LG AHBW096A0.EWGBATK Installation guide

Type
Installation guide
www.lg.com
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
P/NO : MFL69166507
TYPE : Air-to-Water Heat Pump
Original instruction
ENGLISH
TÜRKÇE
2 Air-to-Water Heat Pump
Air-to-Water Heat Pump Installation Manual
TABLE OF CONTENTS
1. SAFETY PRECAUTIONS..............................................................................................................3
2. INSTALLATION PARTS ................................................................................................................7
3. GENERAL INFORMATION ..........................................................................................................8
MODEL INFORMATION................................................................................................................8
COMPONENTS ............................................................................................................................9
ACCESSORIES ..........................................................................................................................12
4. INSTALLATION ...........................................................................................................................13
TRANSPORTING THE UNIT ......................................................................................................13
SELECTION OF THE BEST LOCATION ....................................................................................14
INSTALLATION CONDITIONS....................................................................................................15
INSTALLATION AT SEASIDE......................................................................................................16
SEASONAL WIND AND CAUTIONS IN WINTER.......................................................................16
FOUNDATION FOR INSTALLATION ..........................................................................................17
INSTALLATION SCENES ...........................................................................................................18
WATER PIPING AND WATER CIRCUIT CONNECTION............................................................21
WATER VOLUME AND EXPANSION VESSEL PRESSURE......................................................25
ELECTRICAL WIRING................................................................................................................26
CONNECTING CABLES.............................................................................................................28
WIRING OF MAIN POWER SUPPLY AND EQUIPMENT CAPACITY ........................................33
WATER CHARGING ...................................................................................................................34
INSTALLATION OF THE FINAL CHECK ....................................................................................35
5. ACCESSORIES INSTALLATION ................................................................................................36
INSTALLATION OF REMOTE CONTROLLER ...........................................................................36
THERMOSTAT ............................................................................................................................38
SANITARY WATER TANK AND SANITARY WATER TANK KIT .................................................42
DRY CONTACT...........................................................................................................................45
REMOTE TEMPERATURE SENSOR.........................................................................................46
3WAY VALVE ..............................................................................................................................47
AIR-VENT ...................................................................................................................................48
2WAY VALVE ..............................................................................................................................49
6. SYSTEM SET-UP ........................................................................................................................50
DIP SWITCH SETTING...............................................................................................................51
INSTALLER SETTING ................................................................................................................54
7. CHECK POINTS, MAINTENANCE AND TROUBLESHOOTING ..............................................69
CHECK LIST BEFORE STARTING OPERATION ......................................................................69
MAINTENANCE ..........................................................................................................................70
TEST RUN ..................................................................................................................................70
AIRBORNE NOISE EMISSION ..................................................................................................71
LIMITING CONCENTRATION ....................................................................................................71
VACUUM & CHARGE OF REFRIGERANT ................................................................................72
TROUBLESHOOTING ................................................................................................................75
Safety Precautions
Installation Manual 3
ENGLISH
Do not modify or extend the
power cable.
• There is risk of fire or electric
shock.
Do not install, remove, or
reinstall the unit by yourself
(customer).
• There is risk of fire, electric
shock, explosion, or injury.
For antifreeze, always
contact the dealer or an
authorized service center.
Almost the antifreeze is a toxic
product.
For installation, always
contact the dealer or an
Authorized Service Center.
• There is risk of fire, electric
shock, explosion, or injury.
Do not install the unit on a
defective installation stand.
• It may cause injury, accident,
or damage to the unit.
Be sure the installation area
does not
deteriorate with age.
I
f the base collapses, the unit could
fall with it, causing property damage,
unit failure, and personal injury.
1. Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be
followed.
n
Be sure to read before installing the unit.
n
Be sure to observe the cautions specified here as they include important items related to safety.
n
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified
by the following indications.
n Meanings of symbols used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
WARNING
n Installation
Be sure not to do.
Be sure to follow the instruction.
Do not use a defective or
underrated circuit breaker.
Use this appliance on a
dedicated circuit.
• There is risk of fire or electric
shock.
For electrical work, contact
the dealer, seller, a qualified
electrician, or an Authorized
Service Center.
• There is risk of fire or electric
shock.
Always ground the unit.
• There is risk of fire or electric
shock.
Install the panel and the cover
of control box securely.
• There is risk of fire or electric
shock.
Always install a dedicated
circuit and breaker.
Improper wiring or installation
may cause fire or electric shock.
Use the correctly rated
breaker or fuse.
• There is risk of fire or electric.
4 Air-to-Water Heat Pump
Safety Precautions
Take care to ensure that power
cable could not be pulled out or
damaged during operation.
There is risk of fire or electric shock.
Do not place anything on
the power cable.
There is risk of fire or electric shock.
Do not plug or unplug the power
supply plug during operation.
There is risk of fire or electric shock.
Do not install the water pipe
system as Open loop type.
• It may cause failure of unit.
Use a vacuum pump or inert
(nitrogen) gas when doing
leakage test or purging air. Do
not compress air or oxygen and
do not use flammable gases.
• There is the risk of death,
injury, fire or explosion.
Make sure the connected
condition of connector in
product after maintenance.
• Otherwise, it may cause
product damage.
Do not touch (operate) the
unit with wet hands.
• There is risk of fire or electric
shock.
Do not place a heater or other
appliances near the power cable.
• There is risk of fire or electric
shock.
Do not allow water to run
into electric parts.
• There is risk of fire, failure of
the unit, or electric shock.
Do not store or use flammable
gas or combustibles near the
unit.
There is risk of fire or failure of unit.
Do not use the unit in a
tightly closed space for a
long time.
It may cause damage to the unit.
When flammable gas leaks, turn off
the gas and open a window for
ventilation before turning the unit on.
There is risk of explosion or fire.
Do not touch leaked
refrigerant directly.
• There is risk of frostbite.
Do not touch any electric
part with wet hands. you
should be power off before
touching electric part.
• There is risk of electric shock
or fire.
Do not touch refrigerant pipe
and water pipe or any internal
parts while the unit is operating
or immediately after operation.
• There is risk of burns or
frostbite, personal injury.
If you touch the pipe or
internal parts, you should be
wear protection or wait time to
return to normal temperature.
Otherwise , it may cause burns
or frostbite, personal injury.
If strange sounds, or small or
smoke comes from unit, turn the
breaker off or disconnect the
power supply cable.
• There is risk of electric shock
or fire.
Stop operation and close the window
in storm or hurricane. If possible,
remove the unit from the window
before the hurricane arrives.
There is risk of property damage,
failure of unit, or electric shock.
Do not open the front cover of
the unit while operation. (Do not
touch the electrostatic filter, if
the unit is so equipped.)
• There is risk of physical injury,
electric shock, or unit failure.
n Operation
Safety Precautions
Installation Manual 5
ENGLISH
Turn the main power on 6
hours ago before the product
starting operation.
• Otherwise, it may cause
compressor damage.
Do not touch electric parts
for 10 minutes after main
power off.
• There is risk of physical injury,
electric shock.
The inside heater of product
may operate during stop
mode. It is intended to
protect the product.
Be careful that some part of
the control box are hot.
• There is risk of physical injury or
burns.
When the unit is soaked
(flooded or submerged),
contact an Authorized
Service Center.
• There is risk of fire or electric
shock.
Be cautious that water could
not be poured to the unit
directly.
• There is risk of fire, electric
shock, or unit damage.
Ventilate the unit from time
to time when operating it
together with a stove, etc.
• There is risk of fire or electric
shock.
Turn the main power off
when cleaning or
maintaining the unit.
• There is risk of electric shock.
Take care to ensure that
nobody could step on or fall
onto the unit.
• This could result in personal
injury and unit damage.
For installation, always
contact the dealer or an
Authorized Service Center.
There is risk of fire, electric shock,
explosion, or injury.
If the unit is not used for long
time, we strongly recommend
not to switch off the power
supply to the unit.
There is risk of water freezing.
Safety Precautions
6 Air-to-Water Heat Pump
n Installation
Always check for gas
(refrigerant) leakage after
installation or repair of unit.
• Low refrigerant levels may cause
failure of unit.
Keep level even when
installing the unit.
• To avoid vibration or water
leakage.
Use two or more people to
lift and transport the unit.
• Avoid personal injury.
n Operation
Do not use the unit for special
purposes, such as preserving
foods, works of art, etc.
• There is risk of damage or loss of
property.
Use a soft cloth to clean.
Do not use harsh
detergents, solvents, etc.
• There is risk of fire, electric
shock, or damage to the plastic
parts of the unit.
Do not step on or put
anything on the unit.
• There is risk of personal injury
and failure of unit.
CAUTION
Use a firm stool or ladder when cleaning or
maintaining the unit.
• Be careful and avoid personal injury.
Do not turn on the breaker or power under
condition that front panel, cabinet, top
cover, control box cover are removed or
opened.
• Otherwise, it may cause fire, electric shock,
explosion or death.
Installation Manual 7
ENGLISH
Installation Parts
2. Installation Parts
Before starting installation, please make it sure that all parts are found inside the unit box.
Item Image Quantity
Installation Manual
1
Owner's Manual 1
Remote Controller 1
Cable 1
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
TYPE : Air-to-Water Heat Pmup (For High Temperature)
P/NO : MFL67212807
OWNER’S MANUAL
AIR CONDITIONER
Please read this manual carefully before operating
your set and retain it for future reference.
P/NO : MFL67212706
www.lg.com
TYPE :
Air-to-Water Heat Pump (For High Temperature)
General Information
8 Air-to-Water Heat Pump
3. General Information
Model Information
With advanced inverter technology, is suitable for applications like under floor heating,
under floor cooling, and hot water generation. By Interfacing to various accessories user can
customize the range of the application.
In this chapter, general information of is presented to identify the installation
procedure. Before beginning installation, read this chapter carefully and find helpful information on
installation.
Model name and related information
* : tested under Eurovent Heating condition (inlet Water temperature 30 °C 35 °C at outdoor
ambient temperature 7 °C DB/ 6 °C WB)
** : tested under Eurovent Cooling condition (inlet Water temperature 23 °C 18 °C at outdoor
ambient temperature 36 °C DB/ 24 °C WB)
Unit
Capacity
Power Source (Unit) Chassis
Heating (kW)* Cooling (kW)**
AHBW056A0 4.99 4.99 220-240 V~ 50 Hz UN4
AHBW076A0 7.00 7.00 220-240 V~ 50 Hz UN4
AHBW096A0 9.00 9.00 220-240 V~ 50 Hz UN4
AHBW126A0 12.00 14.50 220-240 V~ 50 Hz UN3
AHBW146A0 14.00 15.50 220-240 V~ 50 Hz UN3
AHBW166A0 16.00 16.10 220-240 V~ 50 Hz UN3
AHBW128A0 12.00 14.50 380·415 V ~50 Hz UN3
AHBW148A0 14.00 15.50 380·415 V ~50 Hz UN3
AHBW168A0 16.00 16.10 380·415 V ~50 Hz UN3
General Information
Installation Manual 9
ENGLISH
Components
9 8
3
1 2
7
6
10
4
5
11
12
A
AB
B
Description
No Name Remarks
1 Entering water pipe PT 25.4mm(Female type)
2 Leaving water pipe PT 25.4mm(Female type)
3 Strainer Filtering and stacking particles inside circulating water
4 Electronic heater Providing additional heating capacity to the water circuit
5 Control box PCB and terminal blocks
6 Plate heat exchanger Heat exchange between refrigerant and water
7 Water pump Circulating the water
8 Pressure gage Indicates circulating water pressure
9 Safety valve Open at water pressure 3 bar
10 Expansion vassel Protecting components from water pressure
11
Main PCB assembly(Inverter)
This PCB controls the cycle parts of the unit
12
Main PCB assembly(Heater)
This PCB controls the functioning of the unit
AHBW056A0/AHBW076A0/AHBW096A0
General Information
10 Air-to-Water Heat Pump
9
1 2
12
11
3
8
6
4
10
7
5
A
A
B
B
Description
No Name Remarks
1 Entering water pipe PT 25.4mm(Female type)
2 Leaving water pipe PT 25.4mm(Female type)
3 Strainer Filtering and stacking particles inside circulating water
4 Electronic heater Providing additional heating capacity to the water circuit
5 Control box PCB and terminal blocks
6 Plate heat exchanger Heat exchange between refrigerant and water
7 Water pump Circulating the water
8 Pressure gage Indicates circulating water pressure
9 Safety valve Open at water pressure 3 bar
10 Expansion vassel Protecting components from water pressure
11
Main PCB assembly(Inverter)
This PCB controls the cycle parts of the unit
12
Main PCB assembly(Heater)
This PCB controls the functioning of the unit
AHBW126A0/AHBW146A0/AHBW166A0
General Information
Installation Manual 11
ENGLISH
1 2
12
11
AB
9
3
8
6
4
10
7
5
BA
Description
No Name Remarks
1 Entering water pipe PT 25.4mm(Female type)
2 Leaving water pipe PT 25.4mm(Female type)
3 Strainer Filtering and stacking particles inside circulating water
4 Electronic heater Providing additional heating capacity to the water circuit
5 Control box PCB and terminal blocks
6 Plate heat exchanger Heat exchange between refrigerant and water
7 Water pump Circulating the water
8 Pressure gage Indicates circulating water pressure
9 Safety valve Open at water pressure 3 bar
10 Expansion vassel Protecting components from water pressure
11
Main PCB assembly(Inverter)
This PCB controls the cycle parts of the unit
12
Main PCB assembly(Heater)
This PCB controls the functioning of the unit
AHBW128A0/AHBW148A0/AHBW168A0
General Information
12 Air-to-Water Heat Pump
Accessories
Accessories supported by LG Electronics
To extend the functionality of , there are various external auxiliary apparatus called as
“accessories”.
They are classified by "accessories" and "3
rd
party accessories" according to the manufacturer.
Accessories are presented LG Electronics, and 3
rd
party accessories are presented by related
manufacturers.
Accessories supported by 3
rd
party Companies
Item Purpose Model
Sanitary water tank kit
Remote air sensor
Dry contact
Sanitary water tank
To operate with sanitary water tank
To control by air temperature
To receive on & off external signal
To generate and store hot water
PHLTB
PQRSTA0
PQDSA
PHS02060310 : 200 liter, Single heating coil,
230 V~ 50 Hz 3 kW Electric heater
PHS02060320 : 200 liter, Double heating coil,
230 V~ 50 Hz 3 kW Electric heater
PHS03060310 : 300 liter, Single heating coil,
230 V~ 50 Hz 3 kW Electric heater
PHS03060320 : 300 liter, Double heating coil,
230 V~ 50 Hz 3 kW Electric heater
Item Purpose Specification
Thermostat To control by air temperature
Heating-Only type (230 V~)
Cooling / Heating type
(230 V~ with
mode selection switch)
3way valve and actuator
To control water flow for hot water
heating or floor heating
3 wire, SPDT (Single Pole Double
Throw) type, 230 V~
2way valve and actuator
To control water flow
for Fan Coil Unit
2 wire,NO(Normal Open)
or NC(Normal Closed)
type, 230 V~
Solar Heating System
To generate auxillary
heating energy for water tank
Installation
Installation Manual 13
ENGLISH
4. Installation
Transporting the Unit
• When carrying the suspended unit, pass the ropes between legs of base panel under the unit.
• Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
Attach the ropes to the unit at an angle of 40° or less.
• Use only accessories and parts which are of the designated specification when installing.
Sub line
40º or less
Locking points for
transportation ropes
Air outlet grille Intake hole
Corner
Handle
Forklift
Always hold the unit by the corners, as holding
it by the side intake holes on the casing may
cause them to deform.
Installation
14 Air-to-Water Heat Pump
Selection of The Best Location
1. Select space for installing unit, which will meet the following conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors by noise from unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• With space for air passage and service work shown next
• Because of the possibility of fire, do not install unit to the space where generation, inflow,
stagnation, and leakage of combustible gas is expected.
Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the unit in order to prevent any person or animal from
accessing the unit.
• If installation site is area of heavy snowfall, then the following directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
2. Select installation location considering following conditions to avoid bad condition when
additionally performing defrost operation.
• Install the unit at a place well ventilated and having a lot of sunshine in case of installing the
product at a place with a high humidity in winter (near beach, coast, lake, etc).
(Ex) Rooftop where sunshine always shines.
• Performance of heating will be reduced and preheat time of the unit may be lengthened in
case of installing the unit in winter at following location:
- Shade position with a narrow space
- Location with much moisture in neighboring floor.
- Location with much humidity around.
- Location where ventilation is good.
It is recommended to install the unit at a place with a lot of sunshine as possible as.
- Location where water gathers since the floor is not even.
3. When installing the unit in a place that is constantly exposed to a strong wind like a coast or on
a high story of a building, secure a normal fan operation by using a duct or a wind shield.
• Install the unit so that its discharge port faces to the wall of the building.
Keep a distance 300mm or more between the unit and the wall surface.
• Supposing the wind direction during the operation season of the air conditioner, install the
unit so that the discharge port is set at right angle to the wind direction.
Be very careful while carrying the unit.
- Do not have only one person carry the unit if it is more than 20 kg (44.1 lbs).
- PP bands are used to pack some products. Do not use them as a mean for transportation because
they are dangerous.
-
Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
- Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic
packaging bag may suffocate children to death.
- When carrying the unit, be sure to support it at 4-points. Carrying and lifting the unit with 3-point
support may make it unstable, resulting in a fall.
CAUTION
Installation
Installation Manual 15
ENGLISH
General considerations
• If a sunroof is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the heat exchanger is
not restricted.
• Ensure that the spaces indicated by arrows
around front, back and side of the unit.
• Do not place animals and plants in the path of
the warm air.
• Take the weight of the unit into account and
select a place where noise and vibration are
minimum.
• Select a place so that the warm air and noise
from the unit do not disturb neighbors.
• The surface of the ground or the structure
must be strong enough to bear the weight of
the unit.
Installation Conditions
More than
300mm
Fence or
obstacles
More than 700mm
More than 600mm
*Minimum *Minimum
300mm300mm
Sunroof
*Minimum
300mm
* : Please secure the space to install the shut-off
valve and strainer.
Installation
16 Air-to-Water Heat Pump
Installation at Seaside
Seasonal Wind and Cautions in Winter
• Sufficient measures are required in a snow area or severe cold area in winter so that unit can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the unit not to come in contact with snow directly. If snow piles up and freezes on the air suction hole,
the system may malfunction. If it is installed at snowy area, attach the hood to the system.
• Install the unit at the higher installation console by 500mm than the average snowfall (annual average snowfall)
if it is installed at the area with much snowfall.
Where snow accumulated on the upper part of the unit by more than 100mm, always remove snow for operation.
1. The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of
the unit. (If width of the frame is wider than that of the unit, snow may accumulate.)
2. Don't install the suction hole and discharge hole of the unit facing the seasonal wind.
Selecting the location
1) If the unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the unit on the opposite side of the sea wind direction.
- It should be strong enough like concrete to
prevent the sea wind from the sea.
- The height and width should be more than 150%
of the unit.
- It should be keep more than 700 mm of space
between unit and the windbreak for easy air
flow.
2) In case, to install the unit on the seaside, set up a windbreak not to be exposed to the sea wind.
3) Select a well-drained place.
CAUTION
1.
Unit should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the unit where it could be exposed to sea wind (salty wind) directly. It can result
corrosion on the unit. Corrosion, particularly on the condenser and evaporator fins, could cause
unit malfunc-tion or inefficient performance.
3. If unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise
itneeds additional anticorrosion treatment on the heat exchanger.
Sea wind
Windbreak
1. If you can’t meet above guide line in the seaside installation, please contact your supplier
for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat
exchanger by using water
Installation
Installation Manual 17
ENGLISH
Foundation for Installation
[Unit:mm]
Foundation bolt executing method
200
1012
361
Nut
75
75
200
Spring washer
Frame
Anti-vibration
materials
Four bolt are
required
3 thread ridges
H-Beam
Concrete
base
100
• Check the strength and level of the installation ground so that the unit will not cause any
operating vibration or noise after installation.
• Fix the unit securely by means of the foundation bolts. (Prepare 4sets of M12 foundation
bolts, nuts and washers each which are available on the market.)
• It is best to screw in the foundation bolts until their length are 20mm from the foundation
surface.
Pallet(Wood Support)
- Remove before Installation
WARNING
• Be sure to remove the Pallet(Wood Support)
of the bottom side of the unit Base Pan before
fixing the bolt. It may cause the unstable state
of the unit settlement, and may cause freezing
of the heat exchanger resulting in abnormal
operations.
• Be sure to remove the Pallet(Wood Support)
of the bottom side of the unit before welding.
Not removing Pallet(Wood Support) causes
hazard of fire during welding.
Installation
18 Air-to-Water Heat Pump
If is installed with pre-existing boiler, the boiler and should not be operated together. If
entering water temperature of is above 55 °C, the system will stop operation to
prevent mechanical damage of the unit. For detailed electric wiring and water piping, please contact
authorized installer.
Some installation scenes are presented for example. As these scenes are conceptual figures,
installer should optimize the installation scene according to the installation conditions.
CASE 1: Connecting heat emitters for heating and cooling
(Under floor loop, Fan coil unit, and Radiator)
R
A
T
Outdoor Indoor
Floor heating loopFan coil unit
Radiator
Room thermostat(field supply)
2way valve
(field supply)
By-pass valve(field supply)
Strainer (Mesh: 1 mm × 1 mm)
Remote controller
S
R
Air vent
Shut-off valve(field supply)
A
Installation Scenes
Note:
• Room thermostat
- Type of thermostat and specification should be complied with chapter 5 of the installation
manual.
• 2way valve
- It is important to install 2way valve to prevent dew condensation on the floor and radiator while
cooling mode.
- Type of 2way valve and specification should be complied with chapter 5 of the installation
manual.
- 2way valve should be installed at the supply side of the collector.
• By-pass valve
- To secure enough water flow rate, by-pass valve should be installed at the collector.
- By-pass valve should guarantee minimum water flow rate in any case. Minimum water flow rate
is described in water pump characteristics curve.
CAUTION
Installation
Installation Manual 19
ENGLISH
CASE 2:
Connecting sanitary water tank
(Under floor loop, Fan coil unit, and Radiator)
R
T
Outdoor Indoor
Floor heating loopFan coil unit
Sanitary
water
tank
Hot water
City water
Radiator
A
Room thermostat(Field supply)
2way valve
(Field supply)
3way valve
(Field supply)
By-pass valve(Field supply)
Air vent
Remote controller
A
R
Shut-off valve(field supply)
Note:
• Sanitary water tank
- It should be equipped with internal electric heater to generate sufficient heat energy in very cold
season.
• 3way valve
- Type of 3way valve and specification should be complied with chapter 5 of the installation
manual.
Installation
20 Air-to-Water Heat Pump
CASE 3: Connecting Solar thermal system
Solar heat source
Hot water
R
T
Outdoor Indoor
Floor heating loopFan coil unit
Sanitary
water
tank
City water
Radiator
Pump(Field supply)
Room thermostat(Field supply)
2way valve
(Field supply)
3way valve
(Field supply)
By-pass valve(Field supply)
Remote controller
R
Shut-off valve(field supply)
Note:
• Sanitary water tank
- It should have additional indirect heat exchanger to utilize heat energy by solar thermal system.
• Pump
- Maximum power consumption of pump should be less than 0.25kW.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77

LG AHBW096A0.EWGBATK Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI