Signature FC7502-LDT-250 User manual

Type
User manual
Fire Control Cable
PVC V75 insulated copper conductor Fire Alarm Cable.
Application: Evacuation system, smoke detectors and Alarms.
Conductor: Plain annealed Copper wire (AS1125)
Core Colour: Red, White Sheath Colour: Red
Standards: AS/NZS3808 (PVC)
Light Duty & Light Duty Twisted
Insulation: PVC V75 Sheath: PVC V75
Voltage: 250/250V
Ordinary Duty & Heavy Duty Twisted
Insulation: PVC V75 (OD), V90 (HD) Sheath: Easy tear PVC V75 (OD), 3V-90 (HD)
Voltage: 450/750V (OD), 0.6/1Kv (HD)
CAUTION
Low Voltage Should NOT be
connected to mains power supply
Electra Cables
Part No.
Nom.
area
mm²
Stranding
No./mm
Insulation
Thickness
mm
Sheath
Thickness
mm
Nom. O/D
mm
Amp
Rating
Maximum
Resistance at
20°C Ω/Km
FC7402LD
0.88
2x7/0.40
0.6
0.8
3.8x6.1
10
21.2
FC7502LD
1.5
2x7/0.50
0.6
0.8
4.1x6.7
15
13.6
Light Duty Twisted
FC7402LDT
0.88
2x7/0.40
0.6
0.8
6.4
10
21.2
FC7502LDT
1.5
2x7/0.50
0.6
0.8
7
15
13.6
Electra Cables
Part No.
Nom.
area
mm²
Stranding
No./mm
Insulation
Thickness
mm
Sheath
Thickness
mm
Nom. O/D
mm
Amp
Rating
Maximum
Resistance at
20°C Ω/Km
FC7502OD
1.5
2x7/0.50
0.6
0.9
4.6x7.6
15
13.6
Heavy Duty
FC7402HD
0.88
2x7/0.40
0.8
1.8
6.4x9.2
10
21.2
FC7502HD
1.5
2x7/0.50
0.8
1.8
6.7x9.8
15
13.6
  • Page 1 1