Envision R-410A Residential Installation guide

Category
Split-system air conditioners
Type
Installation guide
WaterFurnace
IM1615 10/08
Installation Information
Water Piping Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
Envision Series Outdoor Split Installation Manual
Geothermal/Water Source Outdoor Split Heat Pumps
• R-410ARefrigerant
• 2,3,4,5,6TonDualCapacity
1
NS SPLIT INSTALLATION MANUAL
Table of Contents
Nomenclature 2
PhysicalCharacteristics 2
GeneralInstallationInformation 3-6
ElectricalData 7
WaterPiping 8
AirHandlerNomenclature&CoilData 9
LineSetSizing 9
PhysicalData 10
EnvisionCoilNomenclature 11
RefrigerantCoilCompatability 11
HeatRecoveryUnit 12
WiringSchematics 13
ModesofOperation 14
OperationLogic 15
DIPSwitchSettings 16
Refrigeration 17-19
Pressure/TemperatureConversionChart 20
UnitOperatingParameters 21
PressureDropandRecommendedFlowRates 22
UnitStartup&Troubleshooting 23-26
PreventiveMaintenance 27
ReplacementProcedures 27
PhysicalDimensions 28
2
NS SPLIT INSTALLATION MANUAL
Model Nomenclature
1 2 3 4-6 7 8 9 10 11
N D S 049 A 1 0 A C
Model Type
N = Envision Coax Options
C = Copper
Compressor Type N = Cupronickel
D = Dual Capacity
Future Option
Cabinet Configuration A =
S = Outdoor Split
Hot Water Option
Unit Capacity 0 = None
Vintage Voltage
A = Current 1 = 208-230/60/1
Physical Characteristics
Model 026 038 049 064 72
Compressor (1 each)
Factory Charge R410a, oz [kg]
52
[1.47]
56
[1.59]
90
[2.55]
92
[2.61]
104
[2.95]
Coax and Water Piping
Coax & Piping Water Volume - gal [l]
0.7
[2.6]
1.3
[4.9]
1.6
[6.1]
1.6
[6.1]
2.3
[8.7]
Weight - Operating, lb [kg]
189
[186]
236
[107]
250
[113]
271
[123]
290
[132]
Weight - Packaged, lb [kg]
209
[95]
256
[116]
270
[122]
291
[132]
310
[141]
4/9/08
Notes:
All units have TXV expansion devices, and 1/2" [12.2mm] & 3/4" [19.1mm] electrical knockouts.
Dual Capacity Scroll
3
NS SPLIT INSTALLATION MANUAL
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electri-
cal components. Only trained and qualied service personnel should install, repair or service heating and air conditioning
equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing
lters. All other operations should be performed by trained service personnel. When working on heating and air conditioning
equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may
apply, such as the following safety measures:
Follow all safety codes.
Wear safety glasses and work gloves.
Use a quenching cloth for brazing operations.
Have a re extinguisher available for all brazing operations.
Moving and Storage
Move units in the normal “up” orientation. Units may be moved and stored per the information on the packaging. Do not
stack more than three units in total height. Do not attempt to move units while stacked. When the equipment is received, all
items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine
units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally
inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the
damage.
Split Unit Location
Locate the split compressor section away from areas that may disturb the customer and in a way that allows easy re-
moval of the access panels and the top of the cabinet. Provide sufcient room to make water, electrical and refrigerant line
connections and allow space for service personnel to perform maintenance. The NS split is approved for outdoor installa-
tion when properly installed.
Air Coil Location
Refer to the air handler manufacturer’s instructions for the blower coil unit for details on installing the air handling portion
of the system.
Condensate Drain
Follow the blower coil manufacturer’s instructions.
Duct System
All blower coil units/air coils must be installed as specied by the manufacturer’s installation instructions; however, the
following recommendations should considered to minimize noise and service problems.
An air lter must always be installed upstream of the air coil on the return air side of the air handler or furnace. If there
is limited access to the lter rack for normal maintenance, it is suggested that a return air lter grill be installed. Be sure that
the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the lter and plugging the air
coil.
In applications using galvanized metal ductwork, a exible duct connector is recommended on both the supply and
return air plenums to minimize vibration from the blower. To maximize sound attenuation of the unit blower, the supply and
return plenums should include an internal duct liner of 1-inch thick glass ber or be constructed of ductboard. Insulation is
usually not installed in the supply branch ducts. Ducts in unconditioned areas should be wrapped with a minimum of 1-inch
duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s
performance will be adversely affected. If the air handler is connected to existing ductwork, a previous check should have
WARNING:Beforeperformingserviceormaintenanceoperationsonasystem,turnoffmainpower
switchestobothunits.Turnoffaccessoryheaterpowerswitchifapplicable.Electricalshock
couldcausepersonalinjury.Installingandservicingheatingandairconditioningequipmentcan
behazardousduetosystempressureandelectricalcomponents.Onlytrainedandqualiedser-
vicepersonnelshouldinstall,repairorserviceheatingandairconditioningequipment.
Safety Considerations
General Installation Information
4
NS SPLIT INSTALLATION MANUAL
been made to assure that the duct system has the capacity to handle the air required for the unit application. If ducting
is too small, as in replacement of heating only systems, larger ductwork should be installed. All existing ductwork should
be checked for leaks and repairs made accordingly. The duct systems and diffusers should be sized to handle the design
airow quietly. If air noise or excessive airow is a problem, the blower speed can be changed to a lower speed to reduce
airow. This will reduce the performance of the unit slightly in heating; however, it will increase the temperature rise across
the air coil. Airow must still meet minimum requirements.
Equipment Selection
The following guidelines should be used when mating an Envision Split to an air handler/coil.
Select R-410A components only.
Match the air handler to the air handler coil data table.
Indoor matching adjustable TXV is factory installed on every air handler/coil. Fixed orice or cap tube systems
should not be used.
Utilizing Existing Coil or Air Handler
It is recommended that a new R-410A air handler be installed with an Envision Split considering the long term benets
of reliability, warranty, etc. versus the short term installation cost savings. However, the existing air handler may be retained
provided the following:
Coil currently is R-410A rated
Coil uses a TXV. No capillary or xed orice systems should be used
A life expectancy of more than 7 years remaining for the air handler and components
General Installation Information (cont.)
5
NS SPLIT INSTALLATION MANUAL
Air Handler Installation
Air handlers used with dual capacity units must be capable of operating with a minimum of 2 blower speeds. Refer to the
manufacturer’s instructions for the blower coil unit for details on installing the air handling portion of the system. All blower
coil units/air coils must be installed as specied by the manufacturer’s installations instructions. However, the following rec-
ommendations should be considered to minimize noise and service problems.
An air lter must always be installed upstream of the air coil on the return air side of the air handler of furnace. If there is
limited access to the lter rack for normal maintenance, it is suggested that a return air lter grille be installed. Be sure that
the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the lter and plugging the air
coil.
Ensure that the line set size is appropriate to the capacity of the unit (refer to page 9). Line sets should be routed as di-
rectly as possible, avoiding unnecessary bends or turns. All wall penetrations should be sealed properly. Line set should not
come into direct contact with water pipes, oor joists, wall studs, duct work, oors, walls and brick. Line set should not be
suspended from joists or studs with a rigid wire or strap which comes into direct contact with the tubing. Wide hanger strips
which conform to the shape of the tubing are recommended. Isolate hanger straps from line set insulation by using metal
sleeves bent to conform to the shape of insulation. Line set insulation should be pliable, and should completely surround the
refrigerant line.
Notes: Improper installation of equipment may result in undesirable noise levels in the living areas.
Connection to Air Coil
Figures 1 and 2 illustrate typical Envision Split installations. The table on page 9 shows typical lineset diameters and
maximum length. Linesets over 60 feet are not recommended. If the lineset is kinked or deformed and cannot be reformed,
the bad section of pipe should be replaced. A restricted lineset will affect unit performance. As in all R-410A equipment, a
reversible liquid line lter drier is required to insure all moisture is removed from the system. This drier should be replaced
whenever “breaking into” the system for service. All linesets should be insulated with a minimum of 1/2” closed cell insula-
tion. All exterior insulation should be painted with UV resistant paint or covering to insure long insulation life.
Figure 1: Typical Split System Application - Remote Blower Coil
General Installation Information (cont.)
Lineset
To Air Handler
Insulated
Suction Line
Return
Duct
Low
Voltage Wire
Disconnect
Remote Air Handler
(Maximum Recommended Distance is
60' Between Units)
Condensate Drain
(must be trapped)
Supply
Duct
Air
Handler
6
NS SPLIT INSTALLATION MANUAL
Dual Fuel Systems
Envision units can be connected to fossil fuel furnaces that include an A-coil or slab coil. Dual fuel installations utilize the
Envision heat pump for heating until the point that auxiliary heat is called for on the thermostat. At that point, the furnace
will be enabled and the heat pump will be disabled. The Envision heat pump provides air conditioning through the furnace’s
refrigerant coils.
Refer to the furnace manufacturer’s installation manual for the furnace installation, wiring and coil insertion. A
WaterFurnace Dual Fuel thermostat, a eld-installed DPST relay or dual capacity auxiliary heat relay is required. See Figure
2 for typical Dual Fuel application.
In add-on Envision Split applications, the coil should be located in the supply side of the furnace to avoid condensation
damage to the furnace heat exchanger. A high temperature limit should be installed upstream of the coil to de-energize the
compressor whenever the furnace is operating. Without this switch, the Envision Split will trip out on high pressure. A dual
fuel thermostat can remove the Y1 and Y2 calls when a W call is energized to allow gas furnace backup on an Envision Split
application. Refer to thermostat wiring on page 13 for details.
Thermostat
Wire From Furnace
Wire To
Thermostat
Up-Flow
Fossil Fuel
Furnace
Condensate
Drain
(must be trapped)
"A" or
Slab Coil
Supply Duct
Insulated
Suction Line
Return
Duct
Lineset To Air Handler
Disconnect
Figure 2: Typical Split System Heat Pump Coil Add-On Fossil Fuel Furnace
General Installation Information (cont.)
7
NS SPLIT INSTALLATION MANUAL
Rated Voltage
HWA Ext Total Min Max
Model Voltage Min/Max
Pump Loop Unit Circ Fuse/
MCC RLA LRA FLA FLA FLA Amp HACR
026 208-230/60/1 197/253 16.0 10.2 52.0 0.4 5.4 16.0 18.6 25
038 208-230/60/1 197/253 26.0 16.6 82.0 0.4 5.4 22.4 26.6 40
049 208-230/60/1 197/253 33.0 21.1 96.0 0.4 5.4 26.9 32.2 50
064 208-230/60/1 197/253 40.0 25.6 118.0 0.4 5.4 31.4 37.8 60
072 208-230/60/1 197/253 42.5 27.2 150.0 0.4 5.4 33.0 39.8 60
Rated Voltage of 208-230/60/1.
Rev.: 02/20/07
HACR circuit breaker in USA only.
Min/Max Voltage of 197/253.
All fuses Class RK-5.
Compressor
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage
wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. See unit electri-
cal data for fuse or cicuit breaker sizing information.
Electrical Data
Thermostat Wiring
Figure 3b: Thermostat Wiring for Dual Fuel Applications
Figure 3a: Thermostat Wiring
Electrical
Y1
Y2
O
R
C
C
R
Air Handler
Thermostat
24 VA C
Common Common
24 VA C
Reversing Valve
2nd Stage Compressor
1st Stage Compressor
Y1
Y2
O
R
C
G
G
Fan
W
W
Ty pical EZ Wiring Diagram
P1
Air Handler transformer must be at least 75 VA.
L
Lo
Fault Signal
Envision Split
Y1
Y2
O
R
C
L
C
R
Fossil Fuel
Furnace
Thermostat
24 VAC
Common Common
24 VAC
Fault Signal
Reversing Valve
2nd Stage Compressor
1st Stage Compressor
Y1
Y2
O
R
C
LO
G
G
Fan
W
W
Auxiliary Heat Relay
Note: Field installed DPST dual fuel relay
(Required for dual fuel installation)
Auxiliary Heat Relay
P2
P1
Shut
Down
= chassis
Envision Split
Auxiliary
Heat Relay
8
NS SPLIT INSTALLATION MANUAL
Water Piping
Residential NS split units are supplied standard with GeoLink swivel connections with P.T. ports.
CAUTION:Waterpipingexposedtooutsidetemperaturesmaybesubjecttofreezing.
Water Piping
The proper water ow must be provided to each unit whenever the unit operates. To assure proper ow, use pressure/
temperature ports to determine the ow rate. These ports should be located at the supply and return water connections on
the unit. The proper ow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-
to-water heat exchanger.
Closed Loop - Earth coupled Systems (Outdoor Installations)
Locate unit on an air pad with access hole as shown below. When mounting on an existing concrete pad, holes must
be bored through to accommodate 1 1/4-inch P.E. pipe with 1/2-inch insulation.
Connecting To Earth Loop
The earth loop trench should be continued directly under the unit as shown in Figure 4. Make the connections to op-
tional ttings from the loop circulator pump(s) and insure proper backll to support the loop pipe during trench settling. All 1
1/4-inch piping should be insulated with a minimum of 1/2-inch closed cell insulation from below the ground surface to the
loop circulator.
IMPORTANT
- Afreezesensingthermostatisinstalledintheunittoautomaticallystartloopcirculator
pumpiflooptemperaturedropsbelow20°F.Loopfreezesensingshouldalsobemaintainedtothe
lowesttemperaturetheinsulatedloopmayencounterinthecaseofpowerfailure.
Flow Center Installation
Flow centers FC1-GL or FC2-GL, as needed, may be
internally mounted on the NDS splits, Two stub tubes with
barbs are pre connected to the coax. Two tubes with brass
ttings, to adapt to the ow center, 2 hoses to connect
between the two sets of tubes, and four hose clamps are in-
cluded with each NDS unit. The brass adapter ttings have
plastic swivel connectors and are also internally threaded to
accept 1” NPT ttings.
NOTE: For ease of installation, attach provided hoses to
coax rst and then trim to t to elbows on ow center.
Loop Supply
and Return
Piping
Figure 4: Typical Split System Outdoor Installation Using
Closed Loop
9
NS SPLIT INSTALLATION MANUAL
Air Handler Coil Data
Line Set Sizes
Unit Air Factory
Size Handler
Suction Liquid Suction Liquid Suction Liquid
Charge (oz.)
NDS026 NAH026 5/8" OD 3/8" OD 3/4" OD 3/8" OD 3/4" OD 1/2" OD 52
NDS038 NAH036 5/8" OD 3/8" OD 3/4" OD 3/8" OD 3/4" OD 1/2" OD 56
NDS049 NAH048 3/4" OD 3/8" OD 7/8" OD 3/8" OD 7/8" OD 1/2" OD 90
NDS064 NAH060 7/8" OD 1/2" OD 7/8" OD 1/2" OD 1-1/8" OD 1/2" OD 92
NDS072 NAH060 7/8" OD 1/2" OD 7/8" OD 1/2" OD 1-1/8" OD 1/2" OD 104
Notes: Lineset charge for R410A is 0.50 oz. per ft. for 3/8" and 1.0 oz. per ft. for 1/2" tube. Rev.: 4/1/08
Initial Total System Charge = Factory Split charge + lineset charge + 20 oz, then adjust charge by subcooling and superheat measurements.
20 feet 40 feet 60 feet
Air Handler Nomenclature
NAH 036 A 00 0 1 R
Model Type Air Coil
NAH = Envision Air Handler R = Refrigerant
H = Hydronic
Unit Capacity
Refrigerant Models Nom. CFM Motor
022 MBTUH 800 1 = ECM 208-230/60/1
026 MBTUH 925
030 MBTUH 980
036 MBTUH 1225
042 MBTUH 1425 Disconnect
048 MBTUH 1625 0 = No breaker installed (only on 5kW & 10 kW heaters )
060 MBTUH 1760 1 = Breaker installed (only on 15kW & 20kW heaters)
Hydronic Models
026 MBTUH 925
036 MBTUH 1225 Electric Heat
048 MBTUH 1625 00 = No electric heat
060 MBTUH 1760 05 = 5 kW (available on 022-036)
10 = 10 kW (available on 030-060)
Vintage
Note: Kit NAHBC must be ordered to field convert the NAH042-060 to bottomflow air discharge
15 = 15 kW (available on 042-060)
A = Current 20 = 20 kW (available on 060 only)
10
NS SPLIT INSTALLATION MANUAL
NAH022 NAH026 NAH030 NAH036 NAH042 NAH048 NAH060
Air Coil Total Face Area, ft2 [m2]
Tube outside diameter - in. [mm]
Number of rows
Fins per inch
Suction line connection - in. [mm] sweat
Liquid line connection - in. [mm] sweat
Nominal cooling capacity - tons [kW] 1.8 [6.44] 2.1 [7.59] 2.5 [8.79] 3 [10.55] 3.5 [12.30] 4 [14.06] 5 [17.58]
Condensate drain connection - (FPT) in. [mm]
Blower Wheel Size (Dia x W), in. [mm]
Blower motor type/speeds
Blower motor output - hp [W]
Filter Standard - 1" [51mm] MERV3 disposable, in. [mm]
Electrical characteristics (60hz)
Shipping weight - lbs. [kg]
Operating weight - lbs. [kg]
1/11/08
NAH026 NAH036 NAH048 NAH060
Air Coil Total Face Area, ft2 [m2]
Tube outside diameter - in. [mm]
Number of rows
Fins per inch
Water In connection - in. [mm] sweat
Water Out connection - in. [mm] sweat
Nominal cooling capacity - tons [kW] 2.1 [7.59] 3 [10.55] 4 [14.06] 5 [17.58]
Condensate drain connection - (FPT) in. [mm]
Blower Wheel Size (Dia x W), in. [mm]
Blower motor type/speeds
Blower motor output - hp [W]
Filter Standard - 1" [51mm] MERV3 disposable, in. [mm]
Electrical characteristics (60hz)
Shipping weight - lbs. [kg]
Operating weight - lbs. [kg]
3/11/08
220 [99.79]
200 [90.71]
208/230 - 1ph
ECM variable speed
1/2 [373] 1 [746]
20 x 24 [508 x 635]
3/4 [19.05]
11 x 10 [279 x 254]
Air Handler Model Number (Hydronic)
Hydronic
Coil
3
7/8 [22.22]
13
7/8 [22.22]
6.94 [0.64]
3/8 [9.52]
Air Handler Model Number (Refrigerant)
Evaporator
Coil
5.83 [0.54]
3/8 [9.52]
2 3
12
5/8 [15.87] 7/8 [22.22]
3/8 [9.52]
Refrigerant R-410a
3/4 [19.05]
11 x 10 [279 x 254]
ECM variable speed
1/2 [373] 1 [746]
20 x 24 [508 x 635]
208/230 - 1ph
215 [97.52] 220 [99.79]
195 [88.45] 200 [90.71]
NOTE: Water connection dimensions are O.D.
Physical Data
11
NS SPLIT INSTALLATION MANUAL
NR A C 026 C
Cabinet
Model Type
C = Encased
NR = Envision Refrigerant Coil
U = Uncased
NH = Envision Hydronic Coil
Capacity
Configuration Refrigerant Models
A = "A" Coil 026 MBTUH
036 MBTUH
048 MBTUH
Coil 060 MBTUH
Hydronic Models
060 MBTUH
Note: All Refrigerant Coils include TXV. The encased coil cabinet is designed for upflow applications.
Encased/Uncased Coil
Indoor Split Model
(Single)
Indoor Split Model
(Dual Capacity)
Outdoor Split Model
(Dual Capacity)
Recommended
Airow (CFM)
NRAC026* NSZ022 - 800
NRAC026* - NDZ026 NDS026 925
NRAC026* NSZ030 - - 980
NRAC036* NSZ036 - - 1225
NRAC036* - NDZ038 NDS038 1225
NRAC048* NSZ042 - - 1425
NRAC048* NSZ048 - - 1625
NRAC048* - NDZ049 NDS049 1625
NRAC060* NSZ060 - - 1760
NRAC060* - NDZ064 NDS064 1760
NRAC060* NSZ070 - - 1760
NRAC060* - NDZ072 NDS072 1760
7/14/08
Envision Coil Nomenclature
Refrigerant Coil Compatibility
12
NS SPLIT INSTALLATION MANUAL
Service valves have been provided inside the unit for connecting the discharge gas line to a water heating heat recov-
ery unit (see gure 5). To make the connections, close the service valves inside the unit by turning clockwise. Using a
recovery canister connect to either of the schrader ports on the DSH service valves and recover the small amount of refrig-
erant trapped inside of the U-tube. PriortobrazingensurethatallrefrigeranthasbeenremovedfromU-tube. Once
the refrigerant is removed, it is recommended that the tube be cut at the “U” to remove any excess oil that may be trapped.
(This will also allow for easier removal of the tubing with a torch, since each section can be removed independently). Ser-
vicevalvesmustbeprotectedtopreventoverheating. Unbraze the 1/2-inch O.D. U-tube and run tubing from the left
hand service valve to the inlet of the heat recovery unit and from the outlet of the heat recovery unit to the right hand of the
service valve. Typically the one way discharge line length should be limited to 25-30 feet and line size must be increased
depending on unit size and length of run. Follow the instructions supplied with the heat recovery unit for mounting location,
water piping, and start up. A typical installation is shown below.
IMPORTANT-Reopendischargelineservicevalvesbeforestartingupunit,butonlyafterleakchecking,
purging,andevacuatingnewdischargeline.
To
Compressor
Heat Recovery
Unit “In”
From
Heat Recovery
Unit “Out” to
Reversing
Valve
Insulated Line set
With UV Paint
To Air handler
Add-on
Hot Water
Generator with
Internal Pump
Cold
Drain Valve
Pipe Tee
Hot
Venting
Waste Valve or
Vent Coupling
Line set
To Hot Water
Generator
P/T Relief
Valve
Figure 5: Service Valves for Heat Recovery Unit Connections
Figure 6: Typical Hot Water Piping Layout
SIZE 1/2”OD 5/8”OD 3/4”OD
026-038 Up to 9 ft. Up to 25 ft. Up to 30 ft.
049 Up to 5 ft. Up to 13 ft. Up to 30 ft.
064 N/A Up to 9 ft. Up to 25 ft.
072 N/A Up to 6 ft. Up to 20 ft.
Maximum One-Way Line Length
Heat Recovery Unit for Domestic Hot Water
13
NS SPLIT INSTALLATION MANUAL
Wiring Schematics
Envision Series - Dual Capacity Split Wiring Schematic - 208-230/60/1
Fused L2
240V L1
HP
240V L2
P6
Microprocessor
Logic Control
(DC Voltage)
P1
Fused L2
R
C
CC-GND
NO
CR2
COM
NO NC
CR4
COM
F1-10A 240V
NO
CR1
COM
1
2
3
4
5
6
7
8
1
2
3
P4
1
2
3C
P2
Down
C
1
2
3
4
5
6
7
Shut
SL1 I n
Not
SL1 Out
Used
NOTE 2
Acc Com
Acc NC
Acc NO
1
2
3
P3
1 2 3
NO NC
CR3
COM
F1-10A 240V
6
5
4
8
7
P5
12
1
2
9
10
3
13
14
15
16
11
G
W
O
R
C
Y1
Y2
LO
On
SW1
1
2
3
4
5
6
7
8
9
10
11
12
On
SW3
On
SW2
1
2
3
4
5
6
7
8 Pulse L / Constant L
Not Used
Not Used
Fan / Comp
Loop / Well
Test / Norm
Outputs / Norm
Inputs / Norm
Dual/ Single Capacity
Normal/Finish on 2
nd
No RPM / RPM
Must be On
Envision / E Series or Premier
ECM2
Air Flow
Settings
1
2
3
4
5
Status LED PCB
SW4
R
R
R
R
R
G
Y
R
T
C
NOTE 1
SL1 I n
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOT USED
NOT USED
CC
CCHI
Fused L1
Black (7)
RV
FP
Field Selection Dips - #1 On, #6 On, #7 On
Not Used
FP thermistor (loop<15°F,well <30°F) Lockout
High Pressure
Low Pressure / Comfort Alert
Not Used
Microprocessor malfunction*
Not Used
Not Used
Drain
Water Flow
High Press
Low Press/ CA
Air Flow
Status
DHW Limit
DHW off
LED Normal Display Mode
#1 Off, #6 On, #7 On
Not Used
FP thermistor (loop<15°F, well<30°F)
High Pressure
Low Pressure / Comfort Alert
Not Used
Not Used
Not Used
Not Used
Current Fault Status
#6 Off, #7 On
Y1
Y2
O
Not Used
Not Used
SL1
SL2
Inputs
#6 On, #7 Off
Lo Capacity Compressor
RV
FAN
Not Used
Loop Pump 1
Outputs
#6 Off, #7 Off
Not Used
Outputs2
Diagnostic Modes
*Green LED not flashing
Hi Capacity Compressor
Loop Pump 2
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not UsedNot UsedNot Used
Tan
Orange
Orange
Not Used
Not Used
Yellow
Yellow
LP
Blue
Blue
Black
Black
L
Comfort Alert
NO TE 5
CC
Comfort
Alert
R
Y
C
Y2
C
S
R
Unit Power
208-230/60/1
G
L2 L1
CC
Comfort Alert
Red Black
Blue
CS
+
-
DC SOL
Run
Capacitor
NOTE 6
Y 2
Y
L
R
C
DC
Sol
Data
Port
Comfort Alert
Physical Layout
POWER
ALERT
TRIP
Envision Logic Board - Physical Layout
1 2 3
1
P4
OnOff
SW1
240V - L2
240V - L1
Fused L2
Fused L2
Fused L2
F1
F1
R
R
Microprocessor
Premier 2 Logic Board
CR2- Loop
Pump
N.O.
240V - L2
240V - L1
C
C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
P6
1
2
3
4
5
6
7
8
9
10
11
12
13
14
P5
Fused L2
Fused L1
CR1- DHW
Pump
N.O .
CC
CC-GND
CCLO
CCHI
1 2 3
P3
2
3
4
5
6
7
8
9
10
11
12
1
OnOff
SW2
2
3
4
5
6
7
8
1
OnOff
SW3
2
3
4
5
P1
1 2 3 4 5 6 7 8
2
3 4 5
P2
6 71
R C Y1 Y2 GOW L
Shut
Down
ACC
NO
ACC
NC
ACC
COM
C C
SL1
IN
SL 1
Out
SL 2
IN
SL 2
Out
N.O.
CR4-
Com
N.O.
CR3-
Com
N.C.
L2
L1
Heat
Recovery
Unit
Pump
Loop Pump(s)
1/2 HP 208-230/60/1
G
Pump
FP
Thermistor
Light Emitting Diode - Green
Relay Coil
Capacitor w/ Bleed Resistor
Switch - High Pressure
Switch - Low Pressure
Polarized Connector
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Fuse
CC -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
HP -
LP -
RV -
SW1 -
SW2 -
SW3 -
Compressor Contactor
Loop Pump Relay 1
Fuses
Freeze protection sensor
High Pressure Switch
Low Pressure Switch
Reversing Valve Coil
Not Used
DIP Package 8 Position
DIP Package 5 Position
Relay Contacts-
N.O., N.C.
G
T
1
3
2
P
L1
Loop Pump Relay 2
Not Used
CS -
Compressor Solenoid
Not Used
Legend
Notes
Yellow (8)
Gray (9)
Violet (10)
Black (1)
Violet (2)
Violet (3)
White (4)
Black (5)
Yellow (6)
Orange (14 )
Brown (15)
Tan (16)
Red (11)
Red (12)
Black Black
Green/Yellow
Crankcase Heater
Crankcase Heater
Not Used
Not Used
3
4
9
11
2
10
8
1
12
5
14
13
6
7
CA -
Comfort Alert
Connection of remote unit that does not have a loop pump for slave operation
24V Accessory relay (see SW 2-3 for description of operation)
Field installed DPDT dual fuel relay (Required for dual fuel installation)
DHW pump only in models with hot water generation option
Comfort Alert fault output to Premier Control Board
This switch allows the unit to down stage with the t-stat when OFF and finish on second stage when ON.
Finish second stage reduces stage changing in recip dual capacity compressors and should be ON for
unzoned Dual Cap E-Series or Premier 2 speed units
1 -
2 -
3 -
4 -
5 -
6 -
14
NS SPLIT INSTALLATION MANUAL
Heating Operation
Note: At rst power up, a four-minute time delay is employed before the compressor is energized.
Heat,1stStage(Y1)
The compressor and loop pumps are energized 10 seconds after the Y1 input.
Heat,2ndStage(Y1,Y2)DualCapacityUnits
The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum rst stage
compressor run time of 1 minute has expired.
The Comfort Alert will delay the second stage compressor until 5 seconds after it receives “Y2” from the board.
Cooling Operation
In all cooling operations, the reversing valve directly tracks the
“O”
input. Thus, anytime the
“O”
input is present, the
reversing valve will be energized.
Cool,1stStage(Y1,O)
The compressor and loop pumps are energized 10 seconds after the Y1 input.
Cool,2ndStage(Y1,Y2,O)DualCapacityUnits
The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum rst stage
compressor run time of 1 minute has expired.
The Comfort Alert will delay the second stage compressor until 5 seconds after it receives a “Y2” from the board.
Fan Only Operation
The Fan Only mode is controlled directly from the unit thermostat to the unit air handler. No input is given to the micro-
processor to operate the fan function.
Lockout Conditions
During lockout mode, the appropriate thermostat lockout LEDs (if available) will illuminate. The compressor and loop
pumps are de-energized and if the thermostat calls for third stage heating, emergency heat operation will occur.
Lockout modes of any kind can be reset at the thermostat after a 5-second waiting period, which restores normal
operation.
High Pressure
This lockout mode occurs immediately when the normally closed safety switch is momentarily opened.
Low Pressure
This lockout mode occurs when the normally closed switch is opened for 30 continuous seconds.
Freeze Sensing (Water Flow)
This lockout mode occurs when the freeze sensing thermistor temperature (located between the TXV and coax) is at or
below the selected freeze sensing point (well 30°F or loop 15°F) for 30 continuous seconds.
The unit also contains a secondary freeze sensing sensor located on the entering water line of the unit. If the loop
reaches a temperature of 20°F the secondary freeze sensing sensor will cycle the loop pumps "on" until the loop tempera-
ture rises to or above 25°F.
Modes of Operation
15
NS SPLIT INSTALLATION MANUAL
Operation Logic Data
OPERATIONLOGIC
HEATING COOLING
SL1-INON
STG1 STG2 STG3 EMERG STG1 STG2
DUALCAPACITYUNITS
Compressor-Lo
On Off Off Off On Off -
Compressor-Hi
Off On On Off Off On -
RevValve
Off Off Off Off On On -
Loop Pumps
On On On Off On On On
Secondary1-Out
On On On Off On On -
Secondary2-Out
Off On On Off Off On -
EmergLED
Off Off Off On Off Off -
T-StatSignal
Y1 Y1, Y2 Y1, Y2, W W Y1, O Y1, Y2, O -
16
NS SPLIT INSTALLATION MANUAL
DIP Switch Settings
DIPSWITCH
NUMBER
DESCRIPTION OFFPOSITION ONPOSITION
SW1 N/A NOTUSED N/A N/A
SW2
1
Service/TestMode-Allows control of “NORM” or “TEST” opera-
tional modes. Test mode accelerates most timing functions 16
times to allow faster troubleshooting. Test mode also allows view-
ing the “CURRENT” status of the fault inputs on the LED display.
Test Norm
2
FreezeSensingSetting
Allows eld selection of freeze thermistor fault sensing tempera-
tures for well water (30°F) or antifreeze-protected (15°F) earth
loops.
Loop
(Sensing 15° F)
Well
(Sensing 30° F)
3
AccessoryRelay
Allows eld selection of the accessory relay to operate with the
compressor or fan.
Fan Comp
4 NOT USED N/A N/A
5 NOT USED N/A N/A
6
InputDiagnostics-Allows viewing the inputs from the thermo-
stat to the control board such as Y1, Y2, O, G, W, SL1-In on the
LED display.
Diagnostic Inputs
viewed at LEDs
Normal Display
viewed at LEDs
7
OutputDiagnostics-Allows viewing the outputs from the control
board such as the compressor, reversing valve, blower, hot water
pump, and loop pump on the LED display.
Diagnostic
Outputs viewed at
LEDs
Normal
Display viewed
at LEDs
8
ThermostatSelection
Congures the control for a pulsed lockout signal (ComforTalk and
FaultFlash thermostats) or continuous 5 VAC lockout signal.
Pulsed “L”
signal
Continuous “L”
signal
SW3
1 Single or Dual Capacity Operation Dual Cap 1 Speed
2
Zoned/FinishonSecondStage
This switch allows the unit to down stage with the thermostat
when off and nish with second stage when on. Finish on second
stage reduces stage changing in reciprocating dual capacity
compressors.
Normal -
All other systems
Finish on 2nd
Unzoned Dual
Capacity
E-Series or
Premier 2 speed
3 ECM Fan Monitoring - Set for No PRM on split systems No RPM RPM
4 NOT USED N/A N/A
5
On dual capacity units this switch allows stage change: on the y
when off, and 1 minute delay when on. A delay is required on all
reciprocating dual capacity units.
Envision
E-Series or
Premier
17
NS SPLIT INSTALLATION MANUAL
The Envision series comes with a holding charge. The charge must be adjusted in the eld based on performance.
Refrigeration piping on the split consists of installing a brazed copper line set between the blower coil unit and the unit’s split
compressor section. To select the proper tube diameters for the installation, refer to the table on page 9. Line sets over 60
feet long are not recommended because of oil return and pressure drop problems. The suction line must always be insu-
lated. Handle and route the line sets carefully to avoid kinking or bending the tubes. If the line set is kinked or distorted and
it cannot be formed back into its original shape, the bad portion of the pipe should be replaced. A restricted line set will affect
the performance of the system.
Connection to Air Coil
Figures 1 and 2 illustrate typical Envision Split installations. The table on page 9 shows typical lineset diameters and
maximum length. As in all R-410A equipment, a reversible liquid line lter drier is required to insure all moisture is removed
from the system. This drier should be replaced whenever “breaking into” the system for service. All linesets should be
insulated with a minimum of 1/2” closed cell insulation. All insulation should be painted with UV resistant paint or covering to
insure long insulation life.
Fasten the copper line set to the blower coil unit as instructed by the coil installation instructions. Nitrogen should be bled
through the system at 2 to 3 PSI to prevent oxidation inside the refrigerant tubing. Use a low silver phos-copper braze alloy
on all brazed connections.
Braze line set to the service valve stubs on the
inside front of the split cabinet as shown in Figure 7.
Nitrogen should be bled through the system at 2 to
3 PSI to prevent oxidation contamination. Use a low
silver phos-copper braze alloy on all brazed connec-
tions. Envision split units are shipped with a factory
charge and service valves are not to be opened
until the line set has been leak tested, purged and
evacuated. Schrader cores should be removed
before brazing. A heat sink should be used on the
service valves and TXV to prevent damage caused
by excessive heat.
Refrigeration
Replace caps after
opening system
Service ports for
attaching refrigerant
gauges
Insulated
Suction Line
Braze
Connection
Liquid
Line
ccw
ccw
Figure 7: Typical Split System Refrigerant Line Connections
18
NS SPLIT INSTALLATION MANUAL
Leak Testing
The refrigeration line set must be pressurized and checked for leaks before purging and charging the unit. To pressurize
the line set, attach refrigerant gauges to the service ports and add an inert gas (nitrogen or dry carbon dioxide) until pres-
sure reaches 60 to 90 PSIG. Never use oxygen or acetylene to pressure test. Use an electronic leak detector or a good
quality bubble solution to detect leaks on all connections made in the eld. Check the service valve ports and stem for leaks
and all connections made in the eld. If a leak is found, repair it and repeat the above steps. For safety reasons do not pres-
surize the system above 150 psi. Purge pressure from line set. The system is now ready for evacuating and charging.
System Evacuation
Ensure that the line set and air coil are evacuated before opening service valves to the split unit. The line set must be
evacuated to at least 200 microns to remove the moisture and air that may still be in the line set and coil. Evacuate the sys-
tem through both service ports to prevent false readings on the gauge because of pressure drop through service ports.
Initial System Charge Calculation
The Envision unit comes with a factory pre-charge. This volume is not sufcient to run the system. Additional refrigerant
must be added for the lineset. This additional charge added to the factory pre-charge of the Envision unit should be esti-
mated using the following equation:
Addition to Factory Charge = (lineset length x oz. per ft) + (20 oz. for accumulator)
The lineset charge should be calculated by multiplying the length times 0.5 oz./ft for 3/8” liquid line and 1.0 oz/ft for 1/2”
liquid line in R-410A systems. The suction line will not hold ‘liquid’ and can be ignored for the calculation. This should result
in a slightly under-charged unit exhibiting low subcooling and high superheat. As charge is added, the subcooling should
rise and the superheat should fall until 8-16 degrees of superheat is reached when the TXV should be metering the system.
See operating details in the startup section of this manual for exact superheat and subcooling values.
Example: 038 with 40 foot of 3/8” liquid line.
Additional to be added = (40 ft x 0.5 oz./ft) + (20 oz. for accumulator)
= 40 oz.
Solution: 40 oz. should be added to the existing 56 oz. of factory charge as an initial charge.
Charging the System
Charge Method – After purging and evacuating the line set, fully open the service valves counterclockwise. Add R-410A
(liquid) into the liquid line service port until the pressure in the system reaches approximately 200 PSIG. Never add liquid
refrigerant into the suction side of a compressor. Start the unit and measure superheat and subcooling. Keep adding refrig-
erant until the unit meets the superheat and subcooling values on page 21.
Checking Superheat and Subcooling
Determining Superheat
Measure the temperature of the suction line at the point where the expansion valve bulb is clamped.
1.
Determine the suction pressure in the suction line by attaching refrigeration gauges to the schrader connection on the
2.
suction side of the compressor.
Convert the pressure obtained in Step 2 to the saturation temperature by using the R-410A Pressure/Temperature Con-
3.
version Chart on page 20.
Subtract the temperature obtained in Step 3 from Step 1. The difference is the amount of superheat for the unit. Refer to
4.
tables on page 21 for superheat ranges at specic entering water conditions.
Superheat Adjustment
TXV’s are factory set to a specic superheat; however, the superheat should be adjusted for the application. To adjust
the TXV to other superheat settings:
Remove the seal cap from the bottom of the valve.
1.
Turn the adjustment screw clockwise to increase superheat and counterclockwise to decrease superheat. One complete
2.
360° turn changes the superheat approximately 3-4°F, regardless of refrigerant type. You may need to allow as much as
30 minutes after the adjustment is made for the system to stabilize.
Refrigeration (continued)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32