- PAGE 2 -
ACTIONPAC EMB RELEASE 1.3 JULY 2017
Mounting
• Onlyusethemountingbracketsprovided.
• Theheightoftheunitabovetheoorlevelshouldbe
chosen so that the centre of the panel is just above
normal eye level (approximately 1.5 m).
• Theunitshouldbeplacedinanaturallyventedarea
and this area should be considered re safe and free
from high levels of shock and vibration.
• Conditionsshouldnotarisewhichmayallowthe
temperature in this area to reach or exceed the
operating temperature of the unit.
• Donotlocatetheunitwhereaccesstoitsinternal
components and connections are restricted.
WARNING: Observe all health and safety procedures
when lifting or moving this equipment.
Preparation
• Onlytrainedandqualiedpersonnelshouldbe
allowed to install, replace or service this equipment.
Installation should be in accordance with the relevant
local safety standards.
• ThemainswiringshouldcomplywithIEC60227or
IEC60245.
• Aswitchorcircuitbreakershouldbeincludedaspart
of the installation.
• Theswitchorcircuitbreakershouldmeetthe
relevantrequirementsofIEC60947-1and
IEC60947-3.
• Theswitchorcircuitbreakershouldbeinclose
proximity to the equipment and be within easy reach
of the operator.
• Theswitchorcircuitbreakershouldbemarkedasthe
disconnecting device for the equipment and should
disconnect both poles of the supply.
• Theswitchorcircuitbreakershouldnotinterruptthe
protected earth conductor.
• ThisequipmentMUSTbeearthed.
Mounting Diagram
Panel sizes & weights
Panel sizes and weights are dependent on project
specic requirements.