AIREDALE SmartCool 11-233kW Precision Air Conditioner Technical Manual

Type
Technical Manual

6 to 200kW
Technical Manual
Original Instructions
SN, SR and SD
SmartCool Chilled Water
SmartCool™ 6 - 200kW Precision Air Conditioning
2SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Special Precautions



Hazard Intensity Levels
1. DANGER:
2. WARNING: 
3. CAUTION: 
4. IMPORTANT: 
5. NOTE: 
CAUTION


















IMPORTANT

3M Scotch-Weld™ 77 adhesive







Customer Services
Warranty, Commissioning & Maintenance
As standard, Airedale guarantees all non consumable parts only for a period of 12 months, variations tailored to suit
product and application are also available; please contact Airedale for full terms and details.
To further protect your investment in Airedale products, Airedale can provide full commissioning services,
comprehensive maintenance packages and service cover 24 hours a day, 365 days a year (UK mainland).
For a free quotation contact Airedale or your local Sales Engineer.
All Airedale products are designed in accordance with EU Directives regarding prevention of build up of water,
associated with the risk of contaminants such as legionella.
For eff ective prevention of such risk it is necessary that the equipment is maintained in accordance with Airedale
recommendations.
SafeCool
In addition to commissioning, a 24 hour, 7 days a week on-call service is available throughout the year to UK mainland
sites. This service will enable customers to contact a duty engineer outside normal working hours and receive
assistance over the telephone. The duty engineer can, if necessary, attend site, usually within 24 hours or less.
Full details will be forwarded on acceptance of the maintenance agreement.
Spares
A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our Spares department on
request.
Training
As well as our comprehensive range of products, Airedale off ers a modular range of Refrigeration and Air Conditioning
Training courses, for further information please contact Airedale.
Customer Services
For further assistance, please e-mail: [email protected] or telephone:
UK Sales Enquiries + 44 (0) 113 239 1000 [email protected]
International Enquiries + 44 (0) 113 239 1000 [email protected]
Spares Hot Line + 44 (0) 113 238 7878 [email protected]
Airedale Service + 44 (0) 113 239 1000 [email protected]
Technical Support + 44 (0) 113 239 1000 [email protected]
Training Enquiries + 44 (0) 113 239 1000 [email protected]
For information, visit us at our web site: www.airedale.com
Airedale Ltd. endeavours to ensure that the information in this document is correct and fairly stated, but none of the
statements are to be relied upon as a statement or representation of fact. Airedale Ltd. does not accept liability for any
error or omission, or for any reliance placed on the information contained in this document. The development of Airedale
products and services is continuous and the information in this document may not be up to date. It is important to check
the current position with Airedale Ltd. at the address stated. This document is not part of a contract or licence unless
expressly agreed. No part of this document may be reproduced or transmitted in any form or by any means, electronic
or mechanical, including photocopying, recording, or information storage and retrieval systems, for any purpose other
than the purchaser’s personal use, without the express written permission of Airedale Ltd.
©2018 Airedale International Air Conditioning Limited. All rights reserved. Printed in the UK.
Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance
being carried out in accordance with the recommendations provided during the warranty period.
Failure to have the maintenance procedures carried out will invalidate the warranty and any
liabilities by Airedale International Air Conditioning Ltd.
CAUTION
SmartCool™ 6 - 200kW
3
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Environmental Considerations
Units with supply water temperatures below +5°C
Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can
be exposed to freezing temperatures.
Units subject to ambient temperatures lower than 0°C
Glycol of an appropriate concentration (1) must be used within the system to ensure adequate freeze protection.
Please ensure that the concentration is capable of protection to at least 3K lower than ambient.
Water / glycol solution should be constantly circulated through all waterside pipework and coils to avoid static
water from freezing.
Ensure that pumps are started and running even during shut down periods, when the ambient is within 3K of the
solution freeze point (1) (i.e. if the solution freezes at 0°C, the pump must be operating at 3°C ambient).
Additional trace heating is provided for interconnecting pipework.
(1) Refer to your glycol supplier for details.
Environmental Policy
It is our policy to:
Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.
Train personnel in sound environmental practices.
Pursue opportunities to conserve resources, prevent pollution and eliminate waste.
Manufacture products in a responsible manner with minimum impact on the environment.
Reduce our use of chemicals and minimise their release to the environment.
Measure, control and verify environmental performance through internal and external audits.
Continually improve our environmental performance.
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:
Electromagnetic Compatibility Directive (EMC) 2014/30/EU
Machinery Directive (MD) 89/392/EEC version 2006/42/EC
Pressure Equipment Directive (PED) 2014/68/EU
Ecodesign 2009/125/EC
To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the
Declaration of Conformity, supplied with each product.
SmartCool™ 6 - 200kW Precision Air Conditioning
4SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Health and Safety
IMPORTANT
The information contained in this manual is critical to the correct operation and maintenance of the unit and should be
read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit.
Safety
The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/
electrical equipment, care must be taken if you are to obtain the best results.
Electrical installation commissioning and maintenance work on this equipment should be undertaken by competent and
trained personnel in accordance with local relevant standards and codes of practice.
A full hazard data sheet in accordance with COSHH regulations is available should this be required.
Personal Protective Equipment
Airedale recommends that personal protective equipment is used whilst installing, maintaining and commissioning
equipment.
Manual Handling
Some operations when servicing or maintaining the unit may require additional assistance with regard to manual
handling. This requirement is down to the discretion of the engineer.
Remember do not perform a lift that exceeds your ability.
Pressure Equipment Directive (2014/68/EU)
Minimum and Maximum Operation Temperature (TS) and Pressure (PS)
Waterside
Allowable Temperature Range (TS) = Min -5°C* to Max 40°C**
Maximum Allowable Pressure (PS) = 10 Barg
*Based on the waterside temperature in the unit off state in the lowest permitted ambient temperature.
**Based upon maximum machine running temperatures.
Ecodesign Directive 2009/125/EC
The product range within this document is designed in accordance to the European Ecodesign Directive 2009/125/EC.
The appendix at the rear section of the manual gives the product compliancy metrics. Products sold outside of the EU
are exempt from this directive.
When working with any air conditioning units ensure that the electrical isolator is switched off prior
to servicing or repair work and that there is no power to any part of the equipment.
Also ensure that there are no other power feeds to the unit such as fi re alarm circuits, BMS circuits
etc.
CAUTION
SmartCool™ 6 - 200kW
5
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Special Precautions 2
Introduction 8
Construction 9
 
 
System Congurations 10
SN, SR Nomenclature 12
SD Nomenclature 12
Unit Overview 13
SN, SR Range 13
SD Range 13
Chilled Water Components 15
 
Electrical Components 22
 
 
Controls 29
 
Installation Data 37
Dimensions 37
 
 
 
 
 
Incoming Services 45
 
Water Detection Tape Installation 49
 
Technical Data SN C000 Units 52
Mechanical and Electrical Data 52
Waterside Pressure Drop Data 53
Measurement of Sound Data 54
Sound Data 55
Interconnecting Wiring 56
Technical Data SR C000 Units 57
Mechanical and Electrical Data 57
Waterside Pressure Drop Data 58
Sound Data 59
Interconnecting Wiring 60
Technical Data SR C0C0 Units 61
Mechanical and Electrical Data 61
Waterside Pressure Drop Data 62
Sound Data 63
Contents
SmartCool™ 6 - 200kW Precision Air Conditioning
6SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Interconnecting Wiring 64
Technical Data SD CH00 Units 65
Mechanical and Electrical Data 65
Waterside Pressure Drop Data 66
Sound Data 68
Interconnecting Wiring 69
Technical Data SD CL00 Units 70
Mechanical and Electrical Data 70
Waterside Pressure Drop Data 71
Sound Data 73
Interconnecting Wiring 74
Technical Data SD CHCH Units 75
Mechanical and Electrical Data 75
Waterside Pressure Drop Data 76
Sound Data 78
Interconnecting Wiring 79
Technical Data SD CLCL Units 80
Mechanical and Electrical Data 80
Waterside Pressure Drop Data 81
Sound Data 83
Interconnecting Wiring 84
After Sales 85
Contents
SmartCool™ 6 - 200kW
7
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Introduction
Designed to provide environmental precision air conditioning for applications such as telecommunication facilities, data






Range 
SN C000 13 – 36
SR C000 35 – 98
SR C0C0 25 – 70
Range 
 105 – 255
 75 – 184
 92 – 215
 75 – 185
Moisture Content
Operating Band
Moisture Content kg/kg Dry Air
W
et
Bulb Temperature (°C)
Dry Bulb Temperature (°C)
4
0
6
0
7
0
80
%
90
2
0
%
1
0
%
10
1
5
2
0
2
5
5
0
15
18 27
1050 20 25 30 35 40
1
0
0
5
0
%
Relat
i
ve
En
t
ha
l
py
a
t satur
at
io
n
(
J/g
Dr
y
Air
)
12
ASHRAE Allowable Operating Envelope
ASHRAE Recommended Operating Envelope
Airedale Extended Operating Envelope
Airedale Operating Envelope
1
2
1 + 2
SmartCool™ 6 - 200kW Precision Air Conditioning
8SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
SN, SR SD
Precision Air Conditioning System




Construction
SN, SR Units














SD Units














SmartCool™ 6 - 200kW
9
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
System Congurations
SN, SR Range SD Range
SN C000 Units
 
 
SR C000 / C0C0 Units
 
 
SD CL00 / CLCL Units
 
 
SD CH00 / CHCH Units
 
 
SmartCool™ 6 - 200kW Precision Air Conditioning
10 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Single Circuit System Conguration

Dual Circuit System Conguration

SmartCool™ 6 - 200kW
11
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
SN, SR Nomenclature
S R 12 D 055 - - C000 - 0
SProduct Name
SmartCool
R
Regular Case (890mm deep)
N
Narrow Case (600mm deep)
06 684 mm
09 963 mm
12 1242 mm
15 1521 mm
18 1800 mm
DDownflow
010
095
-
-Separator
C000 Single Circuit CW
C0C0 Dual Circuit CW
-
-Separator
0400V / 3Ph +N / 50Hz
1380V / 3Ph +N / 60Hz
Nominal Cooling Capacity (kW)
Power Supply
Case Width
Flow Configuration
Variant
Cooling Configuration
SD Nomenclature
S D 31 D 215 - C H 0 0 - 0
SProduct Name SmartCool
DProduct Variant Dedicated Chilled Water
18 1800 mm
22 2200 mm
25 Case Width 2500 mm
31 3100 mm
35 3500 mm
DDownow
085-255 Nominal Cooling Capacity (kW)
-Separator
CChilled Water
HCoil Streamed For High Flow
LCoil Streamed For Low Flow
CChilled Water Circuit
0No Chilled Water Circuit
HCoil Streamed For High Flow
LCoil Streamed For Low Flow
-Separator
0400V / 3Ph + N / 50Hz
1Power Supply 380V / 3Ph +N / 60Hz
Flow Conguraon
Coil Type
Coil Type Second Circuit
Second Circuit
SmartCool™ 6 - 200kW Precision Air Conditioning
12 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Unit Overview
SN, SR Range
SD Range
Cooling Coil

Chilled Water Valves 



Chilled Water
Pipework




SmartCool™ 6 - 200kW
13
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Chilled Water Components
SN, SR Range
SD Range
Cooling Coil
Chilled Water Valves
Valves
Pipework
Connections
Cooling Coil
SmartCool™ 6 - 200kW Precision Air Conditioning
14 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Chilled Water Components

Range SN SR SD
Number of Circuits Single Single Dual Single Dual
Chilled Water
 
   
   – –

 ––– 
 
 
Threaded Connections 
Grooved Connections ––– 
 ––– 
  
Chilled Water Coil








SmartCool™ 6 - 200kW
15
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Grooved Water Connections

Threaded Water Pipe Connection

SN06 SN09 SN12 SR09 SR12 SR15 SR18 SD18 SD22 SD25 SD31 SD35
Sweat Copper Connection 
Threaded Pipe Connection 
Grooved Water Connection –––––––
 –––––––
  
Flanged Connections




Nominal
  
DN15 15 
DN20 22 
DN25 28 1
DN32 35 
DN40 42 
DN50 54 2
DN65 67 
Water Connection Types
SmartCool™ 6 - 200kW Precision Air Conditioning
16 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Chilled Water Valves
Chilled Water Valve Options
0-10 Volts DC 3 Port Chilled Water Regulating Valve (SN, SR Units)
0-10 Volts DC 3 Port Chilled Water Regulating Valve with Bypass (SN, SR Units)
SN06 SN09 SN12 SR09 SR12 SR15 SR18 SD18 SD22 SD25 SD31 SD35
2 Port Chilled Water Valves 
2 Port Chilled Water
Valves with 2 Port
Commissioning Valve –––––––
3 Port Chilled Water Valves –––––
3 Port Chilled Water
 –––––
  
Inlet
Outlet
0-10V DC 3 Port
Regulating Valve
BI
BI
BI BI
WTS
BL
DR
Coil(s)
M
Inlet
Outlet
0-10V DC 3 Port
Regulating Valve
Bypass Valve
BI
BI
BI
BI
WTS
BL
DR
Coil(s)
M
Binder Point
Bleed Valve
Drain Valve
Water Temperature Sensor
DR
WTS
BL
BI
M
M
0-10V DC 3 Port
Regulating Valve
0-10V DC 2 Port
Regulating Valve
2 Port Regulating Valve
SmartCool™ 6 - 200kW
17
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
0-10 Volts DC 2 Port Chilled Water Regulating Valve (SN, SR, SD Units)


0-10 Volts DC 2 Port Chilled Water Regulating Valve with bypass for auto commissioning (SD Units)






2 Port Valve
Inlet
Outlet
BI
BI
BI
WTS
BL
DR
Coil(s)
M
2 Port Valve
Inlet
Outlet
Bypass Valve
BI
BI WTS
BL
DR
Coil(s)
M
Binder Point
Bleed Valve
Drain Valve
Water Temperature Sensor
DR
WTS
BL
BI
M
M
0-10V DC 3 Port
Regulating Valve
0-10V DC 2 Port
Regulating Valve
2 Port Regulating Valve
SmartCool™ 6 - 200kW Precision Air Conditioning
18 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Pressure Independant Control Valve (PICV)


Valve
 DN20 DN25 DN32 DN40 DN50 DN65 DN80 DN100
 ---   - -
 ---   -
 ---   
 - - - -  
 - - - -   
 ---   -
 ---   -
 ---   
 - - - -  
 - - - -  
     - - -
 -    - -
 -     -
 - -     -
 - -     -
     - - -
      - -
 -     -
 -     -
 - -     -
  
Valve
DN20 DN25 DN32 DN40
 
 
 
 
  
  
  
  
SD Units
SN / SR Units
SmartCool™ 6 - 200kW
19
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
Airow Components
Fan & Motor Assembly






Range SN SR SD
Number of Circuits Single Single Dual Single Dual
Chilled Water
 – –
  
 
 
 
 
 
Constant Pressure Control 
  
SmartCool™ 6 - 200kW Precision Air Conditioning
20 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V2.0_07_2023
Introduction
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86

AIREDALE SmartCool 11-233kW Precision Air Conditioner Technical Manual

Type
Technical Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI