y Compressor contactor
W Heat relay
TH3210D:
C 24Vaccommon
B Changeovervalveenergizedin
heating
R 24Vacpower
L SendsoutputwhensettoEm.Heat
O Changeovervalveenergizedin
cooling
G Fan relay
Y Compressor contactor
Aux Auxiliaryheatrelay
E Emergencyheatrelay
Terminal designations
Wiring
Removefactory-
installedjumper
onlyfortwo-
transformer
systems.
CROGY
E
BAux L
M29393
CROGYWBRc
MCR29392
Installation Guide
69-1929EFS—01 4
ENGLISH
Wiring
2H/1C Heat
Pump System
TH3210D
C 24Vaccommon[3]
B Changeovervalveenergizedin
heating [5]
R Power [1]
L SendsoutputwhensettoEm.Heat[8]
O Changeovervalveenergizedin
cooling [5]
G Fan relay
Y Compressor contactor
Aux Auxiliaryheatrelay[9]
E Emergencyheatrelay[9]
1H/1C System
TH3110D
(1 transformer)
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power [1]
G Fan relay
Y Compressor contactor
W Heat relay
1H/1C System
TH3110D
(2 transformers)
C 24Vaccommon[3, 4]
R Power(heatingtransformer)[1, 2]
Rc Power(coolingtransformer)[1, 2]
G Fan relay
Y Compressor contactor
W Heat relay
See [notes] below
1H/1C Heat
Pump System
TH3110D [7]
C 24Vaccommon[3]
B Changeovervalveenergizedin
heating[5]
R [R+Rcjoinedbyjumper]
Rc Power [1]
O Changeovervalveenergizedin
cooling [5]
G Fan relay
Y Compressor contactor [6]
W [W+Yjoinedbyjumper]
Heat Only
System
TH3110D
C 24Vaccommon [3]
R [R+Rcjoinedbyjumper]
Rc Power [1]
W Heat relay
Heat Only
System with
Fan TH3110D
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power [1]
G Fan relay
W Heat relay
Cool Only
System
TH3110D
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power [1]
G Fan relay
Y Compressor contactor
NOTES
Wirespecifications:
Use18-to22-gaugethermostatwire.
Shieldedcableisnotrequired.
[1] Powersupply.Providedisconnectmeans
andoverloadprotectionasrequired.
[2] Removejumperfor2-transformersys-
tems.
[3] Optional24Vaccommonconnection.
[4] Commonconnectionmustcomefrom
coolingtransformer.
[5] UseeitherOorBterminalsforchangeover
valve.
[6] Useasmallpieceofwire(notsupplied)to
connectWandYterminals.
[7] SetfanoperationswitchtoHeat Pump
(seepage5)andconfiguresystemtype
forheatpump(seepage6).
[8] L terminal sends a continuousoutput
whenthermostatissettoEm.Heat.
ConnecttoHoneywellzoningpanelsto
switchthepaneltoEmergencyHeat.
[9] InstallfieldjumperbetweenAuxandEif
there is no emergency heat relay.
Wiring guide — conventional and heat pump systems
CROGY
E
BAux L
M29393
CROGYW BRc
MCR29394
CROGYW BRc
MCR29395
CROGYWBRc
MCR29396
CR
O
W
B
Rc
MCR29397
CROGY BRc
MCR29399
PRO TH3000 series
5 69-1929EFS—01
ENGLISH
MCR29401
MCR29400
TH3110D only:
• Gas or Oil: For gas or oil heating
systems,leavethefanoperationswitch
inthisfactory-setposition.(Thissettingis
forsystemsthatcontrolthefaninacall
forheat.)
• Electric or Heat Pump: Change the switch
tothissettingforheatpumporelectric
heatsystems.(Thissettingisforsystems
thatallowthethermostattocontrolthefan
inacallforheat,ifafanwireisconnected
to the Gterminal.)
Align the 4 tabs on the wallplate with
correspondingslotsonthebackof
thethermostat,thenpushgently
untilthethermostatsnapsinplace.
Thermostat mounting
Setfanoperationswitch.
Pushexcesswirebackinto
the wall opening.
Plugwallopeningwith
non-flammableinsulation.
Fan operation settings
Installation Guide
69-1929EFS—01 6
ENGLISH
Setup
1
0
MCR29402
Followtheprocedurebelowtoconfigurethethermostattomatchthe
installedheating/coolingsystem,andcustomizefeatureoperationasdesired.
Setup function Settings & options (factory default in bold)
1 System type
TH3110D only
0 Gas, oil or electric heat with air conditioning
1 Heatpump(5minutecompressorofftimeinheatingand
cooling)
5 Heating cycle rate
(CPH:cycles/hour)
TH3110D only
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 For hot water systems & furnacesofover90%efficiency
9 Forelectricfurnaces
[Othercyclerateoptions:2,4,6,7,8,10,11or12CPH]
6 Auxiliary heat
cycle rate (CPH)
TH3210D only
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 For hot water systems & furnacesofover90%efficiency
9 Forelectricfurnaces
[Othercyclerateoptions:2,4,6,7,8,10,11or12CPH]
8 Emergency heat
cycle rate (CPH)
TH3210D only
9 For electric emergency heat
1 For steam or gravity systems
3 For hot water systems & furnacesofover90%efficiency
5 Forgasoroilfurnacesoflessthan90%efficiency
[Othercyclerateoptions:2,4,6,7,8,10,11or12CPH]
9 Compressor
cycle rate (CPH)
3 Recommended for most compressors
[Othercyclerateoptions:1,2,4,5,or6CPH]
14 Temperature
display
0 Fahrenheit
1 Celsius
15 Compressor
protection
5 Five-minute compressor off time **See page 8
[Other options: 0, 1, 2, 3 or 4]
Function
number
Setting
To begin, press and hold the s and t
buttonsuntilthedisplaychanges.
Press t to change settings.
Press stoadvancetonextfunction.
Press and hold tstoexitandsavesettings.
Installer setup
PRO TH3000 series
7 69-1929EFS—01
ENGLISH
10
0
Te st
MCR29403
Aftercompletingtheinstallersetup,pressthesbuttonagaintobeginasys-
temtest.Followtheprocedurebelowtotesttheheatingandcoolingsystem.
1. Set SYSTEM switch to Heat.
2. Press ttoturnonandchecksystems(seetable,below).
3. Press tuntilsystemsturnoff.
4. Set SYSTEM switch to EmHeat and repeat steps 2-3 above (TH3210D only).
5. SetSYSTEM switch to Cool and repeat steps 2-3 above.
6. Press and hold ts to terminate test at any time.
Installer system test
System switch
System test
number
Systemstatus
10 Heating system
0 Heatandfanturnoff.
1 Heatturnson.
2 Auxiliaryheatturnson.
20 Emergency heat
0 Heatandfanturnoff.
1 Heatandfanturnon.
2 Auxiliaryheatturnson.
30 Cooling system
0 Compressorandfanturnoff.
1 Compressorandfanturnon.
70 Thermostat information
(forreferenceonly)
71 Softwarerevisionnumber(majorrevisions)
72 Softwarerevisionnumber(minorrevisions)
73 Configurationidentificationcode(major)
74 Configurationidentificationcode(minor)
75 Productionconfigurationdatecode(week)
76 Productionconfigurationdatecode(year)
System test System status
Shaded areas below apply only to TH3210D.
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressorprotectionisbypassedduringtesting.Topreventequipmentdamage,
avoidcyclingthecompressorquickly.
Installation Guide
Honeywell International Inc.
1985DouglasDriveNorth
GoldenValley,MN55422
http://customer.honeywell.com
Automation and Control Solutions
® U.S. Registered Trademark.
© 2009 Honeywell International Inc.
69-1929EFS—01M.S.05-09
Honeywell Limited-Honeywell Limitée
35DynamicDrive
Toronto,OntarioM1V4Z9
Printed in U.S.A. on recycled
papercontainingatleast10%
post-consumerpaperfibers.
Compressor Protection(SetupFunction15):Forcesthecompressortowaitafewminutes
beforerestarting,topreventdamage.Duringthewaittime,themessageCoolOnorHeatOn
(heatpumpsonly)willflashonthedisplay.
Please contact your distributor to order replacement parts.
Cover plate assembly*................................................. PartNumber50002883-001
12 pack of medium cover plates* ............................. PartNumber50007298-001
*Usetocovermarksleftbyoldthermostats.
Temperature Ranges
• Heat:40°to90°F(4.5°to32°C)
• Cool:50°to99°F(10°to37°C)
Operating Ambient Temperature
• 32°to120°F(0°to48.9°C)
Shipping Temperature
• -20°to120°F(-28.9°to48.9°C)
Operating Relative Humidity
• 5%to90%(non-condensing)
Physical Dimensions
• 3-13/16”Hx5-3/8”Wx1-1/4”D
97mmHx137mmWx32mmD
Electrical Ratings
System Voltage(50/60Hz) RunningCurrent
Heat(1ststage) 20-30Vac 0.02-1.0A
(Powerpile) 750mVDC 100mADC
Emergencyheat 20-30Vac 0.02-1.0A
Auxiliaryheat 20-30Vac 0.02-1.0A
Cooling 20-30Vac 0.02-1.0A
Accessories & replacement parts
Special functions
Specifications
Série PRO TH3000
Thermostatnumériquenonprogrammable
®MarquedéposéeauxÉ.-U. Brevets en instance.
© 2009 Honeywell International Inc.
Tousdroitsréservés.
Guide
d’installation
Doit être installé par un technicien d’expérience ayant
reçu la formation pertinente.
Lireattentivementlesinstructions.Lefaitdenepaslessuivrerisque
d’endommagerleproduitoudeconstituerundanger.
Besoin d’aide?
Pourobtenirdel’aidesurceproduitHoneywell,prièredeconsulterlesiteWeb
http://customer.honeywell.comoudesadresserauxServicesàlaclientèlede
Honeywell en composant le 1800468-1502
Le présent guide porte sur les modèles suivants :
• TH3110D:Poursystèmesà1étagedechauffage/1étagede
refroidissement
• TH3210D:Pourthermopompesà2étagesdechauffage/1étagede
refroidissementseulement
(Retirerlethermostatdelaplaquemuraleetleretournerpourtrouverle
numérodemodèle.)
Types de système
TH3110D:
• Gaz,mazoutouchauffage
électriqueavecclimatisation
• Airchaud,eauchaude,
appareilsdechauffageàhaut
rendement,thermopompesà1
étagedechauffage/1étagede
refroidissement,vapeuretgravité
• Chauffageseulement
• Chauffageseulementavec
ventilateur
• Refroidissementseulement
• Systèmesdechauffage750mV
TH3210D:
• Thermopompesà2étages
dechauffage/1étagede
refroidissement
Guide d’installation
69-1929EFS—01 2
FRANÇAIS
MCR29390
PULL HERE
HIPS
M29389
Installation de la plaque murale
Séparerlaplaquemuraleduther-
mostatcommel’indiquel’illustration
ci-contre,puissuivrelesdirectives
d’installation.
1. Fairepasserlesfilsparl’ouvertureréservée
auxfils.
2. Placerlaplaquemuralesurlemur,
mettredeniveauetmarqueraucrayon
l’emplacementdestrous.
3. Percerlestrousauxendroitsmarqués
àl’aided’uneperceuse,puisinsérerles
chevillesd’ancragefournies.
4. Apposerlaplaquemuralesurleschevilles,
insérerpuisresserrerlesvisdefixation.
Tirerlethermostatparlebaspourle
détacherdelaplaquemurale.
MISE EN GARDE : RISQUE DE CHOC ÉLECTRIQUE
Peutprovoquerdeschocsélectriquesouendommagerlematériel.Couper
l’alimentationélectriqueavantd’effectuerleraccordement.
AVIS SUR LE MERCURE
Silenouveauthermostatremplaceunancienrégulateurcontenantuncontactà
mercure,nepasmettrel’ancienrégulateurauxpoubelles.Communiqueravecle
servicelocaldecueillettedeschetspourobtenirdel’informationsurlerecyclageou
surlabonnefaçondedisposerd’unancienrégulateurcontenantuncontactàmercure.
Utiliserunemèchede3/16po
silemurestenplacoplâtre.
Ancragesmuraux
Troudufil Visdemontage
Utiliserunemèchede7/32po
silemurestenplâtre.
rie PRO TH3000
3 69-1929EFS—01
FRANÇAIS
MCR29391
CROGY
E
BAux L
M29393
CROGYWBRc
MCR29392
Options d’alimentation
BornierduTH3110D
Raccorder la borne Cpourl’alimentationprincipale
enc.a.(optionnelsidespilessontinstallées).
Garderlesfilsdans
cettezone
ombragée
Inrerlespilespourl’alimentationprincipale
oudesecours
TH3110D:
C Commun24Vc.a.Danslessystèmes
àdeuxtransformateurs,utiliserle
filcommundutransformateurde
refroidissement.
B Vanned’inversiondéclenchéeen
modedechauffage
R Alimentation24Vc.a.provenantdu
transformateurdechauffage
Rc Alimentation24Vc.a.provenantdu
transformateurderefroidissement
O Vanned’inversiondéclenchéeen
modederefroidissement
G Relaisdeventilateur
Y Contacteurducompresseur
W Relaisdechauffage
TH3210D:
C Commun24Vc.a.
B Vanned’inversiondéclenchéeen
modedechauffage
R Alimentation24Vc.a.
L Envoieunsignaldesortielorsque
raccordéeauchauffaged’urgence
O Vanned’inversiondéclenchéeen
modederefroidissement
G Relaisdeventilateur
Y Contacteurducompresseur
Aux Relaisdesystèmedechauffage
auxiliaire
E Relaisdechauffaged’urgence
Désignations des bornes
Câblage
Retirer le cavalier
instalenusine
seulementsile
systèmeestàdeux
transformateurs.
Guide d’installation
69-1929EFS—01 4
FRANÇAIS
Câblage
Thermopompes
2C/1F
TH3210D
C Commun24Vc.a. [3]
B Vanned’inversiondéclenchéeenmode
dechauffage[5]
R Alimentation [1]
L Envoieunsignaldesortielorsquerac-
cordéeauchauffaged’urgence [8]
O Vanned’inversiondéclenchéeenmode
derefroidissement[5]
G Relaisdeventilateur
Y Contacteurducompresseur
Aux Relaisdesystèmedechauffage
auxiliaire [9]
E Relaisdesystèmedechauffage
d’urgence[9]
Système 1C/1F
TH3110D
(1 transformateur)
C Commun24Vc.a.[3]
R [R+Rcreliéesparuncavalier]
Rc Alimentation [1]
G Relaisdeventilateur
Y Contacteurducompresseur
W Relaisdechauffage
Système 1C/1F
TH3110D
(2 transformateurs)
C Commun24Vc.a.[3, 4]
R Alimentation(transformateur,
chauffage)[1, 2]
Rc Alimentation(transformateur,
refroidissement)[1, 2]
G Relaisdeventilateur
Y Contacteurducompresseur
W Relaisdechauffage
Voir[remarques]ci-dessous
Thermopompe
1C/1F
TH3110D [7]
C Commun24Vc.a.[3]
B Vanned’inversiondéclenchéeen
modedechauffage[5]
R [R+Rcreliéesparuncavalier]
Rc Alimentation [1]
O Vanned’inversiondéclenchéeen
modederefroidissement[5]
G Relaisdeventilateur
Y Contacteurducompresseur[6]
W [W+Yreliéesparuncavalier]
Système de
chauffage
seulement
TH3110D
C Commun24Vc.a.[3]
R [R+Rcreliéesparuncavalier]
Rc Alimentation [1]
W Relaisdechauffage
Système de
chauffage
seulement avec
ventilateur
TH3110D
C Commun24Vc.a.[3]
R [R+Rcreliéesparuncavalier]
Rc Alimentation [1]
G Relaisdeventilateur
W Relaisdechauffage
Système de
refroidissement
seulement
TH3110D
C Commun24Vc.a.[3]
R [R+Rcreliéesparuncavalier]
Rc Alimentation [1]
G Relaisdeventilateur
Y Contacteurducompresseur
REMARQUES
Caractéristiquestechniquesdesfils:
Utiliserdufilpourthermostatdecalibre18à22.
Iln’estpasnécessaired’utiliserdufilblindé.
[1] Alimentation:Fourniraubesoinundispositif
decoupureetuneprotectioncontrelessur-
charges.
[2] Retirer le cavalierdanslecasdesystèmesà
deuxtransformateurs.
[3] Connexioncommune24Vc.a.enoption.
[4] Laconnexioncommunedoitprovenirdu
transformateurderefroidissement.
[5] UtilisersoitlaborneOsoitlaborneBpourla
vanne d’inversion.
[6] Utiliserunpetitboutdefil(nonfourni)pour
raccorderlesbornesWetY.
[7] Réglerlesélecteurduventilateuràlaposition
Thermopompe (Heat Pump)(voirpage5)
etconfigurerletypedesystèmeàthermo-
pompe(voirpage6).
[8] La borne L envoie unsignalcontinulorsque
lethermostatestrégléàEm.Heat. Raccorder
auxtableauxderégulationparzones
Honeywellpourqueletableaupasseau
chauffaged’urgence.
[9] InstalleruncavalierentrelesbornesAux
etEs’iln’yapasderelaisdechauffage
d’urgence.
Guide de câblage Systèmes classiques et thermopompes
CROGY
E
BAux L
M29393
CROGYW BRc
MCR29394
CROGYW BRc
MCR29395
CROGYWBRc
MCR29396
CR
O
W
B
Rc
MCR29397
CROGY BRc
MCR29399
rie PRO TH3000
5 69-1929EFS—01
FRANÇAIS
MCR29401
MCR29400
TH3110D seulement :
• Gaz ou mazout :Danslecasdesystèmes
dechauffageaugazouaumazout,laisser
lesélecteurduventilateuràlaposition
régléeenusine.(Ceréglageconvient
auxsystèmesquicommandentle
fonctionnementduventilateurlorsd’une
demandedechauffage.)
• Électricité ou thermopompe : Déplacer
lesélecteuràcettepositionsilesystème
estunethermopompeouunappareilde
chauffageélectrique.(Àcetteposition,le
thermostat commande la mise en marche
duventilateurlorsd’unedemandede
chaleursiunfilduventilateurestraccordé
àlaborneG.)
Fairecorrespondreles4languettes
delaplaquemuraleaveclesfentes
correspondantesaudosduther-
mostat,puispousserdoucement
jusqu’àcequelethermostatfasse
entendreundéclic.
Montage du thermostat
Réglerlesélecteurduventilateur.
Repousserlefilenexcèsdans
l’ouverturedanslemur.
Boucherl’ouverturedansle
muraumoyend’unisolant
ininflammable.
Réglage du ventilateur
Guide d’installation
69-1929EFS—01 6
FRANÇAIS
Setup
1
0
MCR29402
Suivrelesdirectivesci-dessouspourconfigurerlethermostatpourqu’ilcor-
respondeausystèmedechauffage-refroidissementinstallé,etpourperson-
nalisersonfonctionnement.
Fonctions Réglage et options (réglages de lusine en gras)
1 Types de système
TH3110D seulement
0 Gaz, mazout ou chauffage électrique avec
climatisation
1 Thermopompe(5minutesdetemporisationducompresseur
enchauffageetenrefroidissement)
5 Nombre de cycles
de chauffage à
l’heure (CPH : cycles
parheure)
TH3110D seulement
5 Pour les appareils au gaz ou au mazout à moins de
90 % d’efficacité
1 Systèmesàvapeurouàgravité
3 Systèmesetappareilsdechauffageàeauchaudeàplus
de90%d’efficacité
9 Pourappareilsdechauffageélectriques
[AutresCPHpossibles:2,4,6,7,8,10,11ou12CPH]
6 Cycles par heure du
chauffage auxiliaire
(CPH)
TH3210D seulement
5 Pour les appareils au gaz ou au mazout à moins de
90 % d’efficacité
1 Systèmesàvapeurouàgravité
3 Systèmesetappareilsdechauffageàeauchaudeàplus
de90%d’efficacité
9 Pourappareilsdechauffageélectriques
[AutresCPHpossibles:2,4,6,7,8,10,11ou12CPH]
8 Urgence Cycles par
heure du chauffage
d’urgence (CPH)
TH3210D seulement
9 Pour système de chauffage d’urgence à l’électricité
1 Systèmesàvapeurouàgravité
3 Systèmesetappareilsdechauffageàeauchaudeàplus
de90%d’efficacité
5 Pourlesappareilsaugazouaumazoutàmoinsde90%
d’efficacité
[AutresCPHpossibles:2,4,6,7,8,10,11ou12CPH]
9 Cycles par heure
du compresseur (CPH)
3 Recommandé pour la plupart des compresseurs
[Autresoptionspossibles:1,2,4,5ou6CPH
14 Affichage de la
température
0 Fahrenheit
1 Celsius
15 Protection du
compresseur
5 Temporisation de 5 minutes **Voir page 8
[Autresoptions:0,1,2,3ou4]
Numérodefonction Réglage
Pourcommencer,appuyersurlestouches
s et tetlesmaintenirenfoncésjusqu’à
cequel’affichagechange.
Appuyersurlatouchetpourmodifierles
réglages.
Appuyersurspourpasseràlafonctionsuivante.
Appuyersurlestouches ts et les maintenir
enfoncéespourquitteretenregistrerréglages.
Mode de configuration par l’installateur
rie PRO TH3000
7 69-1929EFS—01
FRANÇAIS
10
0
Te st
MCR29403
Unefoislaconfigurationterminée,appuyersurlatouchesànouveaupour
procéderàlavérificationdusystème.Suivrelesétapesci-dessouspourvéri-
fierlebonfonctionnementdusystèmedechauffageetderefroidissement.
1. RéglerlesélecteurduSYSTEMàHeat.
2. Appuyersurtpourmettrelessystèmesenmarcheetlesvérifier(voirletableauci-dessous).
3. Appuyersurtjusqu’àcequelessystèmessemettentàl’arrêt.
4. RéglerlesélecteurSYSTEMàEmHeatetrépéterlesétapes2et3ci-dessus(TH3210D
seulement).
5. RéglerlesélecteurSYSTEMàCool(refroidissement)etrépéterlesétapes2et3ci-dessus.
6. Appuyersurlestouches tsetlesmaintenirenfoncéespourmettrefinàlavérificationen
touttemps.
Test du système par l’installateur
Sélecteurdusystème
Numérodetest
dusystème
Étatdu
système
10 Système de
chauffage
0 Lesystèmedechauffageetleventilateursemettentàl’arrêt.
1 Lesystèmedechauffagesemetenmarche.
2 Lechauffageauxiliairesemetenmarche.
20 Chauffage
d’urgence
0 Lesystèmedechauffageetleventilateursemettentàl’arrêt.
1 Lesystèmedechauffageetleventilateursemettenten
marche.
2 Lechauffageauxiliairesemetenmarche.
30 Système de
refroidissement
0 Lecompresseuretleventilateursemettentàl’arrêt.
1 Lecompresseuretleventilateursemettentenmarche.
70 Information sur le
thermostat
(Pour référence
seulement)
71 Numéroderévisiondulogiciel(révisionsmajeures)
72 Numéroderévisiondulogiciel(révisionsmineures)
73 Coded’identificationdelaconfiguration(majeure)
74 Coded’identificationdelaconfiguration(mineure)
75 Codededatedelaconfigurationàlafabrication(semaine)
76 Codededatedelaconfigurationàlafabrication(année)
Test du système État du système
Les parties ombragées concernent seulement le TH3210D.
MISE EN GARDE : RISQUE DE DOMMAGE MARIEL
Lesystèmenetientpascomptedutempsd’arrêtminimalducompresseurpendant
letestparl’installateur.Pouréviterd’endommagerlematériel,éviterlescyclesde
fonctionnementtroprapidesducompresseur.
Guide d’installation
Honeywell International Inc.
1985DouglasDriveNorth
GoldenValley,MN55422
http://customer.honeywell.com
Solutions de régulation et d’automatisation
®MarquedéposéeauxÉ.-U.
© 2009 Honeywell International Inc.
69-1929EFS—01M.S.05-09
Honeywell Limited-Honeywell Limitée
35DynamicDrive
Toronto,OntarioM1V4Z9
ImpriméauxÉtats-Unissurdupapier
recyclécontenantaumoins10%de
fibresdepapierpost-consommation.
Protection du compresseur (Configurationdelafonction15):Cettefonctionobligele
compresseuràattendrequelquesminutesavantderedémarrer.Pendantcetteattente,lesmots
«CoolOn»(ou«HeatOn»silesystèmeutiliséestunethermopompe)clignotentàl’écran.
Prière de communiquer avec le distributeur pour commander des
pièces de rechange.
Ensemble de plaques de recouvrement* ................ Numérodepièce50002883-001
Boîte de 12 plaques de
recouvrement de taille moyenne* ............................. Numérodepièce50007298-001
*Sertàmasquerlesmarqueslaisséesparl’ancienthermostat.
Gammes de température
• Chauffage:4,5°à32°C(40°à90°F)
• Refroidissement:10°à37°C(50°à99°F)
Gamme de température
ambiante de service
• 0°à48,9°C(32°à120°F)
Température à l’expédition
• -28,9°à48,9°C(-20°à120°F)
Humidité relative de service
• 5%à90%(sanscondensation)
Encombrement
• 3-13/16poHx5-3/8poLx1-1/4poP
97mmHx137mmLx32mmP
Caractéristiques électriques nominales
Système Tension Intensité
(50/60Hz) deservice
Chauffage 20-30Vc.a. 0,02-1,0A
(1erétage)
(Powerpile) 750mVc.c. 100mAc.c.
Chauffaged’urgence 20-30Vc.a. 0,02-1,0A
Chauffageauxiliaire 20-30Vc.a. 0,02-1,0A
Refroidissement 20-30Vc.a. 0,02-1,0A
Accessoires/Pièces de rechange
Fonctions spéciales
Caractéristiques techniques
Serie PRO TH3000
Termostato digital no programable
Guía de
instalación
®MarcaregistradadelosEE.UU.Patentesentrámite.
© 2009, Honeywell International Inc.
Todos los derechos reservados.
Este manual incluye los siguientes modelos:
TH3110D:Parasistemasde1calentadory1refrigerador
• TH3210D:Parasistemasdebombadecalorpara2calentadoresy1refrigerador
únicamente
(Quiteeltermostatodelaplacaparaparedygíreloparaverelnúmerodemodelo).
Tipos de sistema
TH3110D:
Sistemadecalefacciónagas,
a aceite o eléctrico con aire
acondicionado
• Calefaccióndeaire,agua
caliente,sistemasdecalefacción
dealtaefectividad,bombas
de calor para 1 calentador y 1
refrigerador,vapor,gravedad
• Sólocalor
• Sólocalorconventilador
• Sólofrío
• Sistemasdecalefacción
de750mV
TH3210D:
• Sistemadebombadecalorpara
2calentadoresy1refrigerador
¿Necesita asistencia?
Paraobtenerasistenciarelacionadaconesteproducto,visite
http://customer.honeywell.comocomuníqueseconelnúmerogratuitodel
serviciodeatenciónalclientedeHoneywell,llamandoal1-800-468-1502
Debe ser instalado por un técnico
capacitado y experimentado
Leaestasinstruccionesatentamente.Sinosigueestasinstrucciones,
puededañarelproductouocasionarunriesgo.
69-1929EFS—01 2
Guía de instalación
ESPAÑOL
MCR29390
PULL HERE
HIPS
M29389
Instalación de la placa para pared
Quitelaplacaparapareddel
termostatocomosemuestra
alaizquierda,yluegosigalas
instruccionesparaelmontaje.
1. Haleloscablesatravésdelagujero
para los cables.
2. Coloquelaplacaenlapared,nivele
ymarquelasposicionesdelosagujeros.
3. Realiceagujerosenlasposiciones
marcadascomosemuestraabajo
eintroduzcalasanclasdeexpansión
con golpes leves.
4. Coloquelaplacaparaparedsobrelas
anclasdeexpansión,introduzcalos
tornillos de montaje y ajústelos.
Haledelaparteinferiorparaquitar
el termostato de la placa para pared.
PRECAUCIÓN: RIESGO ELÉCTRICO
Puedeocasionardescargaseléctricasodañarelequipo.Desconéctelodelafuente
deenergíaantesdecomenzarlainstalación.
Entablarroca,realice
agujerosde3/16".
Anclas de
expansión
Agujeroparaelcable Tornillos de montaje
Enyeso,realice
agujerosde7/32".
AVISO SOBRE EL MERCURIO
Encasodequeesteproductoreemplaceauncontrolquecontengamercurioentubo
sellado,evitearrojarelviejocontrolalabasura.Póngaseencontactoconlaautoridad
localparaelmanejodedesechosafindeobtenerinstruccionessobreelreciclado
ylacorrectaeliminacióndeestetipodedesechos.
3 69-1929EFS—01
Serie PRO TH3000
ESPAÑOL
MCR29391
CROGY
E
BAux L
M29393
CROGYWBRc
MCR29392
Semuestraelbloquedeterminales
del modelo TH3110D
Conecte C parasuministrarcorrienteCA
(opcionalsilasbateríasestáninstaladas).
Mantenga los cables
enestaárea
sombreada
Coloquelasbateríasparasuministro
deenergíaprincipaloderespaldo.
TH3110D:
C 24VCA.Paralossistemasde
2transformadores,utilicecables
comunesdesdeeltransformador
delarefrigeración.
B Válvulainversoraalimentada
durantelarefrigeración
R Corrientede24VCAdel
transformadordecalefacción
Rc Corrientede24VCAdel
transformadorderefrigeración
O Válvulainversoraalimentada
durantelarefrigeración
G Relé del ventilador
Y Interruptorautomáticodel
compresor
W Relé de calor
TH3210D:
C 24VCA
B Válvulainversoraalimentadadurante
larefrigeración
R Corrientede24VCA
L Cuandosefijaen“Em.Heat”,envía
unflujodeairecaliente
O Válvulainversoraalimentadadurante
larefrigeración
G Relé del ventilador
Y Interruptorautomáticodelcompresor
Aux Reléauxiliardecalor
E Relé de emergencia de calor
Designación de terminales
Cableado
Quiteelpuente
instalado en la
fábricasóloen
los sistemas con
dostransformadores.
Opciones de fuentes de energía
69-1929EFS—01 4
Guía de instalación
ESPAÑOL
Cableado
Sistema de bomba
de calor de
2 calentadores
y 1 refrigerador
TH3210D
C 24VCA[3]
B Válvulainversoraalimentadadurante
lacalefacción[5]
R Electricidad[1]
L Cuandosefijaen“Em.Heat”,enaunflujo
de aire caliente [8]
O Válvulainversoraalimentadadurante
larefrigeración[5]
G Relé del ventilador
Y Interruptorautomáticodelcompresor
Aux Reléauxiliardecalor[9]
E Relé de emergencia de calor [9]
Sistema de
1 calentador
y 1 refrigerador
TH3110D
(1 transformador)
C 24VCA[3]
R [R+Rcunidosporunpuente]
Rc Electricidad[1]
G Relé del ventilador
Y Interruptorautomáticodelcompresor
W Relé de calor
Sistema de
1 calentador y
1 refrigerador TH3110D
(2 transformadores)
C 24VCA[3,4]
R Electricidad(transformador
decalefacción)[1, 2]
Rc Electricidad(transformador
derefrigeración)[1, 2]
G Relé del ventilador
Y Interruptorautomáticodelcompresor
W Relé de calor
Sistema de bomba
de calor de
1 calentador y
1 refrigerador
TH3110D [7]
C 24VCA[3]
B Válvulainversoraalimentadadurantela
calefacción[5]
R [R+Rcunidosporunpuente]
Rc Electricidad[1]
O Válvulainversoraalimentadadurante
larefrigeración[5]
G Relé del ventilador
Y Interruptorautomáticodelcompresor [6]
W [W+Yunidosporunpuente]
Sistema sólo calor
TH3110D
C 24VCA [3]
R [R+Rcunidosporunpuente]
Rc Electricidad [1]
W Relé de calor
Sistema sólo calor
ventilador TH3110D
C 24VCA [3]
R [R+Rcunidosporunpuente]
Rc Electricidad[1]
G Relé del ventilador
W Relé de calor
Sistema sólo frío
TH3110D
C 24VCA [3]
R [R+Rcunidosporunpuente]
Rc Electricidad[1]
G Relé del ventilador
Y Interruptorautomáticodelcompresor
NOTAS
Especificacionesdelcable:
Use cable para termostato de calibre
18a22.Noserequierecableblindado.
[1] Fuentedealimentación.Proporciona
elmediodedesconexiónylaprotección
contrasobrecargasrequeridos.
[2] Para sistemas de2transformadores
quiteelpuente.
[3] Conexiónde24VCAopcional.
[4] Laconexióncomúndebeprovenir
deltransformadorderefrigeración.
[5] UseterminalesOoBparalaválvula
inversora.
[6] Useuntrozopequeñodecable(noincluido)
paraconectarlosterminalesWyY.
[7] Coloqueelinterruptordelventilador
enlaposición“Heat Pump” (bomba
de calor[vealapágina5])yconfigure
el tipo de sistema para bomba de calor
(vealapágina6).
[8] ElterminalLenvíaunflujocontinuo
deairecalientecuandoeltermostato
estáenlaposición“Em.Heat”. Conéctelo
alospanelesdeseparacióndeHoneywell
paracambiara“Em.Heat”.
[9] ColoqueelpuentedecampoentreAux
yEsinoexisteunrelédeemergencia
de calor.
Guía de cableado: sistemas convencionales y de bomba de calor
Vea[notas] abajo
CROGY
E
BAux L
M29393
CROGYW BRc
MCR29394
CROGYW BRc
MCR29395
CROGYWBRc
MCR29396
CR
O
W
B
Rc
MCR29397
CROGY BRc
MCR29399
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Honeywell PRO TH3110D Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI