Socomec Fixed COSYS PFC Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Socomec Fixed COSYS PFC Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Fixed COSYS PFC system
Operating instructions
EN
Contents
EN
WARRANTY CONDITIONS _________________________3
GENERAL SAFETY AND USAGE
INSTRUCTIONS __________________________________4
SYSTEM DESCRIPTION ___________________________5
General points __________________________________5
Function ______________________________________5
Construction ___________________________________5
General characteristics ___________________________5
INSTALLATION ___________________________________ 6
Recommendations relating
to installation conditions __________________________6
Connecting the input cables ______________________6
Upstream protection and connection cross section ___6
Technical characteristics _________________________8
COMMISSIONING AND MAINTENANCE ___________10
Checking the equipment ________________________10
Powering up ___________________________________10
Maintenance __________________________________10
3
Fixed COSYS PFC system
Fixed COSYS PFC system - Ref.: 540538A
WARRANTY CONDITIONS
The warranty conditions are set out in the sales contract;
in all other cases, the following conditions shall apply.
The manufacturer guarantees its product against any
manufacturing or operating faults caused by errors
in design, choice of materials or manufacture, in
accordance with the conditions set out below.
The manufacturer may - without prior notice – modify
its product in order to bring it into line with the warranty
conditions or replace defective parts.
The manufacturer's warranty shall not apply in the
following cases:
Faults  caused  by  designs  or  parts  used  without 
consent, or supplied, by the buyer.
• Replacements or repairs resulting from normal wear 
and tear of parts and equipment
• Damage or injury caused by negligence on the user's
part
• Insufficient maintenance or incorrect use of products.
• PFC system not adapted to the network.
The warranty's validity period is 12 months following
installation of the equipment, and may not exceed 18
months from the supply date.
Parts replacements, repairs or modifications carried out
by the manufacturer during the warranty period may
under no circumstances be grounds for extending the
length of the warranty period.
In order to benefit from this warranty, buyers must
expressly inform the manufacturer - within a maximum
of 8 days, beyond which the warranty shall expire – of
any faults in the design, materials or manufacture, giving
precise evidence to support their claim.
Defective parts replaced free of charge by the
manufacturer must be made available to the
manufacturer, as they remain its sole property.
The warranty shall not apply if the buyer has carried out
modifications or repairs to the manufacturer's products
without its prior consent.
The manufacturer's liability is limited to the obligations
described above (repairs or replacements); all other
types of damage shall be excluded.
4
Fixed COSYS PFC system - Ref.: 540538A
GENERAL SAFETY AND USAGE
INSTRUCTIONS
a. This manual sets out the essential instructions relating
to safety, connection and use of the fixed PFC system.
b. This system must only be installed by specialist
personnel with the necessary skills.
c. The PFC system must be installed in a vertical
position.
d. The cable must be connected to earth before the
connections are made.
e. Do not expose the equipment to rain or splashes of
water.
f. Keep the enclosure clean using a dry cloth.
g.  We recommend that you keep this manual in a place
which is accessible to all.
h.  The maintenance and checking operations described
in the “Maintenance” paragraph on page 11 must be
carried out at least once every 12 months. Failure to
follow this instruction shall release Socomec from all
liability with regard to the incorrect operation of the
equipment and the consequences thereof.
i. The maintenance operations must only be carried out
by authorised personnel with the appropriate training.
j.This  system  satisfies  the  European  Community
directives applicable to this product. This is indicated
by the following marking:
k. Compliance with standards CEI 61439-1/-2 and 
    EN 61439-1/-2.
The conditions set out below are likely to
cause operating faults and reduce the PFC
system's service life:
Current, voltage and frequency which are not to
specification.
• The presence of harmonics.
Operation or storage outside the temperature
limits.
The use of switches without current limiting
resistors.
Operation: where there are shocks or vibrations,
excessive or rapid temperature variations, or in
an explosive or corrosive environment.
Installation at an altitude > 2,000 m or below sea
level.
5
Fixed COSYS PFC system
Fixed COSYS PFC system - Ref.: 540538A
SYSTEM DESCRIPTION
General points
Function
Construction
General characteristics
The equipment consists of a series of racks of capacitors 
installed in an enclosure. Depending on the models,
other equipment may be present:
• anti-harmonic device.
• fuse combination switch.
COSYS fixed PFC system are designed to offset variable
reactive energy. Reactive energy may be consumed by a
factory or production unit.
• Power from 17.5 to 60 kvar.
Harmonics from  0  to  100%  in 4 stages: PFC21,
PFC22, PFC23, PFC24.
• Cable input at the bottom (can be the top if required).
• Base plate optional
•  Thermal regulation with fan (depending on equipment).
• Self-healing capacitors.
•  Capacitor cut off from the automatic circuit in case of
removal.
• Steel panel enclosure colour RAL 7035.
• IP rating IP20, IP30 depending on model.
• Rated voltage: 400 V three-phase.
• Rated frequency: 50 Hz.
• Operating temperature: -5°C to 40°C. 
•  Tolerance on capacitor capacity value: -5, +5%. 
•  Discharge device on each bank: < 50 V after 1 minute.
• Capacitor internal connection: delta.
6
Fixed COSYS PFC system - Ref.: 540538A
INSTALLATION
Failure to follow the installation instructions contained in this manual may compromise the
operation and reliability of the PFC system.
Recommendations relating to installation conditions
Recommended operating temperature: between 15°C 
and 35°C.
Relative humidity without condensation: 90% max.
Maximum operating altitude: 2,000 m
Take all necessary precautions to prevent splashes of 
water, paint or other fluids.
The enclosure conforms to protection rating IP20.
It is essential to ensure that there is a clearance of 50cm 
above the PFC system to allow adequate ventilation.
Connecting the input cables
The power is supplied to the terminals provided for this
purpose.
The power, control and measurement cables should be
connected in accordance with the standards in force
and good practice.
The cable bushing plate should be refitted after the cable
gland or other cable passage system has been fitted.
Failure to follow this instruction may seriously
compromise the ventilation efficiency, reduce the
cabinet's level of protection and cause the formation of
hazardous material or objects.
Upstream protection and connection cross section
The selection and co-ordination of the protection
devices upstream of the PFC system depend on the
nominal current and cable fitting conditions.
The protection devices upstream of the PFC system
must conform to the safety standards in force.
The cross section of the cables should be adapted to
the power of the fixed PFC system. Cables should be
selected according to the current values shown in the
table below, which should be increased by a coefficient
of 1.43 in accordance with CEI 60831-1.
Fixed COSYS PFC system - Ref.: 540538A
7
Fixed COSYS PFC system
Technical characteristics
COSYS PFC21
Power
supply
I nominal Upstream protection Figure n° Height x Width x Depth Weight
Kvar A GG fuse (A) Fuserbloc (A)
(without
switch)
(with switch) mm mm with switch
Kg
Kg with
switch
10 14 16 Consult us 1 5 395x170x80 515x560x190 4 4
15 22 32 Consult us 2 5 395x240x80 515x560x190 6 6
20 29 50 Consult us 3 5 475x285x150 515x560x190 10 10
30 43 63 Consult us 3 5 475x285x150 515x560x190 11 11
40 58 100 Consult us 4 5 475x445x150 515x560x190 15 15
50 72 125 Consult us 4 5 475x445x150 515x560x190 16 16
60 87 125 Consult us 4 5 475x445x150 515x560x190 18 18
Power
supply
I nominal Upstream protection Figure n° Height x Width x Depth Weight
Kvar A GG fuse (A) Fuserbloc (A)
(without
switch)
(with switch) mm mm with switch
Kg
Kg with
switch
10 14 16 Consult us 6 6 811x600x286 811x600x286 50 50
15 22 32 Consult us 6 6 811x600x286 811x600x286 53 55
20 29 50 Consult us 6 6 811x600x286 811x600x286 55 57
30 43 63 Consult us 6 6 811x600x286 811x600x286 63 65
40 58 100 Consult us 6 6 811x600x286 811x600x286 72 75
50 72 125 Consult us 6 6 811x600x286 811x600x286 77 80
Power
supply
I nominal Upstream protection Figure n° Height x Width x Depth Weight
Kvar A GG fuse (A) Fuserbloc (A)
(without
switch)
(with switch) mm mm with switch
Kg
Kg with
switch
10 14 16 Consult us 6 6 811x600x286 811x600x286 50 50
15 22 32 Consult us 6 6 811x600x286 811x600x286 53 55
20 29 50 Consult us 6 6 811x600x286 811x600x286 55 57
30 43 63 Consult us 6 6 811x600x286 811x600x286 63 65
40 58 100 Consult us 6 6 811x600x286 811x600x286 72 75
50 72 125 Consult us 6 6 811x600x286 811x600x286 77 80
Power
supply
I nominal Upstream protection Figure n° Height x Width x Depth Weight
Kvar A GG fuse (A) Fuserbloc (A)
(without
switch)
(with switch) mm mm with switch
Kg
Kg with
switch
10 14 16 Consult us 6 6 811x600x286 811x600x286 50 50
15 22 32 Consult us 6 6 811x600x286 811x600x286 53 55
20 29 50 Consult us 6 6 811x600x286 811x600x286 55 57
30 43 63 Consult us 6 6 811x600x286 811x600x286 63 65
40 58 100 Consult us 6 6 811x600x286 811x600x286 72 75
50 72 125 Consult us 6 6 811x600x286 811x600x286 77 80
COSYS PFC22
COSYS PFC23
COSYS PFC24
INSTALLATION
8
Fixed COSYS PFC system - Ref.: 540538A
170
6.5
15
80
50
344
380
157
Figure 1
240
220
6.5
15
80
50
344
380
Figure 2
150
90
25 414
450
285
250
6.5
Figure 3
150
90
25 414
450
445
410
6.5
Figure 4
INSTALLATION
Fixed COSYS PFC system - Ref.: 540538A
9
Fixed COSYS PFC system
190
90
25 464
490
560
525
6.5
Figure 5
130
800200
600
275 11
11
65
1
Figure 6
INSTALLATION
1: base plate optional
10
Fixed COSYS PFC system - Ref.: 540538A
Checking the equipment
Before commissioning the equipment, ensure that all 
connections are correctly tightened, as the terminals
may become loose during transportation of the equip-
ment from the production plant to the site (switch).
Powering up
Once the operations in the previous paragraph have
been carried out, the equipment can be started by
closing the upstream panel protection and the PFC
system cabinet switch (depending on the model).
Maintenance
Routine maintenance of this equipment involves perio-
dically checking (at least once every year) the following 
components:
• Auxiliary circuit fuses
• Capacitor fuses
• Cleanliness of the ventilation grille and the filter to 
ensure proper ventilation of the enclosure
• Retightening of the terminals
•  Visual inspection of the capacitors by replacing those
that are causing deforming of the upper part of the
outer enclosure.
COMMISSIONING AND MAINTENANCE
SOCOMEC can also offer:
•maintenance
•audit
•start-up
•training for your staff
Fixed COSYS PFC system - Ref.: 540538A
11
Fixed COSYS PFC system
COMMISSIONING AND
MAINTENANCE
SOCOMEC - Ref.: 540538 A -  01/11
VALID FOR FRANCE
h EAd O ffICE
SOCOMEC GROUP
S.A. SOCOMEC capital
11 149 200 €
R.C.S. Strasbourg B 548 500 149
B.P. 60010 - 1, rue de Westhouse
F-67235 Benfeld Cedex - FRANCE
I ntERn A t IOn A L
SALES d E p ARt MEnt
SOCOMEC
1, rue de Westhouse - B.P. 60010
F - 67235 Benfeld Cedex - FRANCE
Tel. +33 (0)3 88 57 41 41 - Fax +33 (0)3 88 74 08 00
Socomec worldwide
I n EUROp E
BELGIUM
SOCOMEC BELGIUM
B - 1190 Brussel
Tel. +32 (0)2 340 02 30 - Fax +32 (0)2 346 28 99
FRANCE
SOCOMEC
F - 94132 Fontenay-sous-Bois Cedex
Tel. +33 (0)1 45 14 63 30 - Fax +33 (0)1 45 14 63 38
GERMANY
SOCOMEC GmbH
D - 76275 Ettlingen
Tel. +49 (0)7243 65 29 2 0 - Fax +49 (0)7243 65 29 2 13
ITALY
SOCOMEC Elettrotecnica s.r.l.
I - 20098 San Giuliano Milanese (MI)
Tel. +39 02 9849821 - Fax +39 02 98243310
SPAIN
SOCOMEC ELECTRO, S.L.
E - 08310 Argentona (Barcelona)
Tel. +34 93 741 60 67 - Fax. +34 93 757 49 52
ThE NEThERLANDS
SOCOMEC B.V.
NL - 3991 CD Houten
Tel. +31 (0)30 760 0901- Fax +31 (0)30 637 2166
ThE UNITED KINGDOM
SOCOMEC Ltd
Hitchin Hertfordshire SG4 0TY
Tel. +44 (0)1462 440033 - Fax +44 (0)1462 431143
I n ASIA
NORTh EAST ASIA
SOCOMEC CHINA Co. Ltd
P.R.C 200052 Shanghai - China
Tel. +86 (0)21 5298 9555 - Fax +86 (0)21 6228 3468
SOUTh EAST ASIA & PACIFIC
SOCOMEC SWITCHING AND PROTECTION
UBI TECHPARK - 408569 Singapore
Tel. +65 65 07 94 90 - Fax +65 65 47 86 93
SOUTh ASIA
SOCOMEC INDIA
122001 Gurgaon, Haryana - India
Tel. +91 124 4562 700 - Fax +91 124 4562 738
I n MIddLE EASt
UNITED ARAB EMIRATES
SOCOMEC Middle East
Dubai, U.A.E.
Tel. +971 (0) 4 29 98 441 - Fax +971 (0)4 29 98 449
I n n ORth AMERICA
USA, CANADA & MEXICO
SOCOMEC Inc
Cambridge, MA 02142 USA
Tel. +1 617 245 0447 - Fax +1 617 245 0437
www.socomec.com
Non contractual document. © 2012, Socomec SA. All rights reserved.
4e_couv_SCP_bleu_2012.indd 6 27/01/12 11:35
/